ECOi-LOOP-N EVO C - cooling only
P-LPVN030CA
ECOi-LOOP-N EVO H - reversible
P-LPVN030HA
Total cooling capacity 1)
Min ‑ Max 2)
W
1 687 ‑ 2 948
Sensible cooling capacity 1)
Min ‑ Max 2)
W
1 363 ‑ 2 337
W
2 004 ‑ 3 769
EER
Min ‑ Max 2)
Heating capacity 3)
Min ‑ Max 2)
COP
Min ‑ Max 2)
4,25 ‑ 3,06
4,53 ‑ 3,45
Ventilation
Number of fans
1
Nominal air flow (at low and high speeds)
Min ‑ Max 2)
m³/h
Motor power (at low and high speeds)
Min ‑ Max 2)
W
Air filter
Number / efficiency
290 ‑ 525
13 ‑ 54
1 / Basic or G3
Hydraulic circuit
Water heat exchanger
Number / type
1 / Coaxial
Maximum water pressure
Cooling Min ‑ Max 2)
Nominal water flow
bar
10
l/h
354 ‑ 662
458 ‑ 789
Heating Min ‑ Max 2)
l/h
Cooling Min ‑ Max 2)
kPa
9 ‑ 19,5
Heating Min ‑ Max 2)
kPa
12,3 ‑ 24,6
Connections ‑ inlet/outlet (Ø)
Inch
½ Male gas
Condensate outlet ‑ external (Ø)
mm
16
WPD at nominal water flow 4)
Refrigerant circuit
Number of refrigerant circuits
1
Compressor type
Inverter rotary
Load
g
514
Electrical data
Voltage
Power supply
V
230
Phase
Input power 5)
Single phase
Frequency
Hz
50 ±10%
Cooling Min ‑ Max 2)
W
397 ‑ 964
Heating Min ‑ Max 2)
W
442 ‑ 1 093
Number / capacity Min ‑ Max 2)
‑/W
1 / 600 + 600 ‑ 1 / 1 000 + 1 000
Input power Min ‑ Max 2)
W
1 200 ‑ 2 000
Sound power ‑ radiated
Min ‑ Max 2)
dB(A)
41,9 ‑ 51,5
Sound power ‑ discharge
Min ‑ Max 2)
dB(A)
47,9 ‑ 62,8
Sound pressure 7)
Min ‑ Max 2)
dB(A)
NR 7)
Min ‑ Max 2)
Electric heating coil 6)
Sound levels - without acoustic options
29,3 ‑ 43
25,8 ‑ 39,2
Sound levels - with air outlet silencer and insulation around the fan
Sound power ‑ radiated
Min ‑ Max 2)
dB(A)
42,3 ‑ 51,6
Sound power ‑ discharge
Min ‑ Max 2)
dB(A)
33,2 ‑ 44,4
Sound pressure 7)
Min ‑ Max 2)
dB(A)
NR 7)
Min ‑ Max 2)
24,5 ‑ 35
19,5 ‑ 30,4
Dimension - without air inlet/outlet options
Length
mm
900
Width
mm
636
Height
mm
250
kg
51
Weight - without air inlet/outlet options
Operating weight
1) Nominal cooling capacities based on entering air temperature of 27 °C DB, 19 °C WB with entering water temperature of 30 °C. 2) Thermal load. 3) Nominal heating capacities based on entering air
temperature of 20 °C DB, 15 °C WB with entering water temperature of 20 °C. 4) Without valve. 5) Input power at nominal conditions (compressor + fan at high speed). 6) Electric heating coil is available as an
option. 7) Informative data, considering an hypothetical sound attenuation of the room and installation of 21 dB. In‑line configuration with filter.
Accessories and options
Accessories and options
Air outlet silencer
Electric heaters
Basic or G3M1 filter
Flow switch control
Circuit breaker
General default report
Modbus RTU protocol‑standard. Controller with BACnet MSTP ‑ optional (BACnet IP,
LON and Modbus TCP/IP available upon request)
Insulation around the fan
Drain outlet
Room temperature sensor
Many air inlet/outlet and water connection configurations
Drain pump
Accessories supplied loose
Accessories supplied loose
P-393446
RCS kit remote control with thermostat (POL822)
P-375281
SRC ‑ mini BMS controller (only with Modbus RTU)
EC MOTOR
GREEN VENTILATION
HIGH
EER
HIGH
COP
4,25
4,53
COAXIAL HEAT
EXCHANGER
INVERTER ROTARY
COMPRESSOR
P-372061
SUPER QUIET
Kit remote keyboard panel
VERY HIGH
PERFORMANCE
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.