Hydronics Brochure - FINAL - Flipbook - Page 18
GENERAL INDEX
Air cooled chillers, heat pumps and condensing units
ECOi‑W AQUA‑Z DC 150‑380 C/H · R32
4 scroll compressors. 2 refrigerant circuits.
Plate heat exchanger.
Operation range: OAT ‑15 to 46 °C in cooling and ‑15 to 40 °C (with EC fans) in
heating. LWT ‑10 to 18 °C in cooling and 20 to 53 °C in heating.
Outdoor unit
Cooling
capacity 1)
ErP data
SEER
2)
Heating
capacity 3)
ηs,c 2)
kW
ErP data
SCOP 4)
ηs,h 4)
kW
R32
Sound
power
(S) 5)
dB(A)
Dimension
Height
Height
Width
(STD AC) (EC/HPF)
Length
mm
mm
mm
mm
ECOi‑W AQUA‑Z DC 150‑380 C ‑ chiller ‑ P‑AQADZ****CA
150
STD AC / STD EC
151,0 / 151,0
4,93 / 5,2
194,0 / 204,0
—
—
—
— / 85,0
2 240
2 312
1 152
3 795
170
STD AC / STD EC
170,0 / 170,0
4,90 / 5,15
192,8 / 203,0
—
—
—
— / 85,4
2 240
2 312
1 152
3 795
190
STD AC / STD EC
189,0 / 189,0
4,68 / 5,23
184,3 / 206,1
—
—
—
— / 87,2
2 250
2 300
2 211
2 676
210
STD AC / STD EC
212,0 / 214,0
4,62 / 5,20
181,8 / 204,8
—
—
—
— / 87,4
2 250
2 300
2 211
2 676
230
STD AC / STD EC
229,0 / 229,0
4,48 / 4,90
176,3 / 192,9
—
—
—
— / 87,6
2 250
2 300
2 211
2 676
260
STD AC / STD EC
260,0 / 260,0
4,40 / 4,79
173,1 / 188,4
—
—
—
— / 87,8
2 250
2 300
2 211
2 676
290
STD AC / STD EC
307,0 / 307,0
4,63 / 5,13
182,0 / 202,2
—
—
—
— / 88,6
2 250
2 300
2 211
3 801
320
STD AC / STD EC
326,0 / 325,0
4,33 / 5,12
170,0 / 188,8
—
—
—
— / 89,7
2 250
2 300
2 211
3 801
350
STD AC / STD EC
346,0 / 347,0
4,43 / 4,79
174,2 / 188,5
—
—
—
— / 90,1
2 250
2 300
2 211
3 801
380
STD AC / STD EC
377,0 / 377,0
4,35 / 4,8
171,0 / 188,8
—
—
—
— / 90,3
2 250
2 300
2 211
3 801
154 / 154
3,83 / 4,00
150 / 157,1
— / 85,0
2 240
2 312
1 152
3 795
ECOi‑W AQUA‑Z DC 150‑380 H ‑ heat pump ‑ P‑AQADZ****HA
150
STD AC / STD EC
150 / 150
4,75 / 5,03
187,1 / 198,1
170
STD AC / STD EC
167 / 167
4,71 / 4,97
185,3 / 195,7
178 / 179
3,90 / 4,00
152,8 / 156,8
— / 85,4
2 240
2 312
1 152
3 795
190
STD AC / STD EC
184 / 183
4,45 / 4,94
175,2 / 194,6
190 / 190
3,46 / 3,89
135,6 / 152,7
— / 87,2
2 250
2 300
2 211
2 676
210
STD AC / STD EC
204 / 204
4,39 / 4,82
172.5 / 189,6
201 / 201
3,44 / 3,90
134,7 / 152,8
— / 87,4
2 250
2 300
2 211
2 676
220
STD EC
208
5,03
198
219
3,86
151,3
87,4
—
2 300
2 211
2 676
— / 87,6
2 250
2 300
2 211
2 676
230
STD AC / STD EC
224 / 224
4,34 / 4,71
170,6 / 185,5
241 / 241
3,64 / 3,99
142,5 / 156,4
260
STD AC / STD EC
251 / 251
4,21 / 4,55
165,5 / 179,1
256,9 / 258,5
3,52 / 3,85
137,9 / 151
— / 87,8
2 250
2 300
2 211
2 676
270
STD EC
265
5,01
197,5
288
3,82
149,7
88,5
—
2 300
2 211
3 801
290
STD AC / STD EC
291,1 / 289,3
4,34 / 4,83
170,4 / 190,1
285,6 / 284,8
3,51 / 3,91
137,4 / 153,2
— / 88,6
2 250
2 300
2 211
3 801
300
STD EC
295
5,01
197,3
312
3,92
153,7
88,6
—
2 300
2 211
3 801
320
STD AC / STD EC
307,7 / 310,7
4,33 / 4,89
170 / 192,4
301,3 / 316,5
3,50 / 3,85
137 / 151,2
— / 89,7
2 250
2 300
2 211
3 801
350
STD AC / STD EC
330 / 331
4,40 / 4,79
172,9 / 188,5
337 / 340
3,50 / 3,87
136,9 / 151,9
— / 90,1
2 250
2 300
2 211
3 801
380
STD AC / STD EC
364 / 364,3
4,34 / 4,65
170,5 / 182,9
384 / 384,5
3,66 / 3,95
143,4 / 155,1
— / 90,3
2 250
2 300
2 211
3 801
1) According EN 14511-2018: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According EN 14825 and Following COMMISSION REGULATION (EU) 2016/2281.
3) According EN 14511-2018: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 4) According EN 14825 and Following COMMISSION REGULATION (EU) No 813/2013.
5) Sound levels are at fully loaded conditions. Sound power values refers to ISO 3744 standard.
Accessories and options
Accessories and options
Accessories and options
Anti‑vibration rubber mount / spring dampers *
Mechanical gauges kit (HP and LP manometers)
Compressor jackets
Cascade controller *
Coil guards for sizes 150 ‑ 170
Compressor box for sizes 190 ‑ 380
Desuperheater for sizes 190 ‑ 380
Chiller grilles and drain pan for sizes 190 ‑ 380
Variable speed pumps
Electrical heater for the water tank (only H version)
Power factor corrector capacitors
Water filter *
Energy meter for power input
Remote control kit *
Water pressure switch
Fin&Tube Al/Cu with Epoxy / Blygold treatment
Shut off valves *
Water tank
High efficiency EC fan
Soft starter
High pressure fan (HPF)
Super low noise (S) version
* Field-installed accessories. All other accessories are factory-installed.
AC SELECT.
Smart and user-friendly selection tool. Configure
your air conditioning solution at required
conditions: https://acselect.panasonic.eu/
18