UK 20P BIG AQUAREA M 24 - Flipbook - Page 18
Additional functions
Combination table
CN‑CNT
Backup heater
Indoor unit
Control module
3ph 4 (2)
Remote controller
with Wi-Fi adapter
—
4 (1)
Outdoor unit
R290
Heating capacity
NATURAL
REFRIGERANT
Three phase
20,0 kW
25,0 kW
30,0 kW
WH-WXG20ME8
WH-WXG25ME8
WH-WXG30ME8
Field
supply
CZ‑NS7P
WH-CME8L
4
4
4
—
—
CZ-RTW2TAW1C
4
4
4
Outdoor unit
A++
A+++
ErP 55 °C
Scale from
A+++ to D
ErP 35 °C
Scale from
A+++ to D
WH-WXG20ME8
WH-WXG25ME8
WH-WXG30ME8
Indoor unit
Heating capacity / COP (A +7 °C, W 35 °C)
kW / COP
20,00 / 4,80
25,00 / 4,50
30,00 / 4,40
Dimension
Heating capacity / COP (A +7 °C, W 55 °C)
kW / COP
20,00 / 3,18
25,00 / 3,00
30,00 / 3,00
Net weight
kg
7
Heating capacity / COP (A +2 °C, W 35 °C)
kW / COP
20,00 / 3,39
25,00 / 2,80
30,00 / 2,50
Field supply electrical backup heater
kW
Up to 18 kW
Heating capacity / COP (A +2 °C, W 55 °C)
kW / COP
20,00 / 2,08
25,00 / 1,97
30,00 / 1,95
Heating capacity / COP (A ‑7 °C, W 35 °C)
kW / COP
20,00 / 2,48
25,00 / 2,36
30,00 / 2,33
Recommended fuse, supply 1)
A
≤9kW
9kW< ≤18 kW
20
40
Heating capacity / COP (A ‑7 °C, W 55 °C)
kW / COP
20,00 / 1,90
25,00 / 1,80
30,00 / 1,49
Cooling capacity / EER (A 35 °C, W 7 °C) at Comfort mode
kW / EER
20,00 / 3,02
25,00 / 2,86
26,00 / 2,68
Recommended minimum cable size, supply 1)
mm²
Cooling capacity / EER (A 35 °C, W 7 °C) at Efficiency mode (default)
kW / EER
15,00 / 3,61
15,00 / 3,61
15,00 / 3,61
≤12kW
12kW< ≤15 kW
15kW< ≤18 kW
5x2,5
5x4,0
5x6,0
Cooling capacity / EER (A 35 °C, W 18 °C) at Comfort mode
kW / EER
20,00 / 4,79
25,00 / 4,47
30,00 / 4,10
Connecting cable to the outdoor unit size
mm²
Heating average climate
(W 35 °C / W 55 °C)
Heating warm climate
(W 35 °C / W 55 °C)
Seasonal energy efficiency
SCOP (η,s %)
Energy class 1)
A+++ to D
Seasonal energy efficiency
SCOP (η,s %)
Energy class 1)
A+++ to D
Seasonal energy efficiency
SCOP (η,s %)
4,36 / 3,59 (171 / 141) 4,25 / 3,57 (167 / 140) 3,95 / 3,46 (155 / 135)
A++/A++
A++/A++
A++/A++
5,37 / 4,07 (212 / 160) 5,22 / 4,14 (206 / 163) 4,93 / 4,01 (194 / 158)
A+++ / A+++
A+++ / A+++
A+++ / A+++
3,07 / 2,57 (120 / 100) 3,16 / 2,71 (123 / 105) 3,20 / 2,71 (125 / 105)
Heating cold climate
(W 35 °C / W 55 °C)
Energy class 1)
A+++ to D
A / A+
A+ / A+
Sound power
Heat
dB(A)
56
59
61
HxWxD
mm
1 645 x 1 500 x 460
1 645 x 1 500 x 460
1 645 x 1 500 x 460
2)
Dimension
Net weight
A class pump
kg
Number of speeds
Input power (Min / Max)
Heating water flow (∆T=5 K. 35 °C)
Refrigerant (R290) / CO2 Eq. 3)
A+ / A+
240
240
240
Variable speed
Variable speed
Variable speed
W
230
230
230
L/min
57,3
71,6
86,0
3,0 / 0,009
kg / T
3,0 / 0,009
3,0 / 0,009
Operating range ‑ outdoor
ambient
Heat
°C
‑25 ~ +35
‑25 ~ +35
‑25 ~ +35
Cool
°C
+10 ~ +43
+10 ~ +43
+10 ~ +43
Water outlet
Heat / Cool
°C
20 ~ 75 4) / 5 ~ 20
20 ~ 75 4) / 5 ~ 20
20 ~ 75 4) / 5 ~ 20
Recommended RCD, supply
A
50
50
50
Recommended minimum cable size, supply 4)
mm²
5x10 ‑ 5x16
5x10 ‑ 5x16
5x10 ‑ 5x16
1) Scale from A+++ to D. 2) Sound power level in accordance to EN 12102 under conditions of the EN14825 (part load). 3) WH-WXG models are hermetically sealed. 4) Above
15 °C ambient temperature. 5) Check local regulations. * EER and COP calculation is based in accordance to EN 14511.
18
1) Check local regulations.
WH-CME8L
HxWxD
mm
450 x 450 x 116
2x0,75