Hydronics Brochure - FINAL - Flipbook - Page 14
GENERAL INDEX
Air cooled chillers, heat pumps and condensing units
ECOi‑W AQUA 20‑40 C/H/E · R410A
2 scroll compressors.
Plate heat exchanger.
Operation range: OAT ‑10 to 50 °C in cooling and ‑17 to 20 °C in heating.
LWT ‑10 to 18 °C in cooling and 20 to 50 °C in heating.
Outdoor unit
Cooling
capacity 1)
ErP data 2) 3)
SEER
ηs,c
kW
Heating
capacity 4)
ErP data 2) 5)
SCOP
Energy
efficiency
class
ηs,h
A+++ to D
kW
Sound
power
(STD fan)
Dimension
Operating weight w/o /
w water tank 6)
Height (STD /
HPF)
Width w/o / w Length
water tank
dB(A)
mm
mm
mm
kg
ECOi‑W AQUA 20‑40 C ‑ chiller
20
P‑AQAE0020CA
19,2
4,78
188
—
—
—
—
75
1 983 / 2 025
1 000 / 1 507
1 000
285 / 450
25
P‑AQAE0025CA
24,3
4,38
172
—
—
—
—
76
1 983 / 2 025
1 000 / 1 507
1 000
295 / 460
30
P‑AQAE0030CA
27,1
4,43
174
—
—
—
—
76
1 983 / 2 025
1 000 / 1 507
1 000
325 / 490
35
P‑AQAE0035CA
36,7
4,43
174
—
—
—
—
77
1 983 / 2 025
1 000 / 1 507
1 000
335 / 500
40
P‑AQAE0040CA
39,0
4,48
176
—
—
—
—
77
1 983 / 2 025
1 000 / 1 507
1 000
335 / 500
ECOi‑W AQUA 20‑40 H ‑ heat pump
20
P‑AQAE0020HA
18,7
4,68
184
19,5
3,50
A+
137
75
1 983 / 2 025
1 000 / 1 507
1 000
285 / 450
25
P‑AQAE0025HA
23,7
4,31
169
26,9
3,38
A+
132
76
1 983 / 2 025
1 000 / 1 507
1 000
295 / 460
30
P‑AQAE0030HA
26,4
4,28
168
29,7
3,45
A+
135
76
1 983 / 2 025
1 000 / 1 507
1 000
325 / 490
35
P‑AQAE0035HA
35,8
4,25
167
37,3
3,50
A+
137
77
1 983 / 2 025
1 000 / 1 507
1 000
335 / 500
40
P‑AQAE0040HA
38,1
4,33
170
41,6
3,50
A+
137
77
1 983 / 2 025
1 000 / 1 507
1 000
335 / 500
ECOi‑W AQUA 25‑40 E ‑ condensing unit
25
P‑AQAE0025EA
32,4
—
—
—
—
—
—
75
1 983 / —
1 000 / —
1 000
260 / —
30
P‑AQAE0030EA
33,7
—
—
—
—
—
—
75
1 983 / —
1 000 / —
1 000
270 / —
35
P‑AQAE0035EA
43,1
—
—
—
—
—
—
76
1 983 / —
1 000 / —
1 000
280 / —
40
P‑AQAE0040EA
44,8
—
—
—
—
—
—
76
1 983 / —
1 000 / —
1 000
280 / —
Water connections information. ECOi‑W AQUA 20‑40 C/H ‑ chiller / heat pump
Outdoor unit
20
25
30
35
40
Type of water connections (evaporator)
Male gas threaded
BSPP ISO 228
Male gas threaded
BSPP ISO 228
Male gas threaded
BSPP ISO 228
Male gas threaded
BSPP ISO 228
Male gas threaded
BSPP ISO 228
1½
1½
1½
1½
1½
40
Water inlet/outlet diameter
Inch
Refrigerant connections information. ECOi‑W AQUA 25‑40 E ‑ condensing unit
Outdoor unit
—
25
30
35
Liquid line
Inch
—
⅝
⅝
⅝
⅝
Suction line
Inch
—
1⅛
1⅛
1⅛
1⅛
1) According EN 14511-2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. For condensing unit models: Data refers to 7 °C leaving chilled water temperature and
35 °C condenser air temperature, according EN 14511-2013 standard. 2) According EN 14825. 3) ErP compliant: following COMMISSION REGULATION (EU) 2016/2281. 4) According EN 14511-2013: warm water
inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 5) ErP compliant: following COMMISSION REGULATION (EU) No 813/2013. 6) With 1 pump.
* w/o: without, w: with.
* Check data and configuration on AC SELECT. POA: Price On Applications.
Accessories and options
Accessories and options
Accessories and options
Anti‑vibration rubber mount / spring dampers
Modbus TCP/IP
SRC ‑ mini BMS controller
BACnet IP or BACnet MSTP
Outdoor coil protection grid
Variable or fixed* speed pumps
Fan speed control
Nordic pack (H type only)
Water pressure switch
Finned coil blygold treatment (upon request) or
epoxy
Remote control
Water tank 100 L
Shut off valves
Without neutral (upon request)
High pressure fan (HPF)
Soft starter
* Not available with ECOi-W AQUA C and ECOi-W AQUA H 20-30 due to Ecodesign compliance.
AC SELECT.
Smart and user-friendly selection tool. Configure
your air conditioning solution at required
conditions: https://acselect.panasonic.eu/