Hydronics Brochure - FINAL - Flipbook - Page 97
FAN COIL
CHILLERS
UNITS
FAN COIL UNITS INDEX
Technical features
Fan coil wall DC fan - FK1
S-19FK1E
S-24FK1E
S-27FK1E
S-36FK1E
S-45FK1E
S-52FK1E
H/M/L
H/M/L
H/M/L
H/M/L
H/M/L
H/M/L
2-pipes, with/without 3 way valve
Total cooling capacity 1)
kW
1,90 / 1,65 / 1,40
2,41 / 2,17 / 1,92
2,73 / 2,51 / 2,02
3,61 / 3,11 / 2,65
4,50 / 3,78 / 3,02
5,23 / 4,63 / 4,03
Sensible capacity 1)
kW
1,54 / 1,35 / 1,10
1,91 / 1,71 / 1,50
2,19 / 2,00 / 1,59
2,98 / 2,52 / 2,12
3,41 / 2,84 / 2,25
4,02 / 3,51 / 3,04
908 / 830 / 724
Water flow 1)
l/h
342 / 295 / 250
432 / 389 / 344
489 / 449 / 362
648 / 556 / 473
809 / 680 / 539
Water pressure drop (coil only)
kPa
8/6/4
13 / 11 / 8
17 / 14 / 9
30 / 22 / 16
42 / 30 / 19
56 / 44 / 34
Water pressure drop (with 3 way valve) 1)
kPa
29 / 23 / 18
36 / 29 / 25
44 / 39 / 26
74 / 57 / 42
110 / 80 / 53
142 / 112 / 90
Air flow 1)
m³/h
345 / 276 / 230
416 / 361 / 324
480 / 434 / 343
710 / 572 / 462
753 / 603 / 488
879 / 753 / 637
Input power 1)
W
12 / 11 / 10
14 / 12 / 12
16 / 14 / 12
26 / 19 / 15
22 / 17 / 13
29 / 23 / 18
Sound pressure Lp 1) 2)
dB(A)
27
26
29
39
35
40
Sound power Lw 1)
dB(A)
43
42
45
55
51
56
Heating capacity 3)
kW
2,23 / 1,92 / 1,59
2,72 / 2,39 / 1,97
3,01 / 2,64 / 2,18
4,03 / 3,48 / 2,89
5,13 / 4,21 / 3,09
5,33 / 4,72 / 4,03
Water flow 3)
l/h
381 / 329 / 281
481 / 417 / 339
533 / 463 / 379
715 / 614 / 508
898 / 740 / 544
931 / 827 / 710
Water pressure drop (coil only)
kPa
10 / 8 / 5
16 / 12 / 8
20 / 15 / 10
36 / 27 / 18
52 / 36 / 19
56 / 44 / 33
Water pressure drop (with 3 way valve) 3)
kPa
30 / 24 / 18
39 / 31 / 23
47 / 36 / 25
72 / 60 / 42
118 / 82 / 46
128 / 97 / 74
Air flow 3)
m³/h
406 / 314 / 253
489 / 425 / 343
545 / 471 / 379
765 / 646 / 517
925 / 730 / 511
960 / 810 / 672
Input power 3)
W
13 / 12 / 10
15 / 14 / 12
17 / 15 / 13
28 / 21 / 16
32 / 21 / 14
35 / 26 / 19
Sound pressure Lp 2) 3)
dB(A)
29 / 27 / 24
29 / 26 / 22
32 / 28 / 23
41 / 36 / 30
42 / 36 / 28
43 / 39 / 34
Sound power Lw 3)
dB(A)
45 / 43 / 40
45 / 42 / 38
48 / 44 / 39
57 / 52 / 46
58 / 52 / 44
59 / 55 / 50
Gas female
threaded
Gas female
threaded
Gas female
threaded
Gas female
threaded
Gas female
threaded
Gas female
threaded
Tentative data
Water Connection
Connection type
Inch
1/2
1/2
1/2
1/2
1/2
1/2
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
mm
295 x 890 x 244
295 x 890 x 244
295 x 890 x 244
295 x 890 x 244
295 x 1060 x 249
295 x 1060 x 249
kg
12
13
13
13
14
14
nanoe X Generator
Dimensions and weight
Dimension
HxWxD
Weight
Energy efficiency class 1)
Fan coil wall DC fan - FK1
2-pipes
FCEER 1)
ηs,c
%
A to E
FCCOP 3)
ηs,h
%
A to E
B
B
B
B
A
A
144,2
166,9
172,1
169,3
226,8
213,0
B
B
B
B
B
B
160,0
167,0
170,5
173,4
208,5
198,0
1) According to Eurovent standard. Air: 27 °C DB/19 °C WB, chilled water: 7 °C/12 °C. 2) The sound pressure of the indoor unit shows the value measured of a position of 1 m in front of the main body and 0,8 m
below the unit. The sound pressure is measured in accordance with JIS C 9612. 3) According to Eurovent standard. Air: 20 °C, hot water: 45 °C/40 °C.
New fan coil wall.
First Panasonic water fan coil unit integrated with
nanoe™ X technology.
Fan coil wall unit with stylish design, ideal for
commercial and residential applications in combination
with Aquarea Heat Pumps. The units are integrated with
nanoe™ X technology to improve protection 24/7
(Generator Mark 3).
Bringing nature’s balance
indoors.
The new fan coil wall is
equipped with nanoe™ X for
improved indoor air quality.
nanoe™ X, technology with the
benefits of hydroxyl radicals.
7 effects of nanoe™ X – Panasonic
unique technology.
Capacity to inhibit 5 types of pollutants
Bacteria and
viruses
ErP
✔
SUPER QUIET
Mould
Allergens
Pollen
Deodorises
Moisturises
Odours
Skin and hair
Hazardous
substances
ErP compliant following COMMISSION REGULATION (EU) 2016/2281.