IRE A2W Price List FINAL - Flipbook - Page 29
AQUAREA
AQUAREA INDEX
Aquarea High Performance Split
Aquarea High Performance All in One 185L K Series
Single phase with Electrical Anode · R32
Optional Wi-Fi adapter (CZ-TAW1C).
Indoor unit (H x W x D): 1 642 x 599 x 602 mm.
Operation range down to -25 °C 1) in heating.
Optional
Indoor unit
RRP Outdoor unit
Heating capacity /
COP
Heating
Cooling
capacity / W 35 °C / W 55 °C
EER
DHW
A +7 °C,
W 35 °C
A +7 °C,
W 55 °C
A 35 °C,
W 18 °C
SCOP
Energy
class
Energy
class
WH-
kW / COP
kW / COP
kW / EER
A+++ to D
A+ to F
kg
ADC0309K3E5AN
3,20 / 5,33 3,20 / 2,81 3,20 / 4,71 5,07 / 3,47
A+++ / A++
A+
3,20
100
ADC0309K3E5AN
5,00 / 5,10 5,00 / 3,03 5,00 / 4,90 5,12 / 3,63
A+++ / A++
A+
3,50
100
ADC0309K3E5AN
7,00 / 4,86 7,00 / 2,92 6,70 / 4,72 4,90 / 3,62
A+++ / A++
A+
3,50
100
ADC0309K3E5AN
9,00 / 4,55 8,90 / 2,93 9,00 / 4,18 4,44 / 3,41
A+++ / A++
A+
3,50
ADC0912K6E5AN
12,10 / 4,78 12,00 / 2,96 10,70 / 3,92 4,58 / 3,33
A+++ / A++
A+
ADC16K6E5AN
16,00 / 4,31 14,70 / 2,72 13,00 / 3,80 4,46 / 3,46
A+++ / A++
A
Weight
RRP
Sound
Dimension /
power 2) Weight
COPdhw
Heat
HxWxD
€ WH-
dB(A)
mm / kg
5,291 UDZ03KE5
55
622 x 824 x 298 / 37
1,940
5,291 UDZ05KE5
55
795 x 875 x 380 / 55
2,103
5,291 UDZ07KE5
56
795 x 875 x 380 / 55
2,260
100
5,291 UDZ09KE5
56
795 x 875 x 380 / 55
2,406
2,50
101
6,077 UDZ12KE5
65
1340x900x320/88
3,008
2,50
101
7,401 UDZ16KE5
65
1340x900x320/88
3,610
€
Piping information
Kit
kW
3,0
5,0
7,0
9,0
12,0
16,0
Piping diameter (liquid - gas)
Inch
¼-½
¼-⅝
¼-⅝
¼-⅝
¼-½
¼-⅝
Pipe length range
m
3 ~ 25
3 ~ 40 (3 ~ 50) 1)
3 ~ 40 (3 ~ 50) 1)
3 ~ 40 (3 ~ 50) 1)
3 ~ 30 (3 ~ 50) 3)
3 ~ 30 (3 ~ 50) 3)
Elevation difference (in / out)
m
20
30
30
30
20
20
Pre-charged pipe length
m
10
10
10
10
10
10
Additional gas amount
g/m
20
25
25
25
30
30
Electrical information (power supply to indoor)
Single phase (3 kW heater)
Single phase (6 kW heater)
Kit
kW
3,0
5,0
7,0
9,0
3,0
5,0
7,0
9,0
12,0
16,0
Electric backup heater
kW
3,00
3,00
6,00
3,00
6,00
3,00
6,00
6,00
6,00
6,00
Recommended fuse 4)
A
16 / 16
16 / 16
16 / 30
25 / 16
16 / 30
25 / 16
25 / 30
25 / 30
30 / 30
30 / 30
mm²
3x1,5 /
3x1,5
3x1,5 /
3x1,5
3x1,5 /
3x4,0
3x2,5 /
3x1,5
3x1,5 /
3x4,0
3x2,5 /
3x1,5
3x2,5 /
3x4,0
3x2,5 /
3x4,0
3x4,0 /
3x4,0
3x4,0 /
3x4,0
Recommended minimum cable size, supply 1 / 2 4)
1) Operation range down to -25 °C in heating with 3 ~ 40 m pipe length range, operation range down to -15 °C in heating with 3 ~ 50 m pipe length range. 2) Sound power level in accordance to EN 12102 under
conditions of the EN 14825. 3) Ambient temperature down to -10 °C. Below -10 °C, permitted piping length and elevation difference is 3 ~ 30 m, 20 m. 4) Check local regulations. * Available in Summer 2025.
Tentative data. ** EER and COP calculation is based in accordance to EN 14511. *** This product is designed to comply with the European drinking water standard (EU) 2020/2184. The lifespan of the product is
not guaranteed in the case of the use of groundwater, such as spring water or well water, the use of tap water when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and
warranty costs related to these cases are the customer’s responsibility.
Heating demand calculator.
Hydraulic scheme generator.
This software can quickly and easily determine
the heating requirements for the rooms in a
project. The Heating demand calculator will help
determine approximately how much power is
needed to heat each room individually. The result
in kilowatts will help you choose the space heater
best suited to your needs.
Available on PRO Club.
The Aquarea Hydraulic Scheme Generator (HSG)
allows users to select a hydraulic schematic
according to their installation requirements. This
will be accompanied by the relevant electrical
connection schematic and component list.
Available on PRO Club.
29