UK BIGRAC GEN 26 LR - Flipbook - Page 65
RANGE
R32
NEW
COMMERCIAL
NEW! P Series ‑ Perimetral · R32
First complete package solution for critical environment
up to 21 kW.
· Close-control solution for precise cooling
· Strict control of temperature and humidity
· Version with humidifier and modulating heater
Sizes
71
111
121
141
211
211
Indoor unit
Up flow
T-OPZ
0071AA-E004
0111AA-E004
0121AA-E004
0141AA-E004
0211AA-E004
0211AA-E005
Indoor unit
Down flow
0211AA-E005
T-UPZ
0071AA-E004
0111AA-E004
0121AA-E004
0141AA-E004
0211AA-E004
Cooling capacity 1)
kW
7,44
9,92
12,50
14,71
20,47
20,47
Sensible cooling capacity 1)
kW
6,89
8,41
10,67
12,60
20,47
20,47
3,52
3,13
2,79
2,61
2,38
2,38
m³/h
2.200
3.500
3.500
3.500
7.000
7.000
EER 2)
Air flow
Sound pressure
dB(A)
51
59
59
59
56
56
Height
mm
1 990
1 990
1 990
1 990
1 990
1 990
Width
mm
750
750
750
750
860
860
Depth
mm
600
600
600
600
880
880
kg
150
200
205
205
225
225
Fan type
EC
EC
EC
EC
EC
EC
Quantity
1
1
1
1
1
1
230
400
400
400
400
400
Three phase
Dimension
Overall weight
Fan
Voltage
Power supply
V
Phase
Single phase
Three phase
Three phase
Three phase
Three phase
Hz
50
50
50
50
50
50
kW
0,50
1,10
1,10
1,10
1,50
1,50
Maximum volume airflow
m³/h
2 600
3 500
3 500
3 500
8 000
8 000
Maximum pressure
Pa
700
570
570
570
900
900
Frequency
Maximum power consumption
Humidifier
Humidifier
kg/h
Quantity
3,0
3,0
3,0
3,0
3,0
8,0
1,0
1,0
1,0
1,0
1,0
1,0
5,4
Cylinder volume
l
3,3
3,3
3,3
3,3
3,3
Instantaneous supply flow rate
l/min
0,6
0,6
0,6
0,6
0,6
0,6
Instantaneous discharge flow rate
l/min
10,0
10,0
10,0
10,0
10,0
10,0
Heater
Maximum power
Voltage
Power supply
kW
6
6
6
6
9
9
V
400
400
400
400
400
400
Three phase
Phase
Frequency
Maximum current
PACi NX outdoor combination
Three phase
Three phase
Three phase
Three phase
Three phase
Hz
50
50
50
50
50
50
A
11,3
11,3
11,3
11,3
17,0
17,0
Single phase
U-71PZH4E5
U-100PZH4E5
U-125PZH4E5
U-140PZH4E5
—
—
Three phase
U-71PZH4E8
U-100PZH4E8
U-125PZH4E8
U-140PZH4E8
U-250PZH4E8
U-250PZH4E8
1) Performance refers to: indoor ambient temperature 27 °C DB / 19 °C WB, outdoor ambient temperature 35 °C; R32 refrigerant; The declared performance does not consider the heat generated by the fans,
which must be added to the thermal load of the system. 2) EER (energy efficiency ratio) = total cooling capacity / input power of the PACi NX condenser + input power of the fans and CRAC indoor unit. 3) Outdoor
unit located lower / outdoor unit located higher. 4) Pipe length up to 30 m.
PACi NX outdoor combination
Outdoor unit single phase
U-71PZH4E5
U-100PZH4E5
U-125PZH4E5
U-140PZH4E5
—
Outdoor unit three phase
U-71PZH4E8
U-100PZH4E8
U-125PZH4E8
U-140PZH4E8
U-250PZH4E8
Single phase
V
220 - 230 - 240
220 - 230 - 240
220 - 230 - 240
220 - 230 - 240
—
Three phase
V
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
Sound pressure
Cool / Heat (Hi)
dB(A)
48 / 50
52 / 52
55 / 55
54 / 54
57 / 63
Sound power
Cool / Heat (Hi)
dB(A)
65 / 67
70 / 70
73 / 73
74 / 74
76 / 82
Dimension
HxWxD
mm
996 x 980 x 370
996 x 980 x 370
996 x 980 x 370
996 x 980 x 370
996 x 1140 x 460
Net weight
1ph / 3ph
kg
66 / 66
84 / 82
86 / 84
86 / 84
— / 109
Liquid
Inch (mm)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
1/2 (12,70)
Power supply
Piping diameter
Gas
Inch (mm)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
7/8 (22,22)
Pipe length range
Min ~ Max
m
5 ~ 60
5 ~ 100
5 ~ 100
5 ~ 100
5 ~ 100
Elevation difference (in / out)
Max
m
15 / 30 3)
15 / 30 3)
15 / 30 3)
15 / 30 3)
30
Pre-charged pipe length
m
30
30
30
30
30
Additional gas amount
g/m
45
45
45
45
80
Refrigerant (R32) / CO₂ Eq.
kg / T
1,95 / 1,32
2,70 / 1,82
3,00 / 2,03
3,00 / 2,03
4,80 / 3,24
Operating range
Cool Min ~ Max
°C
-15 ~ +52
-20 4) ~ +52
-20 4) ~ +52
-20 4) ~ +52
-15 ~ +52
Heat Min ~ Max
°C
-20 ~ +24
-20 ~ +24
-20 ~ +24
-20 ~ +24
-20 ~ +35
kW
7,1
10,0
12,5
14,0
25,0
A
25
35
40
40
Electrical information (power supply to outdoor)
Recommended fuse
Connection in. / out.
Single phase
Three phase
A
16
16
16
16
Single phase
mm²
4x2,5
4x2,5
4x2,5
4x2,5
Three phase
mm²
4x2,5
4x2,5
4x2,5
4x2,5
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
30
—
65