Hydronics Brochure - FINAL - Flipbook - Page 120
R410A
GENERAL INDEX
ECOi-RT C/H · R410A
Rooftop cooling only and reversible units.
Cooling capacity: 48,1 to 219,1 kW.
Heating capacity: 50,7 to 214,4 kW.
The range at a glance
· 2 versions: C (cooling only) and H (reversible)
· SEER up to 3,94 and SCOP up to 3,23
· 10 sizes
· Nominal air flow from 9 720 to 32 000 m³/h
· Additional heaters available
· Many aeraulic configurations
· 2 energy recovery system configurations (RECO and
TRECO)
Advantages
· Very high performances: A class EER and COP
· Low energy consumption EC fans
· Wide operating limits
· Thermal/acoustic insulation: double skin (25 mm
glasswool)
· 100% factory tested
Operating limits
To be confirmed with AC SELECT:
https://acselect.panasonic.eu/
Ambient temperature (DB).
‑10 °C 1)
50 °C
Equipment
‑15 °C
-20
-15
18 °C
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
35
40
45
50
55
Temperature before indoor coil 2).
12 °C
26 °C
10 °C
-20
-15
-10
-5
0
5
10
27 °C
15
20
25
30
1) Using fan speed control option. 2) Cooling: °C (WB). Heating: °C (DB).
Accessories and options
Accessories and options
AC HP plug fan
Hot water coil
Anti‑vibration mounts
Local additional remote keyboard
Clogged filter sensor (1 or 2 stages)
Compatible container transportation
Many aeraulic configurations (bottom,
side, front, top)
Compressor soft starter
Modbus / BACnet
EC or EC HP plug fan
RECO or TRECO energy recovery
systems including 3‑dampers and
exhaust fan
Electric heaters
2‑dampers configuration including
free‑cooling/free‑heating functions
FRECO energy recovery system
Epoxy treatment (indoor/outdoor coils)
Room temperature sensor
Fan speed control
Sensors (VOC, enthalpy, CO2)
G4, G4+F7 or G4+F9 filters
Smoke detector
Gas heater
Accessories supplied loose
118
P-372062
Kit adjustable roof curb S1R1 ‑ 0/2 dampers with/without gas for sizes 55‑80
P-575505
Kit adjustable roof curb S1R1 ‑ 0/2 dampers with/without gas for sizes 95‑140
P-575506
Kit adjustable roof curb S1R1 ‑ 0/2 dampers without gas for sizes 160‑210
P- 374372
Kit adjustable roof curb S1R1 ‑ 0/2 dampers with gas for sizes 160‑210
P- 372627
Kit adjustable roof curb S1R1 ‑ 3 dampers with/without gas for sizes 55‑80
P- 372628
Kit adjustable roof curb S1R1 ‑ 3 dampers with/without gas for sizes 95‑140
P- 372629
Kit adjustable roof curb S1R1 ‑ 3 dampers without gas for sizes 190‑210
· 2 refrigerant circuits for an optimised defrost logic,
completely closed in a separate compartment to reduce
noise level. Each circuit comprises of Scroll compressor(s)
(2 per circuit from size 160), indoor and outdoor coils, 4
way reversing valve (H type), filter dryer, sight glass,
thermostatic or electronic expansion valve (from 160 to
210), high and low pressure switches, defrosting pressure
switch, intake temperature sensor, and a liquid
accumulation bottle (for sizes from 160 to 210)
· 2 or 4 Scroll compressors ‑ 1 per circuit from 55 to 140
and 2 per circuit for 160 to 210 assembled together in
tandem. Each compressor is equipped with a crankcase
heater and mounted on rubber pads to eliminate noise and
vibration transmissions. The motors are equipped with
overload protection and have direct start‑up. A phase
sequence monitor is supplied as standard
· The controls are grouped and wired in the unit, factory
tested and shipped READY TO USE. They are located in a
sealed compartment that is isolated from the air flow. The
electrical equipment is compliant with EC standards and
EN60204‑1
· The outdoor and indoor heat exchangers are made of
seamless copper tubes mechanically expanded into
aluminium fins. Outdoor coils are largely dimensioned to
optimise performance and defrost cycles. They are also
equipped with a protective grille to prevent shocks ‑
Bluefin treatment applicable to reversible type
· The unit casing is of heavy duty galvanized steel, painted
with a special anti‑corrosion process (RAL 9001). The
complete unit is covered with double skin panels to ensure
perfect thermal insulation. For full unit access, all service
panels are removable. Under the indoor heat exchanger,
an extractable condensate drain pan allows hygienic
cleaning
· The indoor fan(s) are plug type with AC or EC motors; low
pressure or high pressure according to the configuration
selected by the customer.