Air cooled chillers, heat pumps and condensing units
ECOi‑W AQUA EVO 400‑800 C/H · R410A
4/5/6/8 scroll compressors.
Plate heat exchanger.
Operation range: OAT 10 to 46 °C in cooling and ‑10 to 20 °C in heating (STD units).
LWT ‑3 to 18 °C in cooling and 25 to 55 °C in heating.
Outdoor unit
Nominal
cooling
capacity 1)
AC / EC
ErP data 2) 3)
SEER
ηs,c
Nominal
heating
capacity 4)
AC / EC
AC / EC
AC / EC
%
kW
kW
ErP data 3)
SCOP
ηs,h
Sound
power
(STD) 5)
Sound
power (S) 5)
AC / EC
AC / EC
AC / EC
AC / EC
STD / S
STD / S
%
dB(A)
dB(A)
mm
mm
kg
Dimension
HxW
Operating weight
Length
ECOi‑W AQUA EVO 400‑800 C ‑ chiller
400 /
400
P‑AQAVE0400CA
390,4 /
400,0
4,48 /
4,65
176 /
183
—/—
—/—
—/—
92 / 92
86 / 86
2 500 x
2 175
4 580 /
5 620
3 028 / 3 318
450 S
/ 450
P‑AQAVE0450CA
431,1 /
447,0
4,63 /
4,58
182 /
180
—/—
—/—
—/—
— / 93
87 / 87
2 500 x
2 175
—/
6 680
—/
3 656
490 S
/ 490
P‑AQAVE0490CA
470,2 /
489,0
4,58 /
4,68
180 /
184
—/—
—/—
—/—
— / 93
87 / 87
2 500 x
2 175
—/
7 760
—/
4 069
530 S
/ 530
P‑AQAVE0530CA
513,7 /
535,0
4,78 /
4,55
188 /
179
—/—
—/—
—/—
— / 94
87 / 87
2 500 x
2 175
—/
7 760
—/
4 369
600 /
600
P‑AQAVE0600CA
584,5 /
599,0
4,58 /
4,78
180 /
188
—/—
—/—
—/—
94 / 94
88 / 88
2 500 x
2 175
7 760 /
8 800
4 317 /
4 597
670 /
670
P‑AQAVE0670CA
653,2 /
669,0
4,59 /
4,87
181 /
192
—/—
—/—
—/—
94 / —
88 / 88
2 500 x
2 175
7 760 /
8 800
4 524 /
4 789
750 S /
P‑AQAVE0750CA
750 S
727,7 /
746,0
4,73 /
4,93
186 /
194
—/—
—/—
—/—
—/—
89 / 89
2 500 x
2 175
—/
11000
—/
6 111
800 S /
P‑AQAVE0800CA
800 S
775,4 /
796,0
4,70 /
4,90
185 /
193
—/—
—/—
—/—
—/—
89 / 89
2 500 x
2 175
—/
11000
—/
6 183
ECOi‑W AQUA EVO 400‑800 H ‑ heat pump
400 /
400
P‑AQAVE0400HA
365,6 /
373,5
4,65 /
4,93
183 /
194
404,0 /
404,0
3,46 /
3,62
136 /
142
92 / 92
86 / 86
2 500 x
2 175
5 620 /
6 680
3 769 /
4 131
450 /
450
P‑AQAVE0450HA
410,3 /
419,2
4,53 /
4,83
178 /
190
450,9 /
450,9
3,47 /
3,62
136 /
142
93 / 93
87 / 87
2 500 x
2 175
5 620 /
6 680
3 938 /
4 293
490 /
490
P‑AQAVE0490HA
444,9 /
454,5
4,70 /
4,97
185 /
196
492,7 /
492,7
3,37 /
3,53
132 /
138
93 / 93
87 / 87
2 500 x
2 175
6 680 /
7 760
4 412 /
4 764
530 /
530
P‑AQAVE0530HA
479,3 /
498,7
4,55 /
4,88
179 /
192
532,1 /
532,1
3,38 /
3,53
132 /
138
94 / 94
87 / 87
2 500 x
2 175
6 680 /
7 760
4 744 /
5 101
580 S /
P‑AQAVE0580HA
580 S
520,1 /
533,0
4,60 /
4,75
181 /
187
585,6 /
585,0
—/—
—/—
—/—
88 / 88
2 500 x
2 175
—/
8 800
—/
5 567
620 S /
P‑AQAVE0620HA
620 S
566,3 /
580,0
4,60 /
4,73
181 /
186
627,1 /
626,0
—/—
—/—
—/—
88 / 88
2 500 x
2 175
—/
9 850
—/
5 919
670 S /
P‑AQAVE0670HA
670 S
608,3 /
621,5
4,55 /
4,70
179 /
185
676,7 /
676,7
—/—
—/—
—/—
88 / 88
2 500 x
2 175
—/
9 850
—/
6 059
750 S /
P‑AQAVE0750HA
750 S
686,6 /
704,0
4,55 /
4,65
179 /
183
757,4 /
757,0
—/—
—/—
—/—
89 / 89
2 500 x
2 175
—/
12050
—/
7 497
800 S /
P‑AQAVE0800HA
800 S
727,5 /
746,0
4,58 /
4,65
180 /
183
805,3 /
805,0
—/—
—/—
—/—
89 / 89
2 500 x
2 175
—/
12050
—/
7 683
Water connections information. ECOi‑W AQUA EVO 400‑800 C ‑ chiller
Outdoor unit
400
450
490
530
600
670
750
800
Type of water connections (evaporator and condenser)
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
4
4
4
4
4
5
6
6
Water inlet/outlet diameter
Inch
Water connections information. ECOi‑W AQUA EVO 400‑800 H ‑ heat pump
Type of water connections (evaporator)
Water inlet/outlet diameter
Inch
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
4
4
4
4
4
5
5
6
6
1) According EN 14511-2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) ErP compliant: following COMMISSION REGULATION (EU) 2016/2281. 3) According
EN 14825. 4) According EN 14511-2013: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 5) Sound powers is declared in nominal full load condition (cooling
operation), referring to ISO standard 9614, in accordance with Eurovent certification program.
* Check data and configuration on AC SELECT. POA: Price On Applications.
22
Accessories and options
Accessories and options
Accessories and options
Anti‑vibration spring dampers
Soft starter
Automatic circuit breaker
Hydrokit with 1 or 2 pumps with or without buffer
tank (500 L 400‑450, 1 000 L 470‑670)
Coils treatments
Mechanical gauges
Variable pump (for sizes 750‑800 upon request)
Desuperheater
Overload protection for compressors
Water filter
Fan speed control (‑14 °C in cooling mode –
standard as super low noise version)
Power factor corrector capacitors
Water flow switch
Several communication protocols
Unit protection grilles