UK HYDRONICS GEN 26 - Flipbook - Page 113
RANGE
FAN COIL UNITS
Technical performance
Flex Air fan coil – Cassette AC fan
Fan speed 1)
P-FQ20
P-FQ30
P-FQ40
P-FQ50
P-FQ60
P-FQ70
Min / Med / Max
Min / Med / Max
Min / Med / Max
Min / Med / Max
Min / Med / Max
Min / Med / Max
2-pipes
Total cooling capacity 2)
kW
1,54 / 1,76 / 2,36
1,87 / 2,87 / 3,99
2,78 / 3,49 / 4,69
3,35 / 4,43 / 6,07
3,69 / 5,46 / 7,18
4,04 / 6,48 / 8,61
Sensible capacity 2)
kW
1,29 / 1,48 / 1,98
1,41 / 2,17 / 3,04
2,08 / 2,67 / 3,62
2,52 / 3,35 / 4,47
2,67 / 4,06 / 5,42
2,97 / 4,85 / 6,34
695 / 1 111 / 1 476
Water flow 2)
l/h
265 / 303 / 404
323 / 493 / 683
478 / 597 / 801
576 / 762 / 1 042
636 / 937 / 1 233
Water pressure drop 2)
kPa
4,0 / 5,0 / 10,0
3,0 / 7,0 / 14,0
6,0 / 10,0 / 18,0
7,0 / 12,0 / 22,0
3,0 / 6,0 / 11,0
5,0 / 12,0 / 20,0
Heating capacity 3)
kW
1,92 / 2,17 / 2,74
1,94 / 3,15 / 3,68
3,16 / 3,92 / 5,28
3,80 / 5,08 / 6,84
3,85 / 6,26 / 8,51
4,38 / 7,95 / 10,28
Water flow 3)
l/h
331 / 374 / 472
334 / 543 / 634
544 / 675 / 909
655 / 875 / 1 178
663 / 1 078 / 1 466
754 / 1 369 / 1 771
Water pressure drop 3)
kPa
6,0 / 7,0 / 10,0
3,0 / 9,0 / 11,0
7,0 / 10,0 / 17,0
8,0 / 13,0 / 22,0
3,0 / 8,0 / 14,0
6,0 / 17,0 / 26,0
Total cooling capacity 2)
kW
1,29 / 1,48 / 1,97
1,99 / 2,68 / 3,37
2,55 / 3,21 / 4,00
—
2,97 / 4,96 / 6,63
3,17 / 6,01 / 7,55
Sensible capacity 2)
kW
1,18 / 1,38 / 1,84
1,49 / 2,07 / 2,65
2,03 / 2,58 / 3,30
—
2,23 / 3,77 / 5,06
2,38 / 4,68 / 5,95
Water flow 2)
l/h
232 / 258 / 359
342 / 465 / 576
437 / 563 / 683
—
511 / 851 / 1 137
543 / 1 030 / 1 294
4-pipes
Water pressure drop 2)
kPa
6,0 / 8,0 / 13,0
4,0 / 7,0 / 11,0
6,0 / 10,0 / 15,0
—
5,0 / 14,0 / 24,0
6,0 / 20,0 / 30,0
Heating capacity 4)
kW
1,09 / 1,27 / 1,67
3,10 / 4,40 / 5,46
4,32 / 5,00 / 5,80
—
5,28 / 7,79 / 10,04
6,43 / 10,07 / 12,77
Water flow 4)
l/h
94 / 109 / 144
267 / 379 / 470
372 / 431 / 500
—
455 / 671 / 865
554 / 867 / 1 100
Water pressure drop 4)
kPa
15,0 / 17,0 / 28,0
7,0 / 13,0 / 20,0
13,0 / 17,0 / 23,0
—
4,0 / 7,0 / 11,0
5,0 / 11,0 / 16,0
2-pipes
dB(A)
38 / 42 / 49
35 / 47 / 53
42 / 48 / 57
35 / 40 / 49
38 / 46 / 54
40 / 52 / 59
4-pipes
dB(A)
37 / 41 / 49
35 / 47 / 53
42 / 48 / 57
—
38 / 46 / 54
40 / 52 / 59
2-pipes
dB(A)
27 / 31 / 40
26 / 35 / 44
33 / 39 / 48
26 / 31 / 40
29 / 37 / 45
31 / 43 / 50
4-pipes
dB(A)
Sound levels
Sound power
Sound pressure 5)
NR 5)
27 / 31 / 40
26 / 35 / 44
33 / 39 / 48
—
29 / 37 / 45
31 / 43 / 50
2-pipes
23 / 27 / 35
20 / 30 / 39
28 / 34 / 43
21 / 26 / 35
22 / 32 / 40
25 / 38 / 50
4-pipes
23 / 27 / 35
20 / 30 / 39
28 / 34 / 43
—
22 / 32 / 40
25 / 38 / 45
Ventilation
Number of fans
Air flow
m³/h
1
1
1
1
1
1
360 / 450 / 659
320 / 504 / 734
486 / 626 / 900
529 / 720 / 979
500 / 824 / 1 159
601 / 1 080 / 1 447
G1
G1
G1
G1
G1
G1
Filter
Electrical data
Voltage
Power supply
V
Phase
Consumption
230
230
230
230
230
230
Single phase
Single phase
Single phase
Single phase
Single phase
Single phase
Frequency
Hz
50 / 60
50 / 60
50 / 60
50 / 60
50 / 60
50 / 60
2-pipes
W
25 / 35 / 58
17 / 34 / 58
38 / 58 / 99
28 / 41 / 66
34 / 61 / 88
44 / 92 / 125
W
25 / 35 / 58
17 / 34 / 58
38 / 58 / 99
—
34 / 61 / 88
44 / 92 / 125
W
1 500
2 500
2 500
2x1 500
2x1 500
2x1 500
Female gas
threaded
Female gas
threaded
Female gas
threaded
Female gas
threaded
Female gas
threaded
Female gas
threaded
4-pipes
Electric heater
Water connections
Connection type
2 or 4-pipes
Cooling
Inch
¾
¾
¾
1
1
1
4-pipes
Heating
Inch
½
½
½
—
¾
¾
Dimension and weight
With plastic diffuser
HxWxD
mm
334 x 720 x 720
334 x 720 x 720
334 x 720 x 720
339 x 960 x 960
339 x 960 x 960
339 x 960 x 960
With IRYS COANDA 180
HxWxD
mm
353 x 595 x 595
353 x 595 x 595
353 x 595 x 595
366 x 849 x 849
366 x 849 x 849
366 x 849 x 849
With IRYS COANDA 360
HxWxD
mm
341 x 595 x 595
341 x 595 x 595
341 x 595 x 595
358 x 849 x 849
358 x 849 x 849
358 x 849 x 849
kg
14,8
16,5
16,5
37,1
37,1
39,6
FCEER
A to E
D
C
D
C
C
C
FCCOP
A to E
E
D
D
C
C
D
FCEER
A to E
E
C
D
—
C
D
FCCOP
A to E
E
C
D
—
C
C
Weight
Energy efficiency class 6)
Flex Air fan coil – Cassette AC fan
2-pipes
4-pipes
1) Fan standard factory set speeds. 2) According to Eurovent standard. Air: 27 °C DB/19 °C WB, chilled water: 7 °C/12 °C. 3) According to Eurovent standard. Air: 20 °C, hot water: 45 °C/40 °C. 4) According to
Eurovent standard. Air: 20 °C, hot water: 65 °C/55 °C. 5) Informative data, considering an hypothetical sound attenuation of the room and installation of 9 dB(A). 6) According to Eurovent. *Drain pump and G1 air
filter are included as standard.
Accessories supplied loose
Accessories supplied loose
Plastic or metallic (IRYS COANDA) diffusers (mandatory):
- IC180 G4 - Kit diffuser IRYS COANDA 180° with G4 filter
- IC360 G4 - Kit diffuser IRYS COANDA 360° with G4 filter
TCEASY 2P/4P - Kit controller, HMI-integrated, 2-pipe, 4-pipe, AC fan speed
TCEASY 2P+C/O - Kit controller, HMI-integrated, 2-pipe + changeover, AC fan speed
KIT Plogic - Kit Plogic control board
TCPOD GLASS AC - Kit controller, Modbus, HMI-integrated, AC fan speed, black or
white
KIT WRC - Kit wall-mounted remote control LCD (only with Plogic control board)
PAW-FC-907AC – Wired remote controller with touch control
KIT MB2 - Kit Plogic Modbus board
PAW-FC-903AC – Wired remote controller
IRC - Kit infrared remote control for Plogic
PAW-FC-RC1 - Advanced wired remote controller
SRC - Smart remote control - Mini building management system (only with Modbus
RTU)
ErP
✔
SUPER QUIET
COMMERCIAL
SMART EDGE
ErP compliant following COMMISSION REGULATION (EU) 2016/2281.
113