UK BIGRAC GEN 26 LR - Flipbook - Page 31
RANGE
R32
CZ-RTC5B
COMMERCIAL
COMPATIBLE WITH ALL PANASONIC CONNECTIVITY SOLUTIONS. FOR
DETAILED INFORMATION GO TO THE CONTROL SYSTEMS SECTION
Optional:
CONEX wired
remote
controller,
white.
CZ-RTC6W/
BL/BLW2
CONEX wired
remote
controller,
black.
CZ-RTC6/BL/
BLW2
Infrared
remote
controller.
CZ-RWS3
Econavi
sensor.
CZ-CENSC1
Three phase
10,0 kW
Kit
KIT-100PK4Z8
Remote controller
CZ-RTC5B
Cooling capacity
Nominal (Min - Max)
kW
9,0 (3,0 - 9,7)
EER 1)
Nominal (Min - Max)
W/W
3,23 (3,13 - 5,36)
SEER 2)
6,2 A++
Pdesign
Input power
Nominal (Min - Max)
Annual energy consumption 3)
kW
9,0
kW
2,79 (0,56 - 3,10)
kWh/a
508
Heating capacity
Nominal (Min - Max)
kW
9,0 (3,0 - 10,5)
Heating capacity at -15 °C 4)
Max
kW
9,7
COP 1)
Nominal (Min - Max)
W/W
3,81 (3,56 - 5,36)
SCOP 2)
4,0 A+
Pdesign at -10 °C
Input power
Nominal (Min - Max)
Annual energy consumption 3)
kW
8,8
kW
2,36 (0,56 - 2,95)
kWh/a
3 080
Indoor unit
S-5010PK4E
Air flow
Hi / Med / Lo
m³/min
Moisture removal volume
22,5 / 20,0 / 17,5
L/h
4,0
Hi / Med / Lo
dB(A)
49 / 45 / 41
Sound power
Hi / Med / Lo
dB(A)
65 / 61 / 57
Dimension
HxWxD
mm
295 x 1 060 x 249
Sound pressure 5)
Net weight
kg
14
nanoe X Generator
Mark 3
Outdoor unit
U-100PZ3E8
Power supply
V
380 - 400 - 415
Cool
A
4,65 - 4,45 - 4,25
Heat
A
3,95 - 3,75 - 3,60
Air flow
Cool / Heat
m³/min
Sound pressure
Cool / Heat (Hi)
dB(A)
52 / 52
Sound power
Cool / Heat (Hi)
dB(A)
70 / 70
Dimension
HxWxD
mm
996 x 980 x 370
Current
Net weight
73,0 / 73,0
kg
Piping diameter
83
Liquid
Inch (mm)
3/8 (9,52)
Gas
Inch (mm)
5/8 (15,88)
Pipe length range
m
5 ~ 50
Elevation difference (in / out) 8)
m
15 / 30
Pre-charged pipe length
m
30
Additional gas amount
g/m
45
Refrigerant (R32) / CO₂ Eq.
kg / T
2,4 / 1,62
Cool Min ~ Max
°C
-10 ~ +43
Heat Min ~ Max
°C
-15 ~ +24
Operating range
1) EER and COP calculation is based in accordance to EN 14511. 2) For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the ηs,c / ηs,h values is
calculated based on EN 14825. 3) Factory setting. 4) The value is based on the interpolation. 5) The sound pressure of the units shows the value measured of the position 1 m in front of the main body and 1 m
below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006‑97 specification. 6) Connect the liquid socket tube (Ø6,35‑Ø9,52) to the liquid tubing side indoor unit. 7) Connect the gas
socket tube (Ø12,70‑Ø15,88) to the gas tubing side indoor unit. 8) Outdoor unit located lower / outdoor unit located higher. *Recommended fuse for the indoor 3 A. **Above values are in the case of nanoe™ X
OFF.
Accessories
Accessories
CZ-RTC6W
CONEX wired remote controller (non-wireless), white
CZ-RTC6WBL
CONEX wired remote controller with Bluetooth®, white
CZ-RTC6WBLW2
CONEX wired remote controller with Wi-Fi and Bluetooth®, white
CZ-RTC6
CONEX wired remote controller (non-wireless), black
CZ-RTC6BL
CONEX wired remote controller with Bluetooth®, black
CZ-CAPWFC2
Commercial Wi-Fi Adaptor
PAW-PACR4
Interface to run up to 4 indoor unit groups on backup and
alternative run
PAW-WTRAY
Tray for condenser water compatible with outdoor elevation
platform
CZ-RTC6BLW2
CONEX wired remote controller with Wi-Fi and Bluetooth®, black
PAW-GRDBSE20
Outdoor base ground support for noise and vibration absorption
CZ-RTC5B
Wired remote controller with Econavi function
PAW-GRDSTD40
Outdoor elevation platform 400 x 900 x 400 mm
CZ-RWS3
Infrared remote controller
CZ-CENSC1
Econavi energy saving sensor
R32
A++
A++
REFRIGERANT
7,2 SEER
4,6 SCOP
-10 °C
-15 °C
COOLING MODE
HEATING MODE
R22
R410A
DC FAN
R32
R22 / R410A
RENEWAL
OPTIONAL WI-FI
BMS
CONNECTIVITY
5
YEARS
COMPRESSOR
WARRANTY
SEER: For S‑5010PK4E + U‑50PZ3E5. SCOP: For S‑5010PK4E + U‑60PZ3E5A. INTERNET CONTROL: Optional.
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
31