Hydronics Brochure - FINAL - Flipbook - Page 81
R513A
INDEX HYDRONICS
WATER SOURCE HEAT PUMPS
Technical features
ECOi-LOOP-N FS H - reversible
P-LPFSN07HA
P-LPFSN09HA
Total cooling capacity 1)
W
1690
2040
Sensible cooling capacity 1)
W
1410
1600
Input power (with EC / AC fan) 2)
W
EER according to EN 14511 (with EC / AC fan)
345 / 355
480 / 487
4,9 / 4,75
4,25 / 4,19
Heating capacity 3)
W
1790
2630
Input power (with EC / AC fan) 2)
W
395 / 405
610 / 617
4,6 / 4,41
4,31 / 4,26
340
COP according to EN 14511 (with EC / AC fan)
Ventilation
Min
m³/h
250
Nominal
m³/h
340
400
Max
m³/h
400
460
Nominal input power (with EC / AC fan)
W
15 / 25
20 / 27
Motor power (with EC / AC fan)
W
40 / 75
40 / 75
1 / G2
1 / G2
Air flow
Air filter
Number / efficiency
Hydraulic circuit
Number of plate heat exchanger
1
1
Bar
10
10
Cooling 1)
l/h
351
434
Heating 3)
l/h
405
586
l/h
180
180
Cooling 1)
kPa
3,8
5,8
Heating 3)
kPa
5,1
10,8
Hydraulic connections ‑ inlet/outlet
Inch
Female ISO G ½ INT
Female ISO G ½ INT
Condensate outlet (Ø)
mm
15 x 20
15 x 20
Maximum water pressure
Nominal water flow
Cutoff water flow
WPD at nominal water flow
Refrigerant circuit
Number of refrigerant circuits
Type of compressor
Load
g
1
1
Rotary
Rotary
500
490
Electrical data
Voltage
Power supply
V
Phase
Frequency
230
230
Single phase
Single phase
50 ±10%
Hz
50 ±10%
Maximum current 4)
A
4,6
5,7
Starting current 5)
A
16
16,5
Sound levels
Sound power Lw
Lo / Med / Hi
dB(A)
47,2 / 49,8 / 51,5
49,8 / 51,5 / 54,3
Sound pressure Lp
Lo / Med / Hi
dB(A)
38,2 / 40,8 / 42,5
40,8 / 42,5 / 45,3
NR
Lo / Med / Hi
dB(A)
32 / 34 / 36
34 / 36 / 40
Sound levels - extra low noise version
Sound power Lw
Lo / Med / Hi
dB(A)
42,5 / 44,6 / 46,5
44,7 / 46,5 / 48,6
Sound pressure Lp
Lo / Med / Hi
dB(A)
33,5 / 35,6 / 37,5
35,7 / 37,5 / 39,6
NR
Lo / Med / Hi
dB(A)
28 / 30 / 32
30 / 32 / 34
Standard with cabinet (VC)
LxWxH
mm
1 138 x 260 x 720 min / 750 max (821 with feet)
1 138 x 260 x 720 min / 750 max (821 with feet)
Low height with cabinet (VCL)
LxWxH
mm
1 322 x 260 x 582 min / 612 max (683 with feet)
1 322 x 260 x 582 min / 612 max (683 with feet)
Standard without cabinet (VN)
LxWxH
mm
1 055 (1 084 with feet) x 241 x 667 min / 697 max
(769 with feet)
1 055 (1 084 with feet) x 241 x 667 min / 697 max
(769 with feet)
Low height without cabinet (VNL)
LxWxH
mm
1 185 (1 270 with feet) x 241 x 525 min / 555 max
(626 with feet)
1 185 (1 270 with feet) x 241 x 525 min / 555 max
(626 with feet)
kg
55 / 70
58 / 73
Dimension
Weight
Without cabinet / with cabinet ‑ operating
1) Nominal cooling capacities based on: entering air temperature of 27 °C DB/19 °C WB, with entering water temperature of 30 °C. 2) Absorbed power (compressor + fan) at nominal conditions. 3) Nominal
heating capacities based on: entering air temperature of 20 °C DB/15 °C WB, with entering water temperature of 20 °C. 4) Maximum currents are given at +/‑ 5%. 5) Starting currents are given at +/‑ 10%.
Accessories and options
Accessories and options
Modbus RTU protocol‑standard. Controller with BACnet MSTP ‑ optional (BACnet IP,
LON and Modbus TCP/IP available upon request)
General remote alarm contact
EC fan
Many electric, hydraulic and aeraulic configurations
Feet
Thermal overload
Accessories supplied loose
Low noise
Accessories supplied loose
P-393446
RCS kit remote control with thermostat (POL822)
P-372734
Kit front air intake cabinet
P-375281
SRC ‑ mini BMS controller (only with Modbus RTU)
P-372642
Kit front air intake cabinet (low height)
P-372061
Kit remote keyboard panel
HIGH
EER
HIGH
COP
4,90
4,60
EC MOTOR
GREEN VENTILATION
PLATE HEAT
EXCHANGER
ROTARY
COMPRESSOR
SUPER QUIET
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
81