Hydronics Brochure - FINAL - Flipbook - Page 93
FAN COIL
CHILLERS
UNITS
FAN COIL UNITS INDEX
Technical features
Fan coil cassette AC fan
P-FQ20
P-FQ30
P-FQ40
P-FQ50
P-FQ60
P-FQ70
S2 / S3 / S4 1)
S2 / S3 / S4 1)
S2 / S3 / S4 1)
S2 / S3 / S4 1)
S2 / S3 / S4 1)
S2 / S3 / S4 1)
2-pipes
Total cooling capacity 2)
kW
1,54 / 1,76 / 2,36
1,87 / 2,87 / 3,99
2,78 / 3,49 / 4,69
3,35 / 4,43 / 6,07
3,69 / 5,46 / 7,18
4,04 / 6,48 / 8,61
Sensible capacity 2)
kW
1,29 / 1,48 / 1,98
1,41 / 2,17 / 3,04
2,08 / 2,67 / 3,62
2,52 / 3,35 / 4,47
2,67 / 4,06 / 5,42
2,97 / 4,85 / 6,34
695 / 1 111 / 1 476
Water flow 2)
l/h
265 / 303 / 404
323 / 493 / 683
478 / 597 / 801
576 / 762 / 1 042
636 / 937 / 1 233
Water pressure drop 2)
kPa
4,0 / 5,0 / 10,0
3,0 / 7,0 / 14,0
6,0 / 10,0 / 18,0
7,0 / 12,0 / 22,0
3,0 / 6,0 / 11,0
5,0 / 12,0 / 20,0
Heating capacity 3)
kW
1,92 / 2,17 / 2,74
1,94 / 3,15 / 3,68
3,16 / 3,92 / 5,28
3,80 / 5,08 / 6,84
3,85 / 6,26 / 8,51
4,38 / 7,95 / 10,28
Water flow 3)
l/h
331 / 374 / 472
334 / 543 / 634
544 / 675 / 909
655 / 875 / 1 178
663 / 1 078 / 1 466
754 / 1 369 / 1 771
Water pressure drop 3)
kPa
6,0 / 7,0 / 10,0
3,0 / 9,0 / 11,0
7,0 / 10,0 / 17,0
8,0 / 13,0 / 22,0
3,0 / 8,0 / 14,0
6,0 / 17,0 / 26,0
Total cooling capacity 2)
kW
1,29 / 1,48 / 1,97
1,99 / 2,68 / 3,37
2,55 / 3,21 / 4,00
—
2,97 / 4,96 / 6,63
3,17 / 6,01 / 7,55
Sensible capacity 2)
kW
1,18 / 1,38 / 1,84
1,49 / 2,07 / 2,65
2,03 / 2,58 / 3,30
—
2,23 / 3,77 / 5,06
2,38 / 4,68 / 5,95
Water flow 2)
l/h
232 / 258 / 359
342 / 465 / 576
437 / 563 / 683
—
511 / 851 / 1 137
543 / 1 030 / 1 294
4-pipes
Water pressure drop 2)
kPa
6,0 / 8,0 / 13,0
4,0 / 7,0 / 11,0
6,0 / 10,0 / 15,0
—
5,0 / 14,0 / 24,0
6,0 / 20,0 / 30,0
Heating capacity 4)
kW
1,09 / 1,27 / 1,67
3,10 / 4,40 / 5,46
4,32 / 5,00 / 5,80
—
5,28 / 7,79 / 10,04
6,43 / 10,07 / 12,77
Water flow 4)
l/h
94 / 109 / 144
267 / 379 / 470
372 / 431 / 500
—
455 / 671 / 865
554 / 867 / 1 100
Water pressure drop 4)
kPa
15,0 / 17,0 / 28,0
7,0 / 13,0 / 20,0
13,0 / 17,0 / 23,0
—
4,0 / 7,0 / 11,0
5,0 / 11,0 / 16,0
2‑pipes
dB(A)
38 / 42 / 49
35 / 47 / 53
42 / 48 / 57
35 / 40 / 49
38 / 46 / 54
40 / 52 / 59
4‑pipes
dB(A)
37 / 41 / 49
35 / 47 / 53
42 / 48 / 57
—
38 / 46 / 54
40 / 52 / 59
2‑pipes
dB(A)
27 / 31 / 40
26 / 35 / 44
33 / 39 / 48
26 / 31 / 40
29 / 37 / 45
31 / 43 / 50
4‑pipes
dB(A)
Sound levels
Sound power
Sound pressure 5)
NR 5)
27 / 31 / 40
26 / 35 / 44
33 / 39 / 48
—
29 / 37 / 45
31 / 43 / 50
2‑pipes
23 / 27 / 35
20 / 30 / 39
28 / 34 / 43
21 / 26 / 35
22 / 32 / 40
25 / 38 / 50
4‑pipes
23 / 27 / 35
20 / 30 / 39
28 / 34 / 43
—
22 / 32 / 40
25 / 38 / 45
Ventilation
Number of fans
Air flow
m³/h
Filter
1
1
1
1
1
1
360 / 450 / 659
320 / 504 / 734
486 / 626 / 900
529 / 720 / 979
500 / 824 / 1 159
601 / 1 080 / 1 447
G1
G1
G1
G1
G1
G1
Electrical data
Voltage
Power supply
V
Phase
Consumption
230
230
230
230
230
230
Single phase
Single phase
Single phase
Single phase
Single phase
Single phase
Frequency
Hz
50 / 60
50 / 60
50 / 60
50 / 60
50 / 60
50 / 60
2‑pipes
W
25 / 35 / 58
17 / 34 / 58
38 / 58 / 99
28 / 41 / 66
34 / 61 / 88
44 / 92 / 125
W
25 / 35 / 58
17 / 34 / 58
38 / 58 / 99
—
34 / 61 / 88
44 / 92 / 125
W
1 500
2 500
2 500
2x1 500
2x1 500
2x1 500
Female gas
threaded
Female gas
threaded
Female gas
threaded
Female gas
threaded
Female gas
threaded
Female gas
threaded
4‑pipes
Electric heater
Water connections
Connection type
2 or 4‑pipes
Cooling
Inch
¾
¾
¾
1
1
1
4‑pipes
Heating
Inch
½
½
½
—
¾
¾
Dimension
With plastic diffuser
HxWxD
mm
334 x 720 x 720
334 x 720 x 720
334 x 720 x 720
339 x 960 x 960
339 x 960 x 960
339 x 960 x 960
With IRYS COANDA 180
HxWxD
mm
353 x 595 x 595
353 x 595 x 595
353 x 595 x 595
366 x 849 x 849
366 x 849 x 849
366 x 849 x 849
With IRYS COANDA 360
HxWxD
mm
341 x 595 x 595
341 x 595 x 595
341 x 595 x 595
358 x 849 x 849
358 x 849 x 849
358 x 849 x 849
kg
14,8
16,5
16,5
37,1
37,1
39,6
FCEER
A to E
D
C
D
C
C
C
FCCOP
A to E
E
D
D
C
C
D
FCEER
A to E
E
C
D
—
C
D
FCCOP
A to E
E
C
D
—
C
C
Weight
Weight
Energy efficiency class 6)
Fan coil cassette AC fan
2-pipes
4-pipes
1) Fan speeds. 2) According to Eurovent standard. Air: 27 °C DB/19 °C WB, chilled water: 7 °C/12 °C. 3) According to Eurovent standard. Air: 20 °C, hot water: 45 °C/40 °C. 4) According to Eurovent standard. Air:
20 °C, hot water: 65 °C/55 °C. 5) Informative data, considering an hypothetical sound attenuation of the room and installation of 9 dB(A). 6) According to Eurovent. * Drain pump and G1 air filter are included as
standard.
Accessories and options
Accessories and options
2 way or 3 way valves
Plastic or metallic (IRYS COANDA) diffusers (mandatory)
Auxiliary drain pan
SRC ‑ mini BMS controller
Electric heaters (from 1 500 W to 3 000 W)
Plogic controller (other electromechanical or electronic control systems also
available)
Electromechanical sensor for automatic change over
Fresh air intake
G4 filter
TControl EASY 3S and TControl POD glass controllers (other electromechanical or
electronic control systems also available)
IRC: infrared remote control for Plogic
WRC: wall‑mounted remote control for Plogic
Modbus communication board for Plogic
ErP
✔
SUPER QUIET
ErP compliant following COMMISSION REGULATION (EU) 2016/2281.
91