IRE A2W Price List FINAL - Flipbook - Page 37
AQUAREA
AQUAREA INDEX
Aquarea T-CAP Split
Aquarea T-CAP Bi-bloc K Series Single phase / Three phase · R32
Optional Wi-Fi adapter (CZ-TAW1C).
Indoor unit (H x W x D): 892 x 500 x 348 mm.
Operation range down to -28 °C in heating.
Optional
Indoor unit
RRP Outdoor unit
Heating capacity / COP
Cooling
capacity / EER
Heating W 35 °C / W 55 °C
A +7 °C,
W 35 °C
A +7 °C,
W 55 °C
A 35 °C,
W 7 °C
SCOP
WH-
kW / COP
kW / COP
kW / EER
A+++ to D
kg
SXC09K6E5
9,00 / 5,03
9,00 / 3,07
8,80 / 4,63
4,96 / 3,57
A+++ / A++
41
SXC12K6E5
12,10 / 4,84 12,10 / 3,04 10,70 / 3,92
4,96 / 3,57
A+++ / A++
41
SXC09K9E8
9,00 / 5,03
8,80 / 4,63
4,96 / 3,57
A+++ / A++
41
SXC12K9E8
12,10 / 4,84 12,10 / 3,04 10,70 / 3,92
4,58 / 3,46
A+++ / A++
SXC16K9E8
16,00 / 4,38 16,00 / 2,72 15,50 / 3,60
4,46 / 3,31
A+++ / A++
9,00 / 3,07
RRP
Sound
power 1)
Dimension / Weight
Heat
HxWxD
€ WH-
dB(A)
mm / kg
3,376 UXZ09KE5
65
1 340 x 900 x 320 / 88
3,233
3,369 UXZ12KE5
65
1 340 x 900 x 320 / 88
4,503
3,326 UXZ09KE8
65
1 340 x 900 x 320 / 90
4,528
41
3,937 UXZ12KE8
65
1 340 x 900 x 320 / 90
4,904
42
4,840 UXZ16KE8
65
1 340 x 900 x 320 / 103
5,392
Energy class
Piping information
Kit
Weight
€
Electrical information (power supply to indoor)
kW
9,0
12,0
9,0
12,0
16,0
Single
phase
(3 kW)
Single phase
(6 kW)
Three
phase
(3 kW)
Three phase (9 kW)
Piping diameter (liquid - gas)
Inch
¼-½ ¼-½ ¼-½ ¼-½ ¼-½
Pipe length range
m
3 ~ 30 3 ~ 30 3 ~ 30 3 ~ 30 3 ~ 30
Kit
kW
9,0
9,0
12,0
9,0
9,0
12,0
16,0
Elevation difference (in / out)
m
20
20
20
20
20
Electric backup heater
kW
3,00
6,00
6,00
3,00
9,00
9,00
9,00
Pre-charged pipe length
m
10
10
10
10
10
Additional gas amount
g/m
30
30
30
30
30
Recommended fuse
A
30 /
15 or 16
30 / 30
30 / 30
20 /
15 or 16
20 / 20
20 / 20
20 / 20
Recommended minimum
cable size, supply 1 / 2 2)
mm²
3x4,0 /
3x1,5
3x4,0 /
3x4,0
3x4,0 /
3x4,0
5x1,5 /
3x1,5
5x1,5 /
5x1,5
5x1,5 /
5x1,5
5x2,5 /
5x1,5
1) Sound power level in accordance to EN 12102 under conditions of the EN 14825. 2) Check local regulations. * EER and COP calculation is based in accordance to EN 14511. ** This product is designed to
comply with the European drinking water standard (EU) 2020/2184. The lifespan of the product is not guaranteed in the case of the use of groundwater, such as spring water or well water, the use of tap water
when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and warranty costs related to these cases are the customer’s responsibility.
Aquarea Designer - online tool.
With Panasonic’s online tool, projects
can be developed simply and easily.
The developed tool is optimised to help HVAC
professionals easily identify the most appropriate
Aquarea air to water heat pump for a particular
application.
Available on PRO Club.
AQUAREA DESIGNER
37