CHILLERS AND HEAT PUMPS
HYDRONICS INDEX
Air cooled chillers, heat pumps and condensing units
ECOi‑W AQUA EVO H · R410A
1 inverter scroll compressor.
Plate heat exchanger.
Operation range: OAT ‑10 to 45 °C in cooling and ‑15 to 30 °C in heating.
LWT ‑8 to 18 °C in cooling and 25 to 55 °C in heating.
Outdoor unit
ErP data 2)
Cooling
capacity 1)
SEER
ηs,c
ErP data 4) 5)
Heating
capacity 3)
kW
ErP data 4) 6)
SCOP
Energy
efficiency
class
ηs,h
SCOP
Energy
efficiency
class
A+++ to D
kW
ηs,h
A+++ to D
Sound
Dimension
power 7)
HxWxL
Operating weight
dB(A)
mm
kg
20
P‑AQAVE0020HA
21,0
3,30
129
20,4
3,75
A+
147
3,00
A+
117
74
1 615 x 539 x 1 477
260
30
P‑AQAVE0030HA
28,0
3,98
156
26,1
3,68
A+
144
2,95
A+
115
75
1 615 x 539 x 1 477
275
Water connections information
Outdoor unit
20
30
Type of water connections (evaporator)
Male gas threaded
Male gas threaded
1¼
1¼
Water inlet/outlet diameter
Inch
1) According EN 14511-2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According to EN 14825 standard. 3) According EN 14511-2013: warm water inlet/outlet
temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 4) ErP compliant: following COMMISSION REGULATION (EU) No 813/2013. 5) According to EN 14825 standard - low temperature
application (35 °C). 6) According to EN 14825 standard - medium temperature application (55 °C). 7) Sound levels are at fully loaded conditions. Sound power values refers to ISO 3744 standard.
* Check data and configuration on AC SELECT. POA: Price On Applications.
Accessories and options
Accessories and options
Buffer tank placed under unit
In/out valve kit
Chassis acoustic insulation
Remote ON / OFF
Coils treatments
Water flow switch
Discover a unique feature of ECOi‑W AQUA‑G BLUE
Extended operating limits
53 °C
40 °C
45
35
25
15
5
-15 °C
-5
-15
-25
-20
-15
-10
-5
0
5
10
15
20
°C
45 °C
55
Outdoor air temperature (°C)
Outdoor air temperature (°C)
55
70
Operating range in heating mode.
Operating range in cooling mode.
70 °C
Cooling mode.
A water outlet temperature of ‑15 °C
ensures optimal operation temperature for
process equipment in factories.
45
35
25
15
Heating mode.
Ideal solution for Heating and Domestic Hot
Water production. Reaching 70 °C from
0 °C outside air temperature.
5
-5
-20 °C
-15
-25
15
25
Leaving water temperature (°C)
35
45
55
65
75
Leaving water temperature (°C)
ECOi-W AQUA-G BLUE (R290)
ECOi-W AQUA-Z (R32)
Quiet operation
Sound power level (dB(A)).
100
80
Sound pressure level (dB(A)).
79,9
60
84,1
82,7
80,5
85,1
81,5
85,8
50
81,9
48,2
51,0
54,0
53,3
52,3
48,7
49,7
50,1
40
60
30
40
20
20
0
10
50
60
70
80
0
50
60
Model
Standard mode
70
80
Silent mode.
Silent mode with an impressively low sound
power level of only 79,9 dB(A), pressure
level of only 48,2 dB(A). ECOi‑W AQUA‑G
BLUE provides the perfect balance of
efficiency and silent operation.
Optional compressor jackets for size 50 and
optional compressor box for sizes 60‑70‑80
are available to provide an additional level
of noise reduction.
Model
Silent mode
Standard mode
Silent mode
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.