UK BIGRAC GEN 26 LR - Flipbook - Page 46
GENERAL
R32
NEW
NEW! PACi NX Series Standard multi zone duct unit ·
R32
Energy efficient ducted unit with individual zone
temperature control.
Simple and efficient zone control installation.
Single phase
Kit
Remote controller
Cooling capacity
10,0 kW
10,0 kW
12,5 kW
14,0 kW
KIT-71PQ41Z5
KIT-100PQ41Z5
KIT-100PQ51Z5
KIT-125PQ51Z5
KIT-140PQ51Z5
PCZ-EEB749
PCZ-EEB749
PCZ-EEB749
PCZ-EEB749
PCZ-EEB749
Nom (Min - Max)
kW
7,0 (2,7-7,9)
9,0 (3,0 - 11,0)
9,8 (3,1 - 11,5)
12,0 ( 3,3 - 13,7)
13,2 (3, 4 - 14,8)
6,6 A++
6,2 A++
6,6 A++
254,5%
251,8%
Nom (Min - Max)
kW
7,1 (2,2 - 8,2)
9,1 (3,0 - 13,2)
9,7 (3,0 - 11,5)
12,1 (3,3 - 15,2)
13,3 (3,5 - 15,9)
SEER / ηs,c 1)
Heating capacity
7,1 kW
SCOP / ηs,h 1)
4,3 A+
4,3 A+
4,4 A+
143,2%
141,4%
Indoor unit
S-7110PQ41E
S-7110PQ41E
S-1014PQ51E
S-1014PQ51E
S-1014PQ51E
Number of fans
External static pressure 2)
Nom (Min - Max)
4
4
5
5
5
Pa
30 (10 - 120)
30 (10 - 120)
30 (10 - 130)
30 (10 - 130)
30 (10 - 130)
Air flow
Hi / Med / Lo
m³/h
1 800 / 1 520 / 1 120
1 800 / 1 520 / 1 120
2 250 / 1 800 / 1 450
2 250 / 1 800 / 1 450
2 250 / 1 800 / 1 450
Dimension
HxWxD
mm
266 x 1 164 x 701
266 x 1 164 x 701
266 x 1 455 x 701
266 x 1 455 x 701
266 x 1 455 x 701
kg
47
47
57
57
57
U-71PZ3E5A
U-100PZ3E5
U-100PZ3E5
U-125PZ3E5
U-140PZ3E5
Net weight
Outdoor unit
Power supply
Current
V
220 - 230 - 240
220 - 230 - 240
220 - 230 - 240
220 - 230 - 240
220 - 230 - 240
Cool
A
9,95-9,50-9,10
13,30 - 12,70 - 12,20
13,30 - 12,70 - 12,20
17,20 - 16,40 - 15,80
20,50 - 19,60 - 18,8
Heat
A
7,90-7,55-7,25
11,60 - 11,10 - 10,60
11,60 - 11,10 - 10,60
16,40 - 15,70 - 15,00
17,20 - 16,40 - 15,80
Air flow
Cool / Heat
m³/min
44,7 / 45,9
73,0 / 73,0
73,0 / 73,0
82,0 / 80,0
84,0 / 82,0
Sound pressure
Cool / Heat (Hi)
dB(A)
48 / 49
52 / 52
52 / 52
55 / 55
56 / 56
Sound power
Cool / Heat (Hi)
dB(A)
66 / 68
70 / 70
70 / 70
73 / 73
74 / 74
Dimension
HxWxD
mm
695 x 875 x 320
996 x 980 x 370
996 x 980 x 370
996 x 980 x 370
996 x 980 x 370
50
83
83
87
87
Liquid
Inch (mm)
1/4 (Ø6,35) 7)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
Gas
Inch (mm)
5/8 (15,88)
Net weight
Piping diameter
kg
5/8 (Ø15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
Pipe length range
m
3 - 40
5 ~ 50
5 ~ 50
5 ~ 50
5 ~ 50
Elevation difference (in / out) 3?
m
20 / 30
15 / 30
15 / 30
15 / 30
15 / 30
Pre-charged pipe length
m
30
30
30
30
30
Additional gas amount
g/m
17
45
45
45
45
Refrigerant (R32) / CO₂ Eq.
kg / T
1,32 / 0,89
2,40 / 1,62
2,40 / 1,62
2,80 / 1,89
2,80 / 1,89
Cool Min ~ Max
°C
-10 ~ +43
-10 ~ +43
-10 ~ +43
-10 ~ +43
-10 ~ +43
Heat Min ~ Max
°C
-15 ~ +24
-15 ~ +24
-15 ~ +24
-15 ~ +24
-15 ~ +24
Operating range
Technical focus
· Individual zone temperature control with dedicated fans
and motors for each outlet integrated
· Multi-zone management for 4 or 5 zones
· Two installation configurations: horizontal or vertical
· Simplified duct installation with reduced system
complexity
· No bypass duct required thanks to intelligent direct
control, ensuring optimal comfort and efficiency
· Compatible with PACi NX Standard outdoor units
· Drain pump is optional
· Individual zone control via an intuitive wall controller
(PCZ-EEB749)
· Smart Wi-Fi control through the Aquarea Home App
· Standard Panasonic controller 1) used for setup,
commissioning, service, and maintenance
1) Controller (CZ‑RTC6) must remain connected.
Multi zone management – Energy saving solution
Independent temperature control per each zone can be controlled by a wall control.
24 °C
*
20 °C
*
22 °C
*Wall‑mounted controller (PCZ‑EEB749).
46
Outdoor
*