Hydronics Brochure - FINAL - Flipbook - Page 34
GENERAL INDEX
Water source heat pumps
ECOi‑LOOP HRW H and ECOi‑LOOP HRWE H · R407C
Rotary/scroll compressor.
Plate heat exchanger.
AC fan. Horizontal installation.
G2M1 filter.
Water source heat pumps
Total capacity
Nominal air flow
Cooling 1)
Heating 2)
W
W
Dimension
Operating weight
LxWxH
m³/h
mm
kg
ECOi‑LOOP HRW H ‑ heat pump
19
P‑LPHM019HA*** 3)
5 278
5 826
1 250
900 x 600 x 439
80
27
P‑LPHM027HA*** 3)
7 419
8 342
1 190
1 050 x 600 x 460
100
30
P‑LPHM030HA*** 3)
8 691
9 759
1 490
1 050 x 660 x 460
100
36
P‑LPHM036HA*** 3)
10 138
11 036
1 580
1 050 x 660 x 460
112
42
P‑LPHM042HA*** 3)
11 366
14 422
2 040
1 250 x 705 x 513
133
48
P‑LPHM048HA*** 3)
12 965
14 904
2 750
1 250 x 705 x 513
140
60
P‑LPHM060HA*** 3)
14 344
16 147
2 840
1 250 x 705 x 513
144
72
P‑LPHM072HA*** 3)
17 174
21 500
3 570
1 250 x 705 x 513
149
96
P‑LPHM096HA*** 3)
21 743
26 637
4 700
1 680 x 955 x 770
253
120
P‑LPHM120HA*** 3)
29 951
38 109
5 600
1 680 x 955 x 770
262
ECOi‑LOOP HRWE H ‑ heat pump
27
P‑LPHEM027HA*** 3)
7 320
9 252
1 180
1 050 x 660 x 460
112
30
P‑LPHEM030HA*** 3)
8 710
9 960
1 500
1 050 x 660 x 460
100
36
P‑LPHEM036HA*** 3)
11 060
12 200
1 580
1 250 x 705 x 513
133
42
P‑LPHEM042HA*** 3)
12 500
14 450
2 040
1 250 x 705 x 513
135
60
P‑LPHEM060HA*** 3)
16 700
18 800
2 840
1 250 x 705 x 583
149
72
P‑LPHEM072HA*** 3)
20 600
22 600
3 800
1 680 x 955 x 770
253
96
P‑LPHEM096HA*** 3)
24 500
28 500
4 700
1 680 x 955 x 770
259
Hydraulic circuit information
Water source heat pumps
Number of plate heat exchanger
Maximum water pressure
bar
Connections ‑ inlet/outlet (Ø)
Inch
Condensate outlet ‑ external (Ø)
mm
019
027
030
036
042
048
060
060 HE
072
072 HE
096
1
1
1
1
1
1
1
1
1
1
1
120
1
16
16
16
16
16
16
16
16
16
16
16
16
ISO G ¾ ISO G ¾ ISO G ¾ ISO G ¾ ISO G ¾ ISO G ¾ ISO G ¾
ISO G ¾
ISO G 1¼
ISO G 1¼ ISO G 1¼ ISO G 1¼
INT
INT
INT
INT
INT
INT
INT
INT
19
19
19
19
19
19
19
19
19
22
22
22
1) Nominal cooling capacities based on: entering air temperature of 27 °C DB, 19 °C WB with entering water temperature of 30 °C. 2) Nominal heating capacities based on: entering air temperature of 20 °C DB,
15 °C WB with entering water temperature of 20 °C. 3) *** HWA: units without RCS, HRA: units with RCS, HBA: units with RCS + EH, HHA: units with EH.
* Check data and configuration on the technical documentation. POA: Price On Applications.
Accessories and options
Accessories and options
Circuit breaker
Motorised water valve
Modbus RTU protocol‑standard. Controller with BACnet MSTP ‑ optional (BACnet IP,
LON and Modbus TCP/IP available upon request)
RCS remote control (for controller with protocol communication)
Electric heaters
SRC ‑ mini BMS controller
General alarm dry contact
G3 filter (available upon request)
Main switch
AC SELECT.
Smart and user-friendly selection tool. Configure
your air conditioning solution at required
conditions: https://acselect.panasonic.eu/
34
Room sensor