Big PACi NX Elite high static pressure hide‑away
20,0‑25,0 kW · R32
nanoe™ X (Generator Mark 3).
Maximum piping length 100 m.
High external static pressure, maximum 200 Pa setting.
nanoe™ X as a standard.
Three phase
Kit
20,0 kW
25,0 kW
KIT-200PE4ZH8
KIT-250PE4ZH8
Remote controller
CZ-RTC5B
CZ-RTC5B
Cooling capacity
Nominal (Min - Max)
kW
19,0 (5,7 - 20,0)
22,0 (6,1 - 25,6)
EER 1)
ηs,c 2)
Nominal (Min - Max)
W/W
3,20 (2,78 - 4,60)
2,74 (2,49 - 4,88)
237,8%
213,0%
Pdesign
kW
19,0
22,0
Input power
Nominal (Min - Max)
kW
5,93 (1,24 - 7,20)
8,04 (1,25 - 10,30)
Heating capacity
Nominal (Min - Max)
kW
22,4 (5,0 - 24,5)
24,0 (5,5 - 27,6)
Heating capacity at -15 °C 3)
Max
kW
16,8
19,0
COP 1)
ηs,h 2)
Nominal (Min - Max)
W/W
3,55 (3,27 - 4,76)
3,55 (3,07 - 4,78)
146,0%
145,0%
Pdesign at -10 °C
kW
16,0
17,2
kW
6,31 (1,05 - 7,50)
6,76 (1,15 - 9,00)
S-200PE4E
S-250PE4E
External static pressure at shipment (adjustable)
Pa
75 4) (120 / 180)
75 4) (130 / 200)
Air flow
Hi / Med / Lo
m³/min
72 / 63 / 53
84 / 72 / 59
Sound pressure 5)
Hi / Med / Lo
dB(A)
46 / 44 / 41
47 / 45 / 42
Dimension / Net weight
HxWxD
mm / kg
486 x 1456 x 916 / 83
486 x 1456 x 916 / 87
Input power
Nominal (Min - Max)
Indoor unit
nanoe X Generator
Mark 3
Mark 3
U-200PZH4E8
U-250PZH4E8
380 - 400 - 415 / 3 / 50
380 - 400 - 415 / 3 / 50
Outdoor unit
Power supply
V / ph / Hz
Recommended fuse
A
Air flow
30
30
Cool / Heat
m³/min
116 / 136
116 / 148
Sound pressure
Cool / Heat (Hi)
dB(A)
57 / 61
57 / 63
Sound power
Cool / Heat (Hi)
dB(A)
76 / 80
76 / 82
Dimension 6) / Net weight
HxWxD
mm / kg
996 x 1 140 x 460 / 109
996 x 1 140 x 460 / 109
Piping diameter
Liquid / Gas
Inch (mm)
1/2 (12,7) / 7/8 (22,22)
1/2 (12,7) / 7/8 (22,22)
Pipe length range / Elevation difference (in / out)
m/m
5 ~ 100 / 30
5 ~ 100 / 30
Pre-charged pipe length / Additional gas amount
m / g/m
30 / 80
30 / 80
Refrigerant (R32) / CO₂ Eq.
kg / T
4,8 / 3,24
4,8 / 3,24
Cool Min ~ Max
°C
-15 ~ +52
-15 ~ +52
Heat Min ~ Max
°C
-20 ~ +35
-20 ~ +35
Operating range
1) EER and COP calculation is based in accordance to EN 14511. 2) Energy Label Scale from A+++ to D. For models above 12 kW, the ηs,c / ηs,h values is calculated based on EN 14825. 3) The value is based on the
interpolation. 4) Factory setting. 5) The sound pressure of the units shows the value measured of the position 1,5 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006‑97
specification. 6) Add 100 mm for indoor unit or 70 mm for outdoor unit for piping port.
Accessories
Accessories
CZ-RTC6W
CONEX wired remote controller (non-wireless), white
CZ-RTC6WBL
CONEX wired remote controller with Bluetooth®, white
CZ-RWS3 +
CZ-RWRC3
Infrared remote controller and receiver
CZ-RTC6WBLW2
CONEX wired remote controller with Wi-Fi and Bluetooth®, white
CZ-CAPWFC2
Commercial Wi-Fi Adaptor
CZ-RTC6
CONEX wired remote controller (non-wireless), black
CZ-RTC6BL
CONEX wired remote controller with Bluetooth®, black
PAW-PACR4
Interface to run up to 4 indoor unit groups on backup and
alternative run
CZ-RTC6BLW2
CONEX wired remote controller with Wi-Fi and Bluetooth®, black
PAW-GRDSTD1100 Outdoor ground stand
CZ-RTC5B
Wired remote controller with Econavi function
PAW-GRDBSE20
Outdoor base ground support for noise and vibration absorption
CZ-CENSC1
Econavi energy saving sensor
Demand response compliant as a standard function
Several setting levels are available:
· Level-1, 2, 3: 75 / 50 / 0%
· Level-1, 2 can be set in 40 - 100% (40, 45, 50…95, 100: each 5%)
It allows for forced stop which can be used for fire-alarm connection on LV3.
1
1
2
2
3
3
4
4
5
5
6
6
OPT
COM
LV1
LV2
LV3
*PAW‑OPT‑NX is required.
Indoor unit control PCB
COMPATIBLE WITH ALL PANASONIC CONNECTIVITY SOLUTIONS. FOR
DETAILED INFORMATION GO TO THE CONTROL SYSTEMS SECTION
R32
REFRIGERANT
INTERNET CONTROL: Optional.
48
-15 °C
-20 °C
COOLING MODE
HEATING MODE
R22
R410A
HIGH EFFICIENCY
COMPRESSOR
BLUEFIN
LARGE FAN
R32
R22 / R410A
RENEWAL
OPTIONAL WI-FI
BMS
CONNECTIVITY
5
YEARS
COMPRESSOR
WARRANTY
Demand controller