11 REFRIGERATION COVER 26 - Flipbook - Page 20
GENERAL
iCO2RE OCU‑CR CO₂ Series · R744
Specifications and capacity tables.
R744
200VF5A
400VF8
400VF8A
1000VF8
1000VF8A*
1001VF8A**
2000VF8A
Compressor
MODEL
OCU-CR
Single
compressor
Single
compressor
Single
compressor
Single
compressor
Single
compressor
Single
compressor
Tandem
compressor
Refrigerants
R744
R744
R744
R744
R744
R744
R744
PED category
Ι
ΙΙ
ΙΙ
ΙΙ
ΙΙ
ΙΙ
ΙΙ
Application
MT / LT
MT
MT / LT
MT
MT / LT
MT / LT
MT / LT
220 - 230 - 240
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
Single phase
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Voltage
Power supply
V
Phase
Frequency
Hz
50
50
50
50
50
50
50
Cooling capacity at ET -35 °C AT
32 °C
Min ~ Max
kW
1,1 - 1,9
—
1,9 - 3,8
—
3,8 - 7,6
3,3 - 8,6
3,8 - 14,6
Cooling capacity at ET -10 °C AT
32 °C
Min ~ Max
kW
2,1 - 3,7
3,4 - 6,9
3,8 - 7,5
6,8 - 13,5
7,5 - 14,9
6,2 - 16,0
7,5 - 28,7
1,92
—
1,73
—
1,49
1,67
1,64
SEPR cooling at ET -10 °C AT 32 °C
3,83
3,17
3,20
2,62
2,86
3,00
3,10
Annual electricity consumption at ET -35 °C AT
32 °C
kWh/a
8 021
—
16 255
—
39 985
38 392
66 760
Annual electricity consumption at ET -10 °C AT
32 °C
kWh/a
6 797
13 384
14 488
32 815
32 409
32 822
57 076
Tentative data
SEPR freezing at ET -35 °C AT 32 °C
Multiple
Evaporator connection
Multiple
Multiple
Multiple
Multiple
Multiple
Multiple
Evaporation temperature
Min ~ Max
°C
-45 ~ -5
-20 ~ -5
-45 ~ -5
-20 ~ -5
-45 ~ -5
-45 ~ -5
-45 ~ -5
Ambient temperature
Min ~ Max
°C
-20 ~ +43
-20 ~ +45
-20 ~ +45
-20 ~ +43
-20 ~ +43
-20 ~ +45
-20 ~ +45
Suction
bar
80
80
80
80
80
80
80
Liquid
bar
120
80
80
80
80
Yes
Yes
Yes
Yes
220 - 230 - 240
220 - 230 - 240
220 - 230 - 240
Yes
Yes
Yes
PS line
User system external alarm. Non-voltage contact
Liquid tube electromagnetic valve output
Vac
Showcase operation ON / OFF signal. Digital input.
Non-voltage contact
Modbus communication line (RS485)
Ports
Compressor type
Dimension
WxHxD
mm
Weight
80
Yes
Yes
Yes
220 - 230 - 240
220 - 230 - 240
—
—
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
2- stage
rotary
2- stage
rotary
2- stage
rotary
2- stage
rotary
2- stage
rotary
2- stage
rotary
2- stage
rotary
900 x 930 x 437 1143 x 948 x 609 1143 x 948 x 609 890 x 1941 x 890 890 x 1941 x 890 890 x 1941 x 890 1190x1941x890
Kg
Connections 1)
80
70
136
149
293
320
315
494
Suction
Inch (mm)
3/8 (9,52)
1/2 (12,70)
1/2 (12,70)
3/4 (19,05)
3/4 (19,05)
3/4 (19,05)
7/8 (22,22)
Liquid
Inch (mm)
1/4 (6,35)
3/8 (9,52)
3/8 (9,52)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
3/4 (19,05)
25
50 2)
50 2)
100 2)
100 2)
100 2)
100 2)
Maximum recommended pipe distance
m
Air flow
m³/min
54
59
59
220
220
220
220
External static pressure
Pa
17
50
50
58
58
58
58
Ambient
temperature
°C
32
32
32
32
32
32
32
Evaporating
temperature
°C
-10
-35
-10
-10
-35
-10
-10
-35
-10
-35
-10
-35
Nominal load
ampere
A
7,94
7,26
6,14
7,2
6,2
12,6
12,6
11,6
13,9
TBC
24,31
20,49
Sound level 3)
dB(A)
Performance - additional data
35,5
33,0
36,1
36,0 4)
36,0 4)
39,5 (36,5 4))
42,0 (39,0 4))
1) These diameters correspond to the output of the unit. The required diameter must be calculated with Refrigeration designer available on PRO Club. 2) PZ‑68S (refrigeration oil) must be added according to
Refrigeration designer available on PRO Club. 3) ET ‑10 °C, at maximum speed, 10 m from product. 4) Performance in a silent mode. *CR1000VF8A: subject to availability. **Available in Summer 2026.
CHECK PAGES 28 - 31 FOR A WIDER SELECTION OF ACCESSORIES
45 °C
CO2
R744
HIGH EFFICIENCY
COMPRESSOR
SUPER QUIET
AMBIENT
TEMPERATURE *
ANTI CORROSION
COATING
HEAT RECOVERY
PORT
*45 °C AMBIENT TEMPERATURE: For OCU‑CR400VF8/A, OCU‑CR1001VF8A and OCU‑CR2000VF8A.
20
AUTOMATIC FAN
5
YEARS
COMPRESSOR
WARRANTY
BMS