Hydronics Brochure - FINAL - Flipbook - Page 32
GENERAL INDEX
Water source heat pumps
ECOi‑LOOP 15‑30 C/H · R410A
Rotary compressor.
Coaxial heat exchanger.
EC fan.
Horizontal installation.
Water source heat
pumps
Total capacity
Cooling 1)
Heating 2)
Nominal air flow
W
W
Dimension
Without air inlet/outlet options
Operating weight
Without air inlet/outlet options
LxWxH
m³/h
mm
kg
ECOi‑LOOP 15‑30 C ‑ cooling only
15
P‑LPE015CA
1 507
—
435
900 x 530 x 250
48
20
P‑LPE020CA
2 151
—
465
900 x 530 x 250
48
30
P‑LPE030CA
2 902
—
525
900 x 530 x 250
48
ECOi‑LOOP 15‑30 H ‑ heat pump
15
P‑LPE015HA
1 507
1 934
435
900 x 530 x 250
48
20
P‑LPE020HA
2 151
2 510
465
900 x 530 x 250
48
30
P‑LPE030HA
2 902
3 680
525
900 x 530 x 250
48
Hydraulic circuit information
Water source heat pumps
Water heat exchanger
Number / type
15
20
30
1 / coaxial
1 / coaxial
1 / coaxial
Maximum water pressure
bar
10
10
10
Connections ‑ inlet/outlet (Ø)
Inch
½ Male gas
½ Male gas
½ Male gas
Condensate outlet ‑ external (Ø)
mm
16
16
16
1) Nominal cooling capacities based on entering air temperature of 27 °C DB, 19 °C WB with entering water temperature of 30 °C. 2) Nominal heating capacities based on entering air temperature of 20 °C DB,
15 °C WB with entering water temperature of 20 °C.
* Check data and configuration on AC SELECT. POA: Price On Applications.
Accessories and options
Accessories and options
Accessories and options
Air outlet silencer
Drain pump
Basic or G3M1 filter
Electric heaters
RCS remote control (for controller with protocol
communication)
Circuit breaker
Flow switch control
Room temperature sensor
Modbus RTU protocol‑standard. Controller with
BACnet MSTP ‑ optional (BACnet IP, LON and
Modbus TCP/IP available upon request)
Insulation around the fan
SRC ‑ mini BMS controller
Drain outlet
Pressostatic valve (cooling only)
ECOi‑LOOP‑N 70‑135 H · R513A
Scroll compressor.
Coaxial heat exchanger.
EC fan.
Water source heat
pumps
Total capacity
Cooling 1)
Heating 2)
W
W
Many air inlet/outlet and water connection
configurations
Horizontal installation.
In‑line or perpendicular air flow.
Nominal air flow
Nominal static
pressure
Dimension
Without air inlet/outlet options
m³/h
Pa
mm
kg
Max (HS)
Operating weight
Without air inlet/outlet options
LxWxH
70
P‑LPN070HA
7 011
8 069
1 727
100
1 142 x 762 x 516
134
85
P‑LPN085HA
8 407
9 808
2 165
100
1 142 x 762 x 516
134
100
P‑LPN100HA
10 290
11 307
2 826
100
1 333 x 818 x 580
153
110
P‑LPN110HA
11 183
12 514
3 078
100
1 333 x 818 x 580
153
120
P‑LPN120HA
12 105
13 834
3 309
100
1 333 x 818 x 580
160
135
P‑LPN135HA
13 301
14 639
3 677
100
1 333 x 818 x 580
160
Hydraulic circuit information
Water source heat pumps
Water heat exchanger
Number / type
70
85
100
110
120
135
1 / coaxial
1 / coaxial
1 / coaxial
1 / coaxial
1 / coaxial
1 / coaxial
10
Maximum water pressure
Bar
10
10
10
10
10
Hydraulic connections ‑ inlet/outlet
Inch
1 Male gas
1 Male gas
1 Male gas
1 Male gas
1 Male gas
1 Male gas
Condensate outlet (Ø)
mm
19
19
19
19
19
19
1) Nominal cooling capacities based on entering air temperature of 27 °C DB, 19 °C WB with entering water temperature of 30 °C. 2) Nominal heating capacities based on entering air temperature of 20 °C DB,
15 °C WB with entering water temperature of 20 °C.
* Check data and configuration on AC SELECT. POA: Price On Applications.
32
Accessories and options
Accessories and options
Accessories and options
G2M1 filter or G3 filter
Drain pump
Circuit breaker
Electric heaters
RCS remote control (for controller with protocol
communication)
Modbus RTU protocol‑standard. Controller with
BACnet MSTP ‑ optional (BACnet IP, LON and
Modbus TCP/IP available upon request)
Flow switch control
Room temperature sensor
General default report
SRC ‑ mini BMS controller
Many air configurations