UK HYDRONICS GEN 26 - Flipbook - Page 115
RANGE
FAN COIL UNITS
Technical performance
Flex Air fan coil – Cassette EC fan
Fan speed 1)
P-FQ20
P-FQ30
P-FQ40
P-FQ50
P-FQ60
P-FQ70
Min / Med / Max
Min / Med / Max
Min / Med / Max
Min / Med / Max
Min / Med / Max
Min / Med / Max
2-pipes
Total cooling capacity 2)
kW
1,55 / 1,77 / 2,38
1,88 / 2,88 / 4,00
2,79 / 3,51 / 4,71
3,36 / 4,44 / 6,09
3,71 / 5,48 / 7,20
4,05 / 6,51 / 9,61
Sensible capacity 2)
kW
1,30 / 1,49 / 2,00
1,42 / 2,18 / 3,05
2,09 / 2,69 / 3,64
2,53 / 3,36 / 4,49
2,69 / 4,08 / 5,44
2,98 / 4,88 / 7,21
700 / 1 119 / 1 649
Water flow 2)
l/h
267 / 306 / 409
325 / 497 / 688
481 / 604 / 808
579 / 765 / 1 050
640 / 944 / 1 243
Water pressure drop 2)
kPa
4,0 / 5,0 / 10,0
3,0 / 7,0 / 14,0
6,0 / 10,0 / 18,0
7,0 / 12,0 / 22,0
3,0 / 6,0 / 11,0
5,0 / 12,0 / 25,0
Heating capacity 3)
kW
1,92 / 2,17 / 2,74
1,94 / 3,15 / 3,68
3,16 / 3,92 / 5,28
3,80 / 5,08 / 6,84
3,85 / 6,26 / 8,51
4,38 / 7,95 / 11,03
Water flow 3)
l/h
331 / 374 / 472
334 / 543 / 634
544 / 675 / 909
655 / 875 / 1 178
663 / 1 078 / 1 466
754 / 1 369 / 1 900
Water pressure drop 3)
kPa
6,0 / 7,0 / 10,0
3,0 / 9,0 / 11,0
7,0 / 10,0 / 17,0
8,0 / 13,0 / 22,0
3,0 / 8,0 / 14,0
6,0 / 17,0 / 29,0
Total cooling capacity 2)
kW
1,30 / 1,49 / 1,99
2,00 / 2,69 / 3,38
2,56 / 3,23 / 4,02
—
2,99 / 4,98 / 6,65
3,18 / 6,04 / 7,97
Sensible capacity 2)
kW
1,19 / 1,39 / 1,86
1,50 / 2,08 / 2,66
2,04 / 2,60 / 3,32
—
2,25 / 3,79 / 5,08
2,39 / 4,71 / 6,34
Water flow 2)
l/h
234 / 262 / 344
344 / 464 / 581
442 / 556 / 690
—
516 / 858 / 1 144
549 / 1 041 / 1 366
4-pipes
Water pressure drop 2)
kPa
6,0 / 8,0 / 13,0
4,0 / 7,0 / 11,0
6,0 / 10,0 / 15,0
—
5,0 / 14,0 / 24,0
6,0 / 20,0 / 33,0
Heating capacity 4)
kW
1,09 / 1,27 / 1,67
3,10 / 4,40 / 5,46
4,32 / 5,00 / 5,80
—
5,28 / 7,79 / 10,00
6,43 / 10,67 / 13,99
Water flow 4)
l/h
94 / 109 / 144
267 / 379 / 470
372 / 431 / 500
—
455 / 671 / 865
554 / 867 / 1 205
Water pressure drop 4)
kPa
13,0 / 17,0 / 28,0
7,0 / 13,0 / 20,0
13,0 / 17,0 / 23,0
—
4,0 / 7,0 / 11,0
5,0 / 11,0 / 19,0
2-pipes
dB(A)
36 / 40 / 49
35 / 44 / 53
42 / 48 / 57
35 / 40 / 49
38 / 46 / 54
40 / 52 / 61
4-pipes
dB(A)
36 / 40 / 49
35 / 44 / 53
42 / 48 / 57
—
38 / 46 / 54
40 / 52 / 61
2-pipes
dB(A)
27 / 31 / 40
26 / 35 / 44
33 / 39 / 48
26 / 31 / 40
29 / 37 / 45
31 / 43 / 50
4-pipes
dB(A)
Sound levels
Sound power
Sound pressure 5)
NR 5)
27 / 31 / 40
26 / 35 / 44
33 / 39 / 48
—
29 / 37 / 45
31 / 43 / 50
2-pipes
23 / 27 / 35
20 / 30 / 39
28 / 34 / 43
21 / 26 / 35
22 / 32 / 40
25 / 38 / 45
4-pipes
23 / 27 / 35
20 / 30 / 39
28 / 34 / 43
—
22 / 32 / 40
25 / 38 / 45
Ventilation
Number of fans
Air flow
m³/h
1
1
1
1
1
1
360 / 450 / 659
320 / 504 / 734
486 / 626 / 900
529 / 720 / 979
500 / 824 / 1 159
601 / 1 080 / 1 598
G1
G1
G1
G1
G1
G1
Filter
Electrical data
Voltage
Power supply
V
Phase
Consumption
230
230
230
230
230
230
Single phase
Single phase
Single phase
Single phase
Single phase
Single phase
Frequency
Hz
50 / 60
50 / 60
50 / 60
50 / 60
50 / 60
50 / 60
2-pipes
W
9 / 13 / 29
7 / 14 / 33
13 / 23 / 57
7 / 12 / 25
9 / 23 / 45
11 / 40 / 115
4-pipes
W
9 / 13 / 29
7 / 14 / 32
13 / 22 / 57
—
9 / 23 / 45
11 / 40 / 115
W
1 500
2 500
2 500
2x1 500
2x1 500
2x1 500
Female gas
threaded
Female gas
threaded
Female gas
threaded
Female gas
threaded
Female gas
threaded
Female gas
threaded
Electric heater
Water connections
Connection type
2 or 4-pipes
Cooling
Inch
¾
¾
¾
1
1
1
4-pipes
Heating
Inch
½
½
½
—
¾
¾
Dimension and weight
With plastic diffuser
HxWxD
mm
334 x 720 x 720
334 x 720 x 720
334 x 720 x 720
339 x 960 x 960
339 x 960 x 960
339 x 960 x 960
With IRYS COANDA 180
HxWxD
mm
353 x 595 x 595
353 x 595 x 595
353 x 595 x 595
366 x 849 x 849
366 x 849 x 849
366 x 849 x 849
With IRYS COANDA 360
HxWxD
mm
341 x 595 x 595
341 x 595 x 595
341 x 595 x 595
358 x 849 x 849
358 x 849 x 849
358 x 849 x 849
kg
14,8
16,5
16,5
37,1
37,1
39,6
Weight
Energy efficiency class 6)
Flex Air fan coil – Cassette EC fan
2-pipes
4-pipes
FCEER
A to E
B
A
B
A
A
A
FCCOP
A to E
B
B
B
A
A
A
FCEER
A to E
B
A
B
—
A
B
FCCOP
A to E
C
A
B
—
A
A
1) Fan standard factory set speeds (voltage). 2) According to Eurovent standard. Air: 27 °C DB/19 °C WB, chilled water: 7 °C/12 °C. 3) According to Eurovent standard. Air: 20 °C, hot water: 45 °C/40 °C.
4) According to Eurovent standard. Air: 20 °C, hot water: 65 °C/55 °C. 5) Informative data, considering an hypothetical sound attenuation of the room and installation of 9 dB(A). 6) According to Eurovent. *Drain
pump and G1 air filter are included as standard.
Accessories supplied loose
Accessories supplied loose
Plastic or metallic (IRYS COANDA) diffusers (mandatory):
- IC180 G4 - Kit diffuser IRYS COANDA 180° with G4 filter
- IC360 G4 - Kit diffuser IRYS COANDA 360° with G4 filter
TCEASY 2P/4P - Kit controller, HMI-integrated, 2-pipe, 4-pipe, AC fan speed
TCEASY 2P+C/O - Kit controller, HMI-integrated, 2-pipe + changeover, AC fan speed
TCPOD WHITE (BLACK) 2P/4P - Kit controller, Modbus, HMI-integrated, 2-pipe,
4-pipe, EC fan speed, white (black)
KIT Plogic - Kit Plogic control board
KIT WRC - Kit wall-mounted remote control LCD (only with Plogic control board)
KIT MB2 - Kit Plogic Modbus Board
TCPOD WHITE (BLACK) 2P+EH - Kit controller, Modbus, HMI-integrated, 2-pipe+
electrical heater, EC fan speed, white (black)
IRC - Kit infrared remote control for Plogic
PAW-FC-907EC - Wired remote controller with touch control
SRC - Smart remote control - Mini building management system (only with Modbus
RTU)
PAW-FC-903EC - Wired remote controller
ErP
✔
EC MOTOR
GREEN VENTILATION
SUPER QUIET
VERY HIGH
PERFORMANCE
COMMERCIAL
SMART EDGE
ErP compliant following COMMISSION REGULATION (EU) 2016/2281.
115