IRE A2W Price List FINAL - Flipbook - Page 25
AQUAREA
AQUAREA INDEX
Aquarea T-CAP Hydraulic
Big Aquarea T-CAP Hydraulic M Series Three phase · R290
Water outlet temperature up to 75 °C.
Maintained capacity at 55 °C down to -15 °C.
Wi-Fi adapter included for smart control via Panasonic Comfort Cloud App.
Operation range down to -25 °C in heating.
R290
Included
Outdoor unit
Combination table
Heating capacity
Three phase
Indoor unit
20,0 kW
25,0 kW
30,0 kW
WH-WXG20ME8
WH-WXG25ME8
WH-WXG30ME8
RRP €
14,481
16,543
19,640
Control module
3ph
WH-CME8L
1,590
✔
✔
✔
Remote controller with Wi-Fi adapter
—
CZ-RTW2TAW1C
867
✔
✔
✔
Outdoor unit
3ph
Cooling
capacity / EER
SCOP
Energy class
(heating)
Piping information
Sound
power 1)
Dimension
A +7 °C,
W 35 °C
A +7 °C,
W 55 °C
A 35 °C,
W 18 °C at
Comfort mode
W 35 °C /
W 55 °C
W 35 °C /
W 55 °C
Pipe length
range
(std / max)
Elevation
difference
(in / out)
Heat
HxWxD
Weight
kW / COP
kW / COP
kW / EER
A+++ to D
m
m
dB(A)
mm
kg
WH-WXG20ME8
20,00 / 4,80
20,00 / 3,18
20,00 / 4,79
4,36 / 3,59
A++ / A++
—/—
—
56
1 645 x 1 500 x 460
240
WH-WXG25ME8
25,00 / 4,50
25,00 / 3,00
25,00 / 4,47
4,25 / 3,57
A++ / A++
—/—
—
59
1 645 x 1 500 x 460
240
WH-WXG30ME8
30,00 / 4,40
30,00 / 3,00
30,00 / 4,10
3,95 / 3,46
A++ / A++
—/—
—
61
1 645 x 1 500 x 460
240
Control module
3ph
Heating capacity / COP
WH-CME8L
Field supply electrical
backup heater
Recommended fuse,
supply 2)
kW
Up to 18 kW
Recommended minimum
cable size, supply 2)
Connecting cable to the Dimension
outdoor unit size
HxWxD
Net weight
A
mm²
mm²
mm
kg
20 (≤9kW)
40 (9kW< ≤18kW)
5x2,5 (≤12kW)
5x4,0 (12kW< ≤15kW)
5x6,0 (15kW< ≤18kW)
2x0,75
450 x 450 x 116
7
1) Sound power level in accordance to EN 12102 under conditions of the EN 14825 (part load). 2) Check local regulations. * Available in December 2024. Tentative data. ** EER and COP calculation is based in
accordance to EN 14511. *** This product is designed to comply with the European drinking water standard (EU) 2020/2184. The lifespan of the product is not guaranteed in the case of the use of groundwater,
such as spring water or well water, the use of tap water when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and warranty costs related to these cases are the
customer’s responsibility.
Boost the capacity up to 300 kW by connecting your
unit in cascade.
Designed for central heating projects, small hotels, supermarkets
and restaurants, the cascade manager manages the demand for
energy-efficient heating and cooling balancing working hours.
Aquarea Cascade Edge. PAW-A2W-CME4 and PAW-A2W-CME10.
Cascade up to 4 or 10 units and remotely control your heat pumps via
smartphone, tablet or PC.
A Modbus gateway is required for each connected device: CZ-NSMB (for Big
Aquarea M Series) or PAW-AZAW-MBS-M.
P-Smart Edge.
Control and monitoring online solution for
Aquarea Cascade Edge systems wherever
you are. In a simple click, configure and
receive status updates of all your units.
Aquarea Cascade Edge
Dimensions (H x W x D)
250 x 320 x 155 mm
Weight
2 kg
Degree of protection
IP65
P-Smart Nexus.
Smart multi-site online control
which allows a remote global
supervision of all your sites.
25