UK BIGRAC GEN 26 LR - Flipbook - Page 39
RANGE
R32
CZ-RTC5B
COMMERCIAL
COMPATIBLE WITH ALL PANASONIC CONNECTIVITY SOLUTIONS. FOR
DETAILED INFORMATION GO TO THE CONTROL SYSTEMS SECTION
Optional:
CONEX wired
remote
controller,
white.
CZ-RTC6W/
BL/BLW2
CONEX wired
remote
controller,
black.
CZ-RTC6/BL/
BLW2
Infrared remote
controller.
CZ-RWS3 +
CZ-RWRT3
Econavi
sensor.
CZ-CENSC1
Three phase
Kit
Remote controller
7,1 kW
10,0 kW
12,5 kW
14,0 kW
KIT-71PT3ZH48
KIT-100PT3ZH48
KIT-125PT3ZH48
KIT-140PT3ZH48
CZ-RTC5B
CZ-RTC5B
CZ-RTC5B
CZ-RTC5B
Cooling capacity
Nominal (Min - Max)
kW
6,8 (2,2 - 9,0)
9,5 (3,1 - 12,5)
12,1 (3,2 - 14,0)
13,4 (3,3 - 16,0)
EER 1)
Nominal (Min - Max)
W/W
3,91 (2,69 - 5,79)
4,06 (3,29 - 5,34)
3,46 (3,01 - 5,33)
3,21 (2,67 - 5,32)
7,2 A++
7,2 A++
277,3%
262,4%
kW
6,8
9,5
12,1
13,4
kW
1,74 (0,38 - 3,35)
2,34 (0,58 - 3,80)
3,50 (0,60 - 4,65)
4,17 (0,66 - 6,00)
SEER / ηs,c 2)
Pdesign
Input power
Nominal (Min - Max)
Annual energy consumption 3)
kWh/a
331
462
—
—
8,0 (2,0 - 9,0)
11,2 (3,1 - 14,0)
14,0 (3,2 - 16,0)
16,0 (3,3 - 18,0)
Heating capacity
Nominal (Min - Max)
kW
Heating capacity at -15 °C 4)
Max
kW
7,5
11,9
13,4
15,0
COP 1)
Nominal (Min - Max)
W/W
3,96 (3,16 - 5,56)
4,00 (3,54 - 5,54)
3,78 (3,20 - 5,52)
3,38 (3,10 - 5,50)
169,3%
SCOP / ηs,h 2)
Pdesign at -10 °C
Input power
Nominal (Min - Max)
Annual energy consumption 3)
4,7 A++
4,5 A+
175,6%
kW
4,7
7,8
9,5
10,2
kW
2,02 (0,36 - 2,85)
2,80 (0,56 - 3,95)
3,70 (0,58 - 5,00)
4,74 (0,60 - 5,80)
kWh/a
Indoor unit
Air flow
Hi / Med / Lo
m³/min
1 400
2 427
—
—
S-6071PT3E
S-1014PT3E
S-1014PT3E
S-1014PT3E
35,0 / 29,0 / 25,0
21,0 / 18,0 / 15,5
30,0 / 25,0 / 23,0
34,0 / 28,0 / 24,0
L/h
2,7
3,6
5,4
6,4
Hi / Med / Lo
dB(A)
39 / 35 / 30
42 / 37 / 34
46 / 40 / 35
47 / 41 / 36
Sound power
Hi / Med / Lo
dB(A)
57 / 53 / 48
60 / 55 / 52
64 / 58 / 53
65 / 59 / 54
Dimension
HxWxD
mm
235 x 1 275 x 690
235 x 1 590 x 690
235 x 1 590 x 690
235 x 1 590 x 690
Moisture removal volume
Sound pressure 5)
Net weight
kg
nanoe X Generator
Outdoor unit
Power supply
Cool
Current
34
40
40
40
Mark 2
Mark 2
Mark 2
Mark 2
U-140PZH4E8
U-71PZH4E8
U-100PZH4E8
U-125PZH4E8
V
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
A
2,95 - 2,80 - 2,70
3,60 - 3,40 - 3,25
5,45 - 5,15 - 5,00
6,15 - 5,85 - 5,65
Heat
A
3,15 - 3,00 - 2,90
3,75 - 3,55 - 3,40
5,10 - 4,80 - 4,65
6,20 - 5,90 - 5,65
Air flow
Cool / Heat
m³/min
62,0 / 66,0
76,0 / 70,0
86,0 / 78,0
89,0 / 83,0
Sound pressure
Cool / Heat (Hi)
dB(A)
48 / 50
52 / 52
55 / 55
56 / 56
Sound power
Cool / Heat (Hi)
dB(A)
65 / 67
69 / 69
73 / 73
74 / 74
Dimension
HxWxD
mm
996 x 980 x 370
996 x 980 x 370
996 x 980 x 370
996 x 980 x 370
kg
66
82
84
84
Inch (mm)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
Inch (mm)
Net weight
Liquid
Piping diameter
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
Pipe length range
Gas
m
5 ~ 60
5 ~ 100
5 ~ 100
5 ~ 100
Elevation difference (in / out) 8)
m
15 / 30
15 / 30
15 / 30
15 / 30
Pre-charged pipe length
m
30
30
30
30
Additional gas amount
g/m
30
40
40
40
Refrigerant (R32) / CO₂ Eq.
kg / T
1,95 / 1,32
2,70 / 1,82
3,00 / 2,03
3,00 / 2,03
Cool Min ~ Max
°C
-15 ~ +52
-20 9) ~ +52
-20 9) ~ +52
-20 9) ~ +52
Heat Min ~ Max
°C
-20 ~ +24
-20 ~ +24
-20 ~ +24
-20 ~ +24
Operating range
1) EER and COP calculation is based in accordance to EN 14511. 2) For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the ηs,c / ηs,h values is
calculated based on EN 14825. 3) Factory setting. 4) The value is based on the interpolation. 5) The sound pressure of the units shows the value measured of the position 1 m in front of the main body and 1 m
below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006‑97 specification. 6) Connect the liquid socket tube (Ø6,35‑Ø9,52) to the liquid tubing side indoor unit. 7) Connect the gas
socket tube (Ø12,70‑Ø15,88) to the gas tubing side indoor unit. 8) Outdoor unit located lower / outdoor unit located higher. 9) Pipe length up to 30 m. *Recommended fuse for the indoor 3 A. **Above values are
in the case of nanoe™ X OFF.
Accessories
Accessories
CZ-RTC6W
CONEX wired remote controller (non-wireless), white
CZ-RTC6WBL
CONEX wired remote controller with Bluetooth®, white
CZ-RTC6WBLW2
CONEX wired remote controller with Wi-Fi and Bluetooth®, white
CZ-RTC6
CONEX wired remote controller (non-wireless), black
CZ-RTC6BL
CONEX wired remote controller with Bluetooth®, black
CZ-CAPWFC2
Commercial Wi-Fi Adaptor
PAW-PACR4
Interface to run up to 4 indoor unit groups on backup and
alternative run
PAW-WTRAY
Tray for condenser water compatible with outdoor elevation
platform
CZ-RTC6BLW2
CONEX wired remote controller with Wi-Fi and Bluetooth®, black
PAW-GRDBSE20
Outdoor base ground support for noise and vibration absorption
CZ-RTC5B
Wired remote controller with Econavi function
PAW-GRDSTD40
Outdoor elevation platform 400 x 900 x 400 mm
CZ-RWS3 +
CZ-RWRT3
Infrared remote controller and receiver
CZ-CENSC1
Econavi energy saving sensor
R32
A++
A++
REFRIGERANT
7,7 SEER
4,9 SCOP
-15 °C
-20 °C
COOLING MODE
HEATING MODE
R22
R410A
R32
R22 / R410A
RENEWAL
OPTIONAL WI-FI
BMS
CONNECTIVITY
5
YEARS
COMPRESSOR
WARRANTY
SEER and SCOP: For S‑3650PT3E + U‑36PZH3E5. INTERNET CONTROL: Optional.
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
39