Hydronics Brochure - FINAL - Flipbook - Page 15
CHILLERS AND HEAT PUMPS
HYDRONICS INDEX
Air cooled chillers, heat pumps and condensing units
ECOi‑W AQUA 45‑125 C/H/E · R410A
2 scroll compressors.
Plate heat exchanger.
Operation range: OAT ‑10 to 50 °C in cooling and ‑17 to 20 °C in heating.
LWT ‑10 to 18 °C in cooling and 20 to 50 °C in heating.
Outdoor unit
Cooling
capacity 1)
ErP data 2) 3)
SEER
ηs,c
kW
Heating
capacity 4)
ErP data 2) 5)
SCOP
Energy
efficiency
class
ηs,h
A+++ to D
kW
Sound
power
(STD fan)
Dimension
Operating weight w/o /
w water tank 6)
Height (STD /
HPF)
Width
Length w/o /
w water tank
dB(A)
mm
mm
mm
kg
ECOi‑W AQUA 45‑125 C ‑ chiller
45
P‑AQAE0045CA
45,3
4,40
173
—
—
—
—
81
1 986 / 2 025
1 160
2 180 / 2 680
545 / 1 010
55
P‑AQAE0055CA
52,0
4,53
178
—
—
—
—
81
1 986 / 2 025
1 160
2 180 / 2 680
545 / 1 010
65
P‑AQAE0065CA
66,1
4,53
178
—
—
—
—
81
1 986 / 2 026
1 160
2 180 / 2 680
615 / 1 080
75
P‑AQAE0075CA
73,1
4,68
184
—
—
—
—
81
1 986 / 2 026
1 160
2 180 / 2 680
615 / 1 080
90
P‑AQAE0090CA
90,9
4,45
175
—
—
—
—
84
2 286 / 2 379
1 160
2 180 / 2 680
795 / 1 260
105
P‑AQAE0105CA
104,0
4,50
177
—
—
—
—
84
2 286 / 2 379
1 160
2 180 / 2 680
905 / 1 370
125
P‑AQAE0125CA
123,0
4,55
179
—
—
—
—
84
2 286 / 2 379
1 160
2 180 / 2 680
925 / 1 390
ECOi‑W AQUA 45‑125 H ‑ heat pump
45
P‑AQAE0045HA
44,3
4,20
165
48,5
3,38
A+
132
81
1 986 / 2 025
1 160
2 180 / 2 680
545 / 1 010
55
P‑AQAE0055HA
50,9
4,41
174
58,2
3,38
A+
132
81
1 986 / 2 025
1 160
2 180 / 2 680
545 / 1 010
65
P‑AQAE0065HA
64,1
4,51
177
67,3
3,55
A+
139
81
1 986 / 2 026
1 160
2 180 / 2 680
615 / 1 080
75
P‑AQAE0075HA
71,0
4,63
182
76,0
3,53
A+
138
81
1 986 / 2 026
1 160
2 180 / 2 680
615 / 1 080
90
P‑AQAE0090HA
88,7
4,40
173
88,2
3,40
—
133
84
2 286 / 2 379
1 160
2 180 / 2 680
795 / 1 260
105
P‑AQAE0105HA
101,0
4,44
175
101,0
3,43
—
134
84
2 286 / 2 379
1 160
2 180 / 2 680
905 / 1 370
125
P‑AQAE0125HA
119,0
4,49
177
119,0
3,43
—
134
84
2 286 / 2 379
1 160
2 180 / 2 680
925 / 1 390
ECOi‑W AQUA 45‑125 E ‑ condensing unit
45
P‑AQAE0045EA
57,4
—
—
—
—
—
—
80
1 986
1 160
2 180
—
55
P‑AQAE0055EA
64,5
—
—
—
—
—
—
80
1 986
1 160
2 180
—
65
P‑AQAE0065EA
72,4
—
—
—
—
—
—
80
1 986
1 160
2 180
—
75
P‑AQAE0075EA
79,3
—
—
—
—
—
—
80
1 986
1 160
2 180
—
90
P‑AQAE0090EA
104,0
—
—
—
—
—
—
83
2 286
1 160
2 180
—
105
P‑AQAE0105EA
120,0
—
—
—
—
—
—
83
2 286
1 160
2 180
—
125
P‑AQAE0125EA
136,0
—
—
—
—
—
—
83
2 286
1 160
2 180
—
Water connections information. ECOi‑W AQUA 45‑125 C/H ‑ chiller / heat pump
Outdoor unit
45
55
65
75
90
105
125
Type of water connections (evaporator)
Male gas
threaded BSPP
ISO 228
Male gas
threaded BSPP
ISO 228
Male gas
threaded BSPP
ISO 228
Male gas
threaded BSPP
ISO 228
Male gas
threaded BSPP
ISO 228
Male gas
threaded BSPP
ISO 228
Male gas
threaded BSPP
ISO 228
2
2
2
2
2½
2½
2½
Water inlet/outlet diameter
Inch
Refrigerant connections information. ECOi‑W AQUA 45‑125 E ‑ condensing unit
Outdoor unit
45
55
65
75
90
105
125
Liquid line
Inch
⅝
⅝
⅝
⅝
⅞
⅞
⅞
Suction line
Inch
1⅝
1⅝
1⅝
1⅝
1⅝
1⅝
1⅝
1) According EN 14511-2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. For condensing unit models: Data refers to 7 °C leaving chilled water temperature and
35 °C condenser air temperature, according EN 14511-2013 standard. 2) According EN 14825. 3) ErP compliant: following COMMISSION REGULATION (EU) 2016/2281. 4) According EN 14511-2013: warm water
inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 5) ErP compliant: following COMMISSION REGULATION (EU) No 813/2013. 6) With 1 pump.
* w/o: without, w: with.
* Check data and configuration on AC SELECT. POA: Price On Applications.
Accessories and options
Accessories and options
Accessories and options
Anti‑vibration rubber mount / spring dampers
Super low noise (S): acoustic box around the
compressors
Shut off valves
BACnet IP or BACnet MSTP
Desuperheater
High pressure fan (HPF)
SRC ‑ mini BMS controller
Fan speed control
Modbus TCP/IP
Variable or fixed* speed pumps
Finned coil blygold treatment (upon request) or
epoxy
Outdoor coil protection grid
Water tank 300 L
Refrigerant gauges HP/LP
Without neutral (upon request)
Electrical heater high or low power (H type only)
Remote control
Water pressure switch
Soft starter
* Not available with ECOi-W AQUA C units due to Ecodesign compliance.
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
15