Hydronics Brochure - FINAL - Flipbook - Page 16
GENERAL INDEX
Air cooled chillers, heat pumps and condensing units
ECOi‑W AQUA 140‑210 C/H · R410A
4 scroll compressors.
Plate heat exchanger.
Operation range: OAT ‑10 to 50 °C in cooling and ‑17 to 20 °C in heating.
LWT ‑10 to 18 °C in cooling and 20 to 50 °C in heating.
Outdoor unit
Cooling
capacity 1)
ErP data 2) 3)
SEER
Heating
capacity 4)
ηs,c
kW
ErP data 2) 5)
ηs,h
SCOP
kW
Sound
power
(STD fan)
Dimension
Height
Width
Length w/o /
w water tank
dB(A)
mm
mm
mm
Operating weight w/o /
w water tank 6)
kg
ECOi‑W AQUA 140‑210 C ‑ chiller
140
P‑AQAE0140CA
132
4,40
173
—
—
—
85
2 295
2 210
2 856 / 3 666
1 685 / 2 139
150
P‑AQAE0150CA
146
4,45
175
—
—
—
85
2 295
2 210
2 856 / 3 666
1 705 / 2 159
170
P‑AQAE0170CA
164
4,38
172
—
—
—
87
2 321
2 210
2 856 / 3 666
1 798 / 2 253
190
P‑AQAE0190CA
181
4,40
173
—
—
—
88
2 321
2 210
2 856 / 3 666
1 891 / 2 343
210
P‑AQAE0210CA
208
4,25
167
—
—
—
88
2 321
2 210
2 856 / 3 666
2 201 / 2 653
4,39
173
144
3,30
129
85
2 295
2 210
2 856 / 3 666
1 685 / 2 139
ECOi‑W AQUA 140‑210 H ‑ heat pump
140
P‑AQAE0140HA
128
150
P‑AQAE0150HA
142
4,36
171
154
3,33
130
85
2 295
2 210
2 856 / 3 666
1 705 / 2 159
170
P‑AQAE0170HA
164
4,31
169
170
3,30
129
87
2 321
2 210
2 856 / 3 666
1 798 / 2 253
190
P‑AQAE0190HA
178
4,23
166
195
3,28
128
88
2 321
2 210
2 856 / 3 666
1 891 / 2 343
210
P‑AQAE0210HA
208
4,28
168
218
3,23
126
88
2 321
2 210
2 856 / 3 666
2 201 / 2 653
Water connections information
Outdoor unit
140
150
170
190
210
Type of water connections (evaporator)
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
2½
2½
2½
2½
2½
Water inlet/outlet diameter
Inch
1) According EN 14511-2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According EN 14825. 3) ErP compliant: following COMMISSION REGULATION (EU)
2016/2281. 4) According EN 14511-2013: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 5) ErP compliant: following COMMISSION REGULATION (EU) No
813/2013. 6) With 1 pump.
* w/o: without, w: with.
* Check data and configuration on AC SELECT. POA: Price On Applications.
Accessories and options
Accessories and options
Accessories and options
Anti‑vibration rubber mount / spring dampers
Modbus TCP/IP
SRC ‑ mini BMS controller
BACnet IP and BACnet MSTP
Outdoor coil protection grid
Variable or fixed* speed pumps
Desuperheater (upon request)
Nordic pack (H type only)
Water tank 300 L
Fan speed control
Refrigerant gauges HP/LP
Without neutral
Finned coil blygold treatment (upon request) and
epoxy
Remote control
Water pressure switch
Hydraulic gauges
Soft starter
Shut off valves
* ECOi-W AQUA C units can’t be Ecodesign compliant with this option.
AC SELECT.
Smart and user-friendly selection tool. Configure
your air conditioning solution at required
conditions: https://acselect.panasonic.eu/
16