RANGE
R32
CZ-RTC5B
Panel (sold separately):
White (RAL9003):
CZ-KPY4W
COMMERCIAL
COMPATIBLE WITH ALL PANASONIC CONNECTIVITY SOLUTIONS. FOR
DETAILED INFORMATION GO TO THE CONTROL SYSTEMS SECTION
Optional:
CONEX wired
remote
controller,
white.
CZ-RTC6W/
BL/BLW2
Graphite black
(RAL9011)
CZ-KPY4B
CONEX wired
remote
controller,
black.
CZ-RTC6/BL/
BLW2
Standard
Infrared
remote
controller.
CZ-RWS3 +
CZ-RWRY3W
Econavi
sensor.
CZ-CENSC1
Single phase
Kit
2,5 kW
3,6 kW
5,0 kW
6,0 kW
KIT-25PY3Z5
KIT-36PY3Z5
KIT-50PY3Z5
KIT-60PY3Z5
Remote controller
CZ-RTC5B
CZ-RTC5B
CZ-RTC5B
CZ-RTC5B
Cooling capacity
Nominal (Min - Max)
kW
2,5 (1,5 - 3,9)
3,6 (1,5 - 4,0)
5,0 (1,5 - 5,6)
6,0 (2,0 - 7,0)
EER 1)
Nominal (Min - Max)
W/W
4,46 (3,55 - 5,88)
3,96 (3,57 - 5,88)
3,50 (3,03 - 6,25)
3,39 (2,77 - 6,90)
6,5 A++
6,7 A++
7,3 A++
6,8 A++
kW
2,5
3,6
5,0
6,0
kW
0,56 (0,26 - 1,10)
0,91 (0,26 - 1,12)
1,43 (0,24 - 1,85)
1,77 (0,29 - 2,53)
SEER 2)
Pdesign
Input power
Nominal (Min - Max)
Annual energy consumption 3)
kWh/a
134
188
238
3,05
3,2 (1,5 - 4,6)
3,6 (1,5 - 4,6)
5,0 (1,5 - 6,4)
6,0 (1,8 - 7,0)
Heating capacity
Nominal (Min - Max)
kW
Heating capacity at -15 °C 4)
Max
kW
2,6
2,6
3,7
4,7
COP 1)
Nominal (Min - Max)
W/W
4,44 (3,41 - 6,52)
4,29 (3,38 - 6,52)
3,94 (2,91 - 7,50)
3,61 (2,86 - 7,60)
4,2 A+
SCOP 2)
Pdesign at -10 °C
Input power
Nominal (Min - Max)
Annual energy consumption 3)
4,6 A++
4,3 A+
4,4 A+
kW
2,8
2,8
4,0
4,6
kW
0,72 (0,23 - 1,35)
0,84 (0,23 - 1,36)
1,27 (0,20 - 2,20)
1,66 (0,24 - 2,45)
kWh/a
Indoor unit
Air flow
Hi / Med / Lo
Sound pressure 5)
Sound power
Dimension
Net weight
912
1 264
1 500
S-36PY3E
S-50PY3E
S-60PY3E
14,0 / 10,5 / 8,0
8,5 / 7,0 / 6,0
9,5 / 7,0 / 6,0
12,0 / 9,5 / 6,5
L/h
0,7
1,5
2,3
2,8
Hi / Med / Lo
dB(A)
31 / 28 / 25
34 / 30 / 25
39 / 34 / 27
43 / 37 / 31
Moisture removal volume
m³/min
850
S-25PY3E
Hi / Med / Lo
dB(A)
46 / 43 / 40
49 / 45 / 40
54 / 49 / 42
58 / 52 / 46
Indoor (H x W x D)
mm
243 x 575 x 575
243 x 575 x 575
243 x 575 x 575
243 x 575 x 575
Panel (H x W x D)
mm
30 x 625 x 625
30 x 625 x 625
30 x 625 x 625
30 x 625 x 625
Indoor / Panel
kg
15 / 2,8
15 / 2,8
15 / 2,8
15 / 2,8
Mark 2
Mark 2
Mark 2
Mark 2
nanoe X Generator
Outdoor unit
U-25PZ3E5
U-36PZ3E5
U-50PZ3E5
U-60PZ3E5A
V
220 - 230 - 240
220 - 230 - 240
220 - 230 - 240
220 - 230 - 240
Cool
A
2,65 - 2,55 - 2,45
4,20 - 4,05 - 3,85
6,65 - 6,35 - 6,10
8,20 - 7,85 - 7,55
Heat
A
3,40 - 3,25 - 3,10
3,95 - 3,75 - 3,60
5,695 - 5,70 - 5,45
7,70 - 7,35 - 7,05
42,6 / 41,5
Power supply
Current
Air flow
Cool / Heat
m³/min
33,6 / 34,0
32,6 / 34,0
32,7 / 31,9
Sound pressure
Cool / Heat (Hi)
dB(A)
46 / 47
46 / 47
46 / 48
47 / 48
Sound power
Cool / Heat (Hi)
dB(A)
64 / 66
64 / 66
64 / 64
64 / 65
Dimension
HxWxD
mm
619 x 824 x 299
619 x 824 x 299
619 x 824 x 299
695 x 875 x 320
kg
32
32
35
46
Inch (mm)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35) 5)
Inch (mm)
1/2 (12,70) 6)
Net weight
Liquid
Piping diameter
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
Pipe length range
Gas
m
3 ~ 15
3 ~ 15
3 ~ 20
3 ~ 40
Elevation difference (in / out) 8)
m
15 / 15
15 / 15
15 / 15
15 / 30
Pre-charged pipe length
m
7,5
7,5
7,5
30
Additional gas amount
g/m
10
10
15
15
Refrigerant (R32) / CO₂ Eq.
Operating range
kg / T
0,87 / 0,59
0,87 / 0,59
1,14 / 0,77
1,15 / 0,78
Cool Min ~ Max
°C
-10 ~ +43
-10 ~ +43
-10 ~ +43
-10 ~ +43
Heat Min ~ Max
°C
-15 ~ +24
-15 ~ +24
-15 ~ +24
-15 ~ +24
1) EER and COP calculation is based in accordance to EN 14511. 2) For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the ηs,c / ηs,h values is
calculated based on EN 14825. 3) Factory setting. 4) The value is based on the interpolation. 5) The sound pressure of the units shows the value measured of the position 1,5 m below the unit. The sound
pressure is measured in accordance with Eurovent 6/C/006‑97 specification. 6) Connect the liquid socket tube (Ø6,35‑Ø9,52) to the liquid tubing side indoor unit. 7) Connect the gas socket tube (Ø12,70‑Ø15,88)
to the gas tubing side indoor unit. 8) Outdoor unit located lower / outdoor unit located higher. *Recommended fuse for the indoor 3 A. **Above values are in the case of nanoe™ X OFF.
Accessories
Accessories
CZ-RTC6W
CONEX wired remote controller (non-wireless), white
CZ-KPY4W
CZ-RTC6WBL
CONEX wired remote controller with Bluetooth®, white
CZ-KPY4B*
NEW! Panel for 4 way 60x60 cassette, graphite black (RAL9011)
CZ-RTC6WBLW2
CONEX wired remote controller with Wi-Fi and Bluetooth®, white
CZ-RTC6
CONEX wired remote controller (non-wireless), black
PAW-PACR4
Interface to run up to 4 indoor unit groups on backup and
alternative run
CZ-RTC6BL
CONEX wired remote controller with Bluetooth®, black
CZ-RTC6BLW2
CONEX wired remote controller with Wi-Fi and Bluetooth®, black
PAW-WTRAY
Tray for condenser water compatible with outdoor elevation
platform
CZ-RTC5B
Wired remote controller with Econavi function
PAW-GRDBSE20
Outdoor base ground support for noise and vibration absorption
CZ-RWS3 +
CZ-RWRY3W
Infrared remote controller and receiver
PAW-GRDSTD40
Outdoor elevation platform 400 x 900 x 400 mm
CZ-CENSC1
Econavi energy saving sensor
CZ-CAPWFC2
Commercial Wi-Fi Adaptor
R32
A++
A++
REFRIGERANT
7,3 SEER
4,6 SCOP
28%
NEW! Panel for 4 way 60x60 cassette, white (RAL9003)
*Available in Autumn 2026.
-10 °C
-15 °C
COOLING MODE
HEATING MODE
R22
R410A
DC FAN
R32
R22 / R410A
RENEWAL
OPTIONAL WI-FI
BMS
CONNECTIVITY
5
YEARS
COMPRESSOR
WARRANTY
SEER: For S‑50PY3E + U‑50PZ3E5. SCOP: For S‑25PY3E + U‑25PZ3E5. ECONAVI and INTERNET CONTROL: Optional.
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
33