11 REFRIGERATION COVER 26 - Flipbook - Page 36
GENERAL
NEW
NEW! iCOOL SE Series – OCU‑LRE – A2L‑ready LT
models · R454C / R455A / R448A / R449A
Specifications and capacity tables.
A2L
READY
Model
OCU-LRE012L05*
OCU-LRE022L05*
OCU-LRE030L05*
Compressor
Single Inverter
compressor
Single Inverter
compressor
Single Inverter
compressor
R454C, R455A, R448A,
R449A
R454C, R455A, R448A,
R449A
R454C, R455A, R448A,
R449A
Compatible refrigerants
PED category
I
I
I
Application
LT
LT
LT
Cooling capacity at ET -35 °C AT 32 °C,
R454C
Min ~ Max
kW
0,1 - 0,7
0,4 - 1,5
0,6 - 1,8
Cooling capacity at ET -10 °C AT 32 °C,
R454C
Min ~ Max
kW
—
—
—
SEPR freezing at ET -35 °C AT 32 °C
TBC
TBC
TBC
SEPR cooling at ET -10 °C AT 32 °C
TBC
TBC
TBC
Annual electricity consumption at ET -35 °C AT 32 °C
kWh/a
TBC
TBC
TBC
Annual electricity consumption at ET -10 °C AT 32 °C
kWh/a
TBC
TBC
TBC
COP at ET -35°C, AT 32 °C
TBC
TBC
TBC
COP at ET -10°C, AT 32 °C
TBC
TBC
TBC
12,4
Nominal operating current at ET -10 °C MT / -30 °C LT AT 32 °C and
230 - 400 V 50 Hz
A
5,5
9,5
Maximum operating current (in the most loaded phase at 230 - 400 V 50 Hz)
A
7,2
12,7
17
Maximum power consumption
kW
1,4
2,6
3,6
1 000 x 605 x 450
Dimensions
mm
1 000 x 605 x 450
1 000 x 605 x 450
Weight
WxHxD
kg
75
75
75
Sound level at 10 m
dB(A)
42,5
42,5
42,5
Fans x diameter
mm
1x450
1x450
1x450
Air flow
m³/h
3 600
3 600
V / ph / Hz
Tentative data
3 600
Fan power supply
220 - 240 / 1 / 50
220 - 240 / 1 / 50
220 - 240 / 1 / 50
Fan power consumption
W
170
170
170
Nominal fan current
A
1,4
1,4
1,4
C-6RVN63L0B
C-7RVN113L0B
C-7RVN153L0B
Condenser
Model
Compressor
Volumetric flow
m³/h
0,6 - 4,1
1,25 - 7,5
1,7 - 10,4
Rotation range
rps
30 - 90
30 - 90
30 - 90
Full load amperage
A
3,6
7,1
9,6
Peak current limit / Locked rotor amperage
A
15 / —
25 / —
25 / —
Current
Oil type
Connections
FV68S
FV68S
FV68S
Oil compressor charge
dm³
0,6
0,7
0,7
Crankcase heater power consumption
W
35
35
35
Suction
Inch
1/2
5/8
3/4
Inch
3/8
3/8
3/8
dm³
3,9
3,9
3,9
220 - 240 / 1 / 50
220 - 240 / 1 / 50
220 - 240 / 1 / 50
3x2,5
3x2,5
3x2,5
C16
C20
C20
m
20
20
20
Evaporator above
m
7
7
7
Evaporator below
m
7
7
7
Suction
Suction
Suction
19
Liquid
Liquid receiver
CU power
supply
Voltage
V / ph / Hz
Recommended minimum cable cross-section
mm²
Recommended minimum protection
Maximum recommended pipe distance
Maximum height distance
Which pipes needs to be insulated
Suction / liquid / both
Recommended insulation thickness
mm
19
19
Maximum quantity of evaporators connected
Qty.
3
3
3
Evaporation temperature
Min ~ Max
°C
-35 ~ -15
-35 ~ -15
-35 ~ -15
Ambient temperature
Min ~ Max
°C
-20 ~ 43
-20 ~ 43
-20 ~ 43
*Available in Autumn 2026.
CHECK PAGE 57 FOR A SELECTION OF ACCESSORIES
43 °C
HIGH EFFICIENCY
COMPRESSOR
36
SUPER QUIET
AMBIENT
TEMPERATURE
AUTOMATIC FAN
BMS
CONNECTIVITY