CHILLERS AND HEAT PUMPS
HYDRONICS INDEX
Air cooled chillers, heat pumps and condensing units
ECOi‑W AQV C/H/E · R410A
4 scroll compressors.
Plate heat exchanger.
Operation range: OAT 5 to 47 °C in cooling and ‑10 to 20 °C in heating (STD units).
LWT ‑8 to 18 °C in cooling and 20 to 55 °C in heating.
Outdoor unit
Cooling
capacity 1)
STD / S / HT
ErP data 2) 3)
SEER
ηs,c
STD / S / HT
STD / S / HT
kW
Heating
capacity 4)
STD / S / HT
ErP data 3) 5)
SCOP
ηs,h
STD / S / HT
STD / S / HT
kW
Sound
power 6)
Dimension
Operating weight
HxWxL
STD / S / HT
STD / S / HT
dB(A)
mm
kg
ECOi‑W AQV 85‑140 C ‑ chiller
85
P‑AQVE0085CA
95
P‑AQVE0095CA
105 P‑AQVE0105CA
115 P‑AQVE0115CA
125 P‑AQVE0125CA
140 P‑AQVE0140CA
83,5 / 80,6 /
86,2
93,6 / 90,2 /
96,9
103,0 / 98,6 /
107
110,1 / 106 /
115
121,9 / 119,1 /
124
136,6 / 133,1 /
139
4,55 / 4,75 /
4,73
4,8 / 4,78 /
4,75
4,78 / 4,98 /
4,95
4,8 / 5,0 /
4,95
4,73 / 4,8 /
4,78
4,53 / 4,6 /
4,6
179 / 187 /
186
189 / 188 /
187
188 / 196 /
195
189 / 197 /
195
186 / 189 /
188
178 / 181 /
181
4,25 / 4,25 /
4,6
4,68 / 4,68 /
5,02
4,63 / 4,63 /
4,95
4,17 / 4,17 /
4,55
4,33 / 4,33 /
4,6
4,28 / 4,28 /
4,5
—
—
—
84 / 82 / 95
2 185 x 1 095 x 2 555
—
—
—
84 / 82 / 95
2 185 x 1 095 x 2 555
—
—
—
84 / 82 / 95
2 185 x 1 095 x 2 555
—
—
—
84 / 82 / 95
2 185 x 1 095 x 2 555
—
—
—
88 / 86 / 95
2 185 x 1 095 x 3 155
—
—
—
88 / 86 / 95
2 185 x 1 095 x 3 155
167 / 167 /
181
184 / 184 /
198
182 / 182 /
195
164 / 164 /
179
170 / 170 /
181
168 / 168 /
177
91,8 / 89,5 /
93,4
102,8 / 99,8 /
104,9
110 / 108 /
113,7
119 / 115 /
121,9
134 / 129 /
135
146,9 / 142 /
148
3,61 / 3,61 /
3,99
3,64 / 3,64 /
3,96
3,78 / 3,78 /
4,12
3,77 / 3,77 /
4,07
3,47 / 3,47 /
3,73
3,54 / 3,54 /
3,77
141 / 141 /
157
143 / 143 /
155
148 / 148 /
162
148 / 148 /
160
136 / 136 /
146
139 / 139 /
148
84 / 82 / 95
2 185 x 1 095 x 2 555
84 / 82 / 95
2 185 x 1 095 x 2 555
84 / 82 / 95
2 185 x 1 095 x 2 555
84 / 82 / 95
2 185 x 1 095 x 2 555
88 / 86 / 95
2 185 x 1 095 x 3 155
88 / 86 / 95
2 185 x 1 095 x 3 155
—
—
—
—
—
84 / 82 / 95
2 185 x 1 095 x 2 555
—
—
—
—
—
84 / 82 / 95
2 185 x 1 095 x 2 555
—
—
—
—
—
84 / 82 / 95
2 185 x 1 095 x 2 555
—
—
—
—
—
84 / 82 / 95
2 185 x 1 095 x 2 555
—
—
—
—
—
88 / 86 / 95
2 185 x 1 095 x 3 155
—
—
—
—
—
88 / 86 / 95
2 185 x 1 095 x 3 155
1 058 / 1 088 /
1 058
1 072 / 1 102 /
1 072
1 111 / 1 141 /
1 111
1 143 / 1 173 /
1 143
1 183 / 1 213 /
1 183
1 262 / 1 292 /
1 262
ECOi‑W AQV 85‑140 H ‑ heat pump
85
P‑AQVE0085HA
95
P‑AQVE0095HA
105 P‑AQVE0105HA
115 P‑AQVE0115HA
125 P‑AQVE0125HA
140 P‑AQVE0140HA
81 / 78,4 /
83,5
89,9 / 86,7 /
93,4
98,9 / 95,1 /
104
106,9 / 102 /
112
115,8 / 112 /
118
129,2 / 124,6 /
132
1 090 / 1 120 /
1 090
1 105 / 1 135 /
1 105
1 149 / 1 179 /
1 149
1 180 / 1 210 /
1 180
1 227 / 1 257 /
1 227
1 301 / 1 331 /
1 301
ECOi‑W AQV 85‑140 E ‑ condensing unit
85
P‑AQVE0085EA
95
P‑AQVE0095EA
105 P‑AQVE0105EA
115 P‑AQVE0115EA
125 P‑AQVE0125EA
140 P‑AQVE0140EA
92,1 / 89 /
95
103,2 / 99,5 /
106,8
113,2 / 108,7 /
117,7
121,8 / 116,6 /
127
134,7 / 131,6 /
137,2
151,0 / 147,2 /
153,8
971 / 1 001 /
—
983 / 1 013 /
—
1 013 / 1 043 /
—
1 043 / 1 073 /
—
1 066 / 1 096 /
—
1 142 / 1 172 /
—
Water connections information. ECOi‑W AQV 85‑140 C/H ‑ chiller / heat pump
Outdoor unit
85
Type of water connections (evaporator)
Male gas threaded Male gas threaded Male gas threaded Male gas threaded Male gas threaded Male gas threaded
Water inlet/outlet diameter
Inch
2½
95
105
115
125
140
2½
2½
2½
2½
2½
Condenser information. ECOi‑W AQV 85‑140 E ‑ condensing unit
Type of connections
To be brazed
To be brazed
To be brazed
To be brazed
To be brazed
To be brazed
Inlet diameter
Inch
⅝
⅝
⅝
⅝
⅞
⅞
Outlet diameter
Inch
1⅜
1⅜
1⅜
1⅜
1⅜
1⅜
1) According EN 14511-2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. For condensing unit models: Data refers to 7 °C leaving chilled water temperature and
35 °C condenser air temperature, according EN 14511-2013 standard. 2) ErP compliant: following COMMISSION REGULATION (EU) 2016/2281. 3) According EN 14825. 4) According EN 14511-2013: warm water
inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 5) ErP compliant: following COMMISSION REGULATION (EU) No 813/2013. 6) Sound levels are at fully loaded conditions.
Sound power values refers to ISO 3744 standard.
* Check data and configuration on AC SELECT. POA: Price On Applications.
Accessories and options
Accessories and options
Anti‑vibration spring dampers
Power factor corrector capacitors
Automatic circuit breaker
Several communication protocols
Coils treatments
Soft starter
Desuperheater
Unit protection grilles
Fan speed control
Water differential pressure
Hydrokit with 1 or 2 pumps with or without buffer tank
Water filter
Mechanical gauges
Water pressure switch
Overload protection for compressors
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.