Hydronics Brochure - FINAL - Flipbook - Page 117
R32
ROOFTOPS INDEX
ROOFTOPS
Technical features
Size
ECOi-RT-Z 40-50 H - cooling only
Cooling capacity 1)
kW
Input power 1)
kW
EER 1)
Pdesign 2) 3)
kW
SEER 2) 3)
Energy efficiency class 2) 3)
ηs,c 2) 3)
A+ to E
40
50
40,8
50,5
11,7
15,6
3,49
3,24
40,8
50,5
4,28
4,24
B
B
168,3
166,7
50,5
ECOi-RT-Z 40-50 H - reversible
Cooling capacity 1)
kW
40,8
Input power 1)
kW
11,7
15,6
3,49
3,24
40,8
50,5
4,28
4,24
EER 1)
Pdesign 2) 3)
kW
SEER 2) 3)
Energy efficiency class 2) 3)
ηs,c 2) 3)
A+ to E
B
B
168,3
166,7
53,0
Heating capacity 1)
kW
52,0
Input power 1)
kW
11,3
14,7
3,72
3,61
COP 1)
Pdesign 2) 3)
kW
SCOP 2) 3)
Energy efficiency class 2) 3)
ηs,h 2) 3)
A+ to E
52,0
53,0
3,44
3,42
B
B
134,4
133,6
Tentative data
Electrical data
Voltage
Power supply
V
Phase
Frequency
Hz
400
400
Three phase
Three phase
50
50
Refrigerant and compressors
Number of refrigerant circuits
Compressors
Number / type
Mounting type
Capacity steps
1
1
2 / Scroll
2 / Scroll
Tandem
Tandem
0 / 50 / 100
0 / 50 / 100
Copper tubes and aluminium fins
Copper tubes and aluminium fins
Copper tubes and aluminium fins
Copper tubes and aluminium fins
Backward curved centrifugal
Backward curved centrifugal
%
Indoor coil
Coil type
Outdoor coil
Coil type
Indoor fans - EC type
Fan type
Number of fans
Air flow rate
Min. / Nominal / Max.
2
2
7 500
9 200
2 / Axial
2 / Axial
mm
2 484 x 1 850 x 1 652
2 484 x 1 850 x 1 652
kg
694
712
m³/h
Outdoor fans
Fan
Number / type
Dimension and weight
Dimension
LxWxH
Weight (without option)
1) Following EN 14511 2018. 2) Following EN 14825 2017. 3) Following COMMISSION REGULATION (EU) 2016/2281.
R32
HIGH
SEER
HIGH
SCOP
REFRIGERANT
3,82
3,56
ErP
✔
EC MOTOR
GREEN VENTILATION
SCROLL
COMPRESSOR
VERY HIGH
PERFORMANCE
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
115