GENERAL
P Series - Perimetral
Perimetral and compact solution.
Cooling capacity - chilled water: 9,9 to 160,0 kW.
Cooling capacity - direct expansion: 8,2 to 95,0 kW.
The range at a glance
Although optimised for data centres, the technical characteristics
of the P Series units make them ideal for various types of special
applications, including: metrology labs, TV production studios,
musical instrument recording and storage rooms, museums and
archives, control rooms in power stations and railway junctions.
Moreover, they are ideal for use in many industrial sectors:
optics, electronics, electromedical devices, electrical or
electronic equipment production, musical instrument production,
etc.
Advantages
· Versions with upward and downward air delivery
· Strict control of room temperature and humidity
· Very high EER (energy efficiency ratio) and low operating costs
· High usage flexibility and wide range of accessories
· Version with low GWP R513A refrigerant available
Free cooling and two sources models available.
Technical performance
UPA/OPA - direct expansion air conditioners with air cooled or water cooled condensers
Sizes
Cooling capacity 1)
kW
Sensible cooling capacity 1)
kW
EER 2)
71
111
141
211
251
301
321
322
361
461
422
512
662
852
932
8,2
10,7
14,7
21,0
27,4
32,3
35,2
33,8
38,1
48,1
43,7
57,8
67,3
84,4
94,9
7,9
10,7
12,9
21,0
25,7
32,3
35,2
33,8
38,1
46,8
43,7
53,6
66,2
73,7
86,3
3,83
3
3,40
3,30
3,14
3,21
3,13
3,34
3,57
3,63
3,47
3,34
3,26
3,27
3,64
21 000
Air flow
m³/h
2 200
3200
3 200
7 000
7 000
12 000
12 000
12 000
14 000
14 000
14 000
14 000
18 000
18 000
Sound pressure
dB(A)
51
59
59
56
57
67
67
67
58
58
58
59
61
61
61
Height
mm
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
Width
mm
750
750
750
860
860
1 410
1 410
1 410
1 750
1 750
1 750
1 750
2 300
2 300
2 640
Depth
mm
600
600
600
880
880
880
880
880
880
880
880
880
880
880
880
kg
170
220
225
280
305
360
385
430
460
470
535
540
685
705
745
Air cooled free cooling
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
Water cooled free cooling
○
○
○
○
○
○
●
○
○
●
○
○
●
●
○
Two sources
○
○
○
●
○
○
●
○
○
●
○
●
●
●
●
Dimension
Overall weight
UPN/OPN - direct expansion air conditioners with air cooled or water cooled condensers · R513A
Sizes
Cooling capacity 1)
kW
Sensible cooling capacity 1)
kW
EER 2)
Air flow
m³/h
Sound pressure
Dimension
71
111
141
181
211
251
301
302
312
322
422
512
612
7,82
11,52
13,58
19,78
22,24
26,92
33,82
30,92
40,12
46,58
46,92
55,65
59,37
59,37
7,82
11,52
12,42
19,78
22,24
25,72
33,82
30,92
40,12
44,05
46,92
55,62
3,49
3,32
3,41
3,41
3,29
3,30
3,61
3,32
3,36
3,36
3,43
3,46
3,47
2 200
3 200
3 200
7 000
7 000
7 000
12 000
12 000
12 000
12 000
14 000
14 000
18 000
Tentative data
dB(A)
51
59
59
58
58
58
67
67
67
67
59
59
61
Height
mm
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
Width
mm
750
750
750
860
860
860
1 410
1 410
1 410
1 410
1 750
1 750
2 300
Depth
mm
600
600
600
880
880
880
880
880
880
880
880
880
880
kg
225
235
235
280
295
305
360
380
365
385
535
540
685
Overall weight
UPU/OPU - chilled water air conditioners
Sizes
Cooling capacity 1)
kW
Sensible cooling capacity 1)
kW
EER 2)
10
20
30
50
60
70
80
110
160
220
9,9
17,2
30,0
41,0
52,8
63,1
65,4
80,0
110,0
160,0
9,3
14,9
27,8
36,2
47,4
54,2
61,8
73,0
99,7
146,0
38,26
29,13
30,00
24,54
22,75
24,17
24,79
24,17
29,33
24,17
36 000
Air flow
m³/h
2 200
3 200
7 000
8 000
12 000
12 000
16 000
18 000
24.000
Sound pressure
dB(A)
51
59
56
60
67
68
61
62
62
65
Height
mm
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
Width
mm
750
750
860
860
1 410
1 410
1 750
1 750
2 640
3 495
Depth
mm
600
600
880
880
880
880
880
880
880
880
kg
125
150
245
250
270
280
375
410
690
810
○
○
○
●
○
●
○
●
●
○
Dimension
Overall weight
Two sources
1) Performance refers to: intake air 24 °C-45%Rh; R410A refrigerant; condensing temperature 45 °C; water temperature 7/12 °C; external static pressure 30 Pa. The declared performance does not consider the
heat generated by the fans, which must be added to the thermal load of the system. 2) EER (energy efficiency ratio)= total cooling capacity / input power of compressors + input power of fans (excluding air
cooled condensers).
10