IRE A2W Price List FINAL - Flipbook - Page 28
GENERAL INDEX
Aquarea High Performance Split
Aquarea High Performance All in One 185L K Series Single phase · R32
Optional Wi-Fi adapter (CZ-TAW1C).
Indoor unit (H x W x D): 1 642 x 599 x 602 mm.
Operation range down to -25 °C 1) in heating.
Optional
Indoor unit
RRP Outdoor unit
Heating capacity /
COP
Heating
Cooling
capacity / W 35 °C / W 55 °C
EER
DHW
A +7 °C,
W 35 °C
A +7 °C,
W 55 °C
A 35 °C,
W 18 °C
SCOP
Energy
class
Energy
class
Weight
RRP
Sound
Dimension /
power 2) Weight
COPdhw
€ WH-
Heat
HxWxD
dB(A)
mm / kg
kW / COP
kW / COP
kW / EER
A+++ to D
A+ to F
WH-ADC0309K3E5
3,20 / 5,33
3,20 / 2,81 3,20 / 4,71 5,07 / 3,47
A+++ / A++
A+
3,20
100
5,599 WH-UDZ03KE5 55
622 x 824 x 298 / 37
1,940
WH-ADC0309K3E5
5,00 / 5,10 5,00 / 3,03 5,00 / 4,90 5,12 / 3,63
A+++ / A++
A+
3,50
100
5,599 WH-UDZ05KE5 55
795 x 875 x 380 / 55
2,103
WH-ADC0309K3E5
7,00 / 4,86 7,00 / 2,92 6,70 / 4,72 4,90 / 3,62
A+++ / A++
A+
3,50
100
5,599 WH-UDZ07KE5 56
795 x 875 x 380 / 55
2,260
WH-ADC0309K3E5
9,00 / 4,55 8,90 / 2,93 9,00 / 4,18 4,44 / 3,41
A+++ / A++
A+
3,50
100
5,599 WH-UDZ09KE5 56
795 x 875 x 380 / 55
2,406
WH-ADC0912K6E5
12,10 / 4,78 12,00 / 2,96 10,70 / 3,92 4,58 / 3,33
A+++ / A++
A+
2,50
101
7,366 WH-UDZ12KE5 65
1340 x 900 x 320 / 88
3,008
WH-ADC16K6E5
16,00 / 4,31 14,70 / 2,72 13,00 / 3,80 4,46 / 3,46
A+++ / A++
A
2,50
101
7,401 WH-UDZ16KE5 65
1340 x 900 x 320 / 88
3,610
kg
€
Piping information
Kit
kW
3,0
5,0
7,0
9,0
12,0
16,0
Piping diameter (liquid - gas)
Inch
¼-½
¼-⅝
¼-⅝
¼-⅝
¼-½
¼-⅝
Pipe length range
m
3 ~ 25
3 ~ 40 (3 ~ 50) 1)
3 ~ 40 (3 ~ 50) 1)
3 ~ 40 (3 ~ 50) 1)
3 ~ 30 (3 ~ 50) 3)
3 ~ 30 (3 ~ 50) 3)
Elevation difference (in / out)
m
20
30
30
30
20
20
Pre-charged pipe length
m
10
10
10
10
10
10
Additional gas amount
g/m
20
25
25
25
30
30
Electrical information (power supply to indoor)
Single phase (3 kW heater)
Single phase (6 kW heater)
Kit
kW
3,0
5,0
7,0
9,0
3,0
5,0
7,0
9,0
12,0
16,0
Electric backup heater
kW
3,00
3,00
3,00
3,00
6,00
3,00
6,00
6,00
6,00
6,00
Recommended fuse 4)
A
16 / 16
16 / 16
16 / 30
25 / 16
16 / 30
25 / 16
25 / 30
25 / 30
30 / 30
30 / 30
mm²
3x1,5 /
3x1,5
3x1,5 /
3x1,5
3x1,5 /
3x4,0
3x2,5 /
3x1,5
3x1,5 /
3x4,0
3x2,5 /
3x1,5
3x2,5 /
3x4,0
3x2,5 /
3x4,0
3x4,0 /
3x4,0
3x4,0 /
3x4,0
Recommended minimum cable size, supply 1 / 2 4)
1) Operation range down to -25 °C in heating with 3 ~ 40 m pipe length range, operation range down to -15 °C in heating with 3 ~ 50 m pipe length range. 2) Sound power level in accordance to EN 12102 under
conditions of the EN 14825. 3) Ambient temperature down to -10 °C. Below -10 °C, permitted piping length and elevation difference is 3 ~ 30 m, 20 m. 4) Check local regulations. * Available in Summer 2025.
Tentative data. ** EER and COP calculation is based in accordance to EN 14511. *** This product is designed to comply with the European drinking water standard (EU) 2020/2184. The lifespan of the product is
not guaranteed in the case of the use of groundwater, such as spring water or well water, the use of tap water when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and
warranty costs related to these cases are the customer’s responsibility.
28