RANGE
MODEL
REFRIGERATION – iCOOL
LCU-KSC280M08 LCU-KSC400M08 LCU-KRC020L08 LCU-KRC035L08 LCU-KRC050L08 LCU-KSC090L08
Compressor
Tandem
compressor
Inverter +
ON / OFF
Tandem
compressor
Inverter +
ON / OFF
Single Inverter
compressor
Single Inverter
compressor
Single Inverter
compressor
Single Inverter
compressor
Compatible refrigerants
R448A, R449A,
R134a, R513A
R448A, R449A,
R134a, R513A
R448A, R449A
R448A, R449A
R448A, R449A
R448A, R449A
PED category
II
II
II
I
II
II
Application
MT
MT
LT
LT
LT
LT
Cooling capacity at ET -35 °C CT 45 °C
Min ~ Max
kW
—
—
0,2 - 1,6
0,3 - 2,4
1,0 - 4,3
1,8 - 6,9
Cooling capacity at ET -10 °C CT 45 °C
Min ~ Max
kW
4,6 - 27,7
5,4 - 38,0
—
—
—
—
Nominal operating current at ET -10 °C MT / -30 °C LT AT 32 °C
and 400 V 50 Hz
A
28,7
36,9
3,9
6,1
11,7
18,9
Maximum operating current (in the most loaded phase at 400 V
50 Hz)
A
38,4
51
5,7
8,4
14,9
27,9
Maximum power consumption
kW
20,4
26,6
2,7
3,9
7,0
13,1
Dimensions
mm
1 650 x 975 x 649
1 860 x 975 x 890
1 000 x 705 x 530
1 000 x 705 x 530
1 000 x 772 x 536
1 300 x 705 x 530
WxHxD
Weight
kg
301
380
85
85
132
159
Sound level at 10 m
dB(A)
52,0
55,0
39,0
42,0
50,0
55,0
Sound level at 10 m with housing “H” customisation option
dB(A)
49,0
52,0
36,0
39,0
47,0
52,0
C-SBVN373L0B/
C-SCN603H8T
4CC149NA04/
C-SCN753H8T
C-7RVN113L0A
Model
Volumetric flow
m³/h
7,7 - 24,6 / 23,6
10,7 - 39,3/30,3
1,25 - 7,5
1,7 - 10,4
5,2 - 18,7
10,0 - 37,6
rps
31-80
21-75
15-90
15-90
25-90
25-72
A
18,4 / 16,0
26,0 / 19,4
4,4
6,4
10
22,9
46 / 80
52 / 96
11,2 / —
15 / —
28 / —
46 / —
FV32S (PVE)
Full load amperage
Current
Peak current limit / Locked rotor
A
amperage
Oil type
FV68S (PVE)
FV68S (PVE)
FV68S (PVE)
FV68S (PVE)
FV68S (PVE)
W
2x90
2x90
35
35
35
2x90
dm³
2,0 + 2,8 + 2x0,6
2x2,8 + 2,0
0,7 + 0,4
0,7 + 0,4
2,1 + 0,4
2,5 + 0,4
Suction
Inch
1 3/8
1 5/8
5/8
7/8
7/8
1 1/8
Liquid
Inch
7/8
7/8
3/8
3/8
3/8
5/8
dm³
14
30
3,9
3,9
7,1
14
Voltage
V / Hz
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
Recommended minimum cable cross-section
mm²
5x10,0
5x16,0
5x2,5
5x2,5
5x4,0
5x6,0
C50
C63
C16
C16
C25
C32
m
70
70
40
40
40
40
Evaporator above
m
12
12
12
12
12
12
Evaporator below
m
12
12
12
12
12
12
Crankcase heater power consumption
Oil charge
Liquid receiver
CU power
supply
ACC144NA03
Rotation range
Compressor
Connections
C-7RZ320L4ABL C-9RZ580L4AAL
Recommended minimum protection
Maximum recommended pipe distance
Maximum height distance
Which pipes needs to be insulated
Suction / liquid / both
Suction
Suction
Suction
Suction
Suction
Suction
Recommended insulation thickness
mm
13
13
13
19
19
19
Maximum quantity of evaporators connected
Qty.
10
20
5
5
5
5
Evaporation temperature
Min ~ Max
°C
-15 ~ 10
-15 ~ 10
-35 ~ 5
-35 ~ -15
-35 ~ -15
-35 ~ -10
Ambient temperature
Min ~ Max
°C
-20 ~ 43
-20 ~ 43
-20 ~ 43
-20 ~ 43
-20 ~ 43
-20 ~ 43
CHECK PAGE 57 FOR A SELECTION OF ACCESSORIES
HIGH EFFICIENCY
COMPRESSOR
BMS
CONNECTIVITY
51