UK HYDRONICS GEN 26 - Flipbook - Page 21
RANGE
R410A
CHILLERS AND HEAT PUMPS
Technical performance
Voltage
V
Phase
Power supply
Frequency
Hz
Size
ECOi-W AQUA EVO H - heat pump
400
400
Three phase
Three phase
50
20
50
30
P-AQAVE0020HA
P-AQAVE0030HA
Cooling capacity 1)
Nominal (Min - Max)
kW
20,0 (9,33 - 28,0)
29,0 (13,9 - 35,9)
Input power 1)
Nominal (Min - Max)
kW
4,15 (2,38 - 6,61)
7,24 (3,51 - 13,0)
EER 1)
Nominal (Min - Max)
Cooling capacity 2)
Nominal (Min - Max)
Input power 2)
Nominal (Min - Max)
EER 2)
Nominal (Min - Max)
4,82 (3,92 - 4,24)
4,01 (3,96 - 2,76)
kW
21,0 (6,60 - 25,2)
28,0 (9,43 - 31,1)
kW
6,95 (2,52 - 10,3)
10,9 (3,14 - 12,4)
3,02 (2,62 - 2,45)
2,57 (3,00 - 2,51)
EER 75%
3,83
3,65
EER 50%
4,53
4,48
EER 25%
3,80
4,79
SEER 3)
ηs,c 3)
3,30
3,98
129
156
Nominal water flow (in the evaporator)
m³/h
3,64
5,92
Heating capacity 4)
Nominal (Min - Max)
kW
20,4 (9,94 - 29,4)
26,1 (11,5 - 34,0)
Input power 4)
Nominal (Min - Max)
kW
5,02 (2,98 - 8,37)
6,45 (3,01 - 9,80)
COP 4)
Nominal (Min - Max)
Heating capacity 5)
Nominal (Min - Max)
Input power 5)
Nominal (Min - Max)
COP 5)
Nominal (Min - Max)
4,06 (3,34 - 3,51)
4,05 (3,82 - 3,47)
kW
20,4 (8,90 - 27,4)
26,1 (10,2 - 33,9)
kW
6,44 (3,34 - 9,64)
8,42 (3,97 - 11,6)
3,17 (2,66 - 2,84)
3,10 (2,57 - 2,91)
3,75
3,68
SCOP 6) 7)
Energy efficiency class 6) 7)
ηs,h 6) 7)
A+++ to D
SCOP 6) 8)
Energy efficiency class 6) 8)
ηs,h 6) 8)
A+++ to D
A+
A+
147
144
3,00
2,95
A+
A+
117
115
5,92
Nominal water flow (in the evaporator)
m³/h
3,64
Sound power 9)
dB(A)
74
75
Sound pressure at 10 m 10)
dB(A)
43
44
20
30
mm
1 615 x 539 x 1 477
1 615 x 539 x 1 477
kg
260
275
Male gas threaded
Male gas threaded
1¼
1¼
Physical features
ECOi-W AQUA EVO H - heat pump
Dimension
HxWxL
Operating weight
Water connections
Type of connections (evaporator)
Inlet/outlet diameter
Inch
1) According to EN 14511‑2013: chilled water inlet/outlet temperature: 23/18 °C, outdoor ambient temperature 35 °C. 2) According to EN 14511‑2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor
ambient temperature 35 °C DB. 3) According to EN 14825 standard. 4) According to EN 14511‑2013: warm water inlet/outlet temperature: 30/35 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 5) According
to EN 14511‑2013: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 6) ErP compliant: following COMMISSION REGULATION (EU) No 813/2013. 7) According to
EN 14825 standard ‑ low temperature application (35 °C). 8) According to EN 14825 standard ‑ medium temperature application (55 °C). 9) Sound levels are at fully loaded conditions. Sound power values refers
to ISO 3744 standard. 10) Sound pressures refer to ISO 3744 standard, parallelepiped shape.
Accessories and options
Accessories and options
Buffer tank placed under unit
Coils treatments
Chassis acoustic insulation
Accessories supplied loose
Accessories supplied loose
P-373705
Water temperature sensor for second set-point zone
P-362384
Valves in – out
P-347941
Remote ON / OFF control
P-348144
3 way valve for DHW production – ON / OFF – DN 20
P-364735
Remote keyboard panel
P-375890
3 way valve for second set-point zone – 0-10 V – DN 25
P-362577
Flow switch
P-375891
3 way valve for second set-point zone – 0-10 V – DN 32
P-473465
Pressure switch
ErP
✔
HIGH
SEER
HIGH
SCOP
3,98
3,75
AIR
COOLED
PLATE HEAT
EXCHANGER
SCROLL INVERTER
COMPRESSOR
DHW
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.