Hydronics Brochure - FINAL - Flipbook - Page 17
CHILLERS AND HEAT PUMPS
HYDRONICS INDEX
Air cooled chillers, heat pumps and condensing units
ECOi‑W AQUA‑Z 50‑170 C/H · R32
2 scroll compressors.
Plate heat exchanger.
Operation range: OAT ‑15 to 48 °C (47 °C for sizes 150 ‑ 170) in cooling and ‑15 to 40 °C in
heating. LWT ‑10 to 18 °C in cooling and 20 to 55 °C (53 °C for sizes 150 ‑ 170) in heating.
Outdoor unit
ErP data (STD AC / STD EC) Heating
ErP data (STD AC / STD EC)
Cooling
capacity 1)
capacity 4)
2) 3)
2) 3)
ηs,h *2) 6)
η
SEER *
SCOP *2) 5) Energy
s,c *
efficiency
class *2) 6)
kW
A+++ to D
kW
Sound
Dimension
power
(STD AC / Height
(STD / EC/
S) *
HPF)
R32
Width Length
without
water
tank
Operating weight
without water
tank 7)
dB(A)
mm
mm
mm
kg
ECOi‑W AQUA‑Z 50‑170 C ‑ chiller
50
P‑AQAZ0050CA
51,6
4,60 / 5,05
180,9 / 198,9 —
—
—
—
83 / 81
1 986 / 2 034
1 160
2 180
527
60
P‑AQAZ0060CA
57,6
4,59 / 5,02
180,5 / 197,8 —
—
—
—
84 / 81
1 986 / 2 034
1 160
2 180
547
70
P‑AQAZ0070CA
69,7
4,61 / 5,31
181,3 / 209,6 —
—
—
—
81 / 78
1 986 / 2 034
1 160
2 180
621
75
P‑AQAZ0075CA
78,2
4,72 / 5,29
185,6 / 208,7 —
—
—
—
81 / 78
1 986 / 2 034
1 160
2 180
637
85
P‑AQAZ0085CA
82,8
4,45 / 4,96
175,0 / 195,6 —
—
—
—
84 / 82
2 286 / 2 334
1 160
2 180
701
100 P‑AQAZ0100CA
100
4,88 / 5,19
192,3 / 204,9 —
—
—
—
86 / 83
2 286 / 2 334
1 160
2 180
731
115 P‑AQAZ0115CA
116
4,59 / 5,01
180,5 / 197,3 —
—
—
—
87 / 84
2 286 / 2 334
1 160
2 180
813
130 P‑AQAZ0130CA
126
4,43 / 4,71
174,2 / 185,6 —
—
—
—
87 / 84
2 286 / 2 334
1 160
2 180
815
150 P‑AQAZ0150CA
154
4,70 / 5,22
184,8 / 205,6 —
—
—
—
89 / 86
2 285 / 2 333
1 151
3 789
1 265
170 P‑AQAZ0170CA
173
4,68 / 5,16
184,2 / 203,2 —
—
—
—
91 / 88
2 285 / 2 333
1 151
3 789
1 279
ECOi‑W AQUA‑Z 50‑170 H ‑ heat pump
50
P‑AQAZ0050HA
51,1
4,46 / 4,83
175,2 / 190,2 51,7
3,53 / 3,90
A+ / A+
138,0 / 152,8 83 / 81
1 986 / 2 034
1 160
2 180
527
60
P‑AQAZ0060HA
57
4,42 / 4,50
173,6 / 176,9 59,7
3,54 / 3,94
A+ / A+
138,5 / 154,5 84 / 81
1 986 / 2 034
1 160
2 180
547
70
P‑AQAZ0070HA
69
4,51 / 5,04
177,5 / 198,8 71,8
3,47 / 3,71
A+ / A++
135,6 / 145,3 81 / 78
1 986 / 2 034
1 160
2 180
621
75
P‑AQAZ0075HA
77,4
4,61 / 4,99
181,5 / 196,7 78,5
3,65 / 3,80
A+ / A++
143,2 / 148,8 81 / 78
1 986 / 2 034
1 160
2 180
637
85
P‑AQAZ0085HA
82
4,33 / 4,80
170,3 / 188,9 86,5
3,60 / 4,02
A+ / A++
141,2 / 157,8 84 / 82
2 286 / 2 334
1 160
2 180
701
100 P‑AQAZ0100HA
99,3
4,77 / 4,93
187,7 / 194,1 107,6
3,64 / 4,10
—/—
142,5 / 160,9 86 / 83
2 286 / 2 334
1 160
2 180
731
115 P‑AQAZ0115HA
115
4,44 / 4,82
174,6 / 190,0 122,3
3,66 / 4,02
—/—
143,2 / 157,9 87 / 84
2 286 / 2 334
1 160
2 180
813
130 P‑AQAZ0130HA
125
4,23 / 4,51
166 / 177,2
137,5
3,72 / 3,97
—/—
145,7 / 155,9 87 / 84
2 286 / 2 334
1 160
2 180
815
150 P‑AQAZ0150HA
152
4,59 / 5,04
180,5 / 198,7 159,1
3,57 / 4,04
—/—
139,9 / 158,4 89 / 86
2 285 / 2 333
1 151
3 789
1 265
170 P‑AQAZ0170HA
170
4,49 / 4,92
176,6 / 193,8 180,1
3,60 / 3,95
—/—
140,9 / 155,2 91 / 88
2 285 / 2 333
1 151
3 789
1 279
Water connections information
Outdoor unit
50
60
70
75
85
100
115
130
150
170
Type of water connections
(evaporator)
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
2
2
2
2
2½
2½
2½
2½
2½
2½
Water inlet/outlet diameter
Inch
1) According EN 14511-2018: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According EN 14825. 3) ErP compliant: following COMMISSION REGULATION (EU)
2016/2281. 4) According EN 14511-2018: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 5) ErP compliant: following COMMISSION REGULATION (EU) No
813/2013. 6) According EN 14511-2018: warm water inlet/outlet temperature: 30/35 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 7) With 1 pump.
* STD AC: standard version with AC fan, STD EC: standard version with high efficiency EC fan, S: super low noise version with high efficiency EC fan + compressor sound jackets.
* Check data and configuration on AC SELECT. POA: Price On Applications.
Accessories and options
Accessories and options
Accessories and options
Anti‑vibration rubber mount / spring dampers *
High pressure fan (HPF)
SRC ‑ mini BMS controller
Cascade controller *
Outdoor coil protection grid
Variable speed pumps
Compressor jackets (standard for S versions)
Power factor corrector capacitors
Water pressure switch *
Desuperheater
Refrigerant gauges HP/LP
Water tank 300 L
Electrical heater for the water tank
Remote control kit *
Without neutral
Fin&Tube Al/Cu with epoxy / Blygold treatment
Shut off valves
High efficiency EC fan
Soft starter
Communication protocols: Modbus RTU (Std.),
Modbus TCP/IP, BACnet MSTP, BACnet IP
* Field-installed accessories. All other accessories are factory-installed.
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.