UK HYDRONICS GEN 26 - Flipbook - Page 23
RANGE
R290
CHILLERS AND HEAT PUMPS
Technical performance
Voltage
V
Phase
Power supply
Frequency
400
400
400
400
Three phase
Three phase
Three phase
Three phase
Hz
Size
ECOi-W AQUA-G BLUE 50-80 H EC fan - heat pump
50
50
50
50
50
60
70
80
P-AQAG0080HA
P-AQAG0050HA
P-AQAG0060HA
P-AQAG0070HA
Cooling capacity 1)
kW
48,2
56,1
64,9
74,1
Input power 1)
kW
15,0
19,0
21,6
25,0
EER 1)
3,20
3,00
3,00
3,00
SEER 2)
ηs,c 2)
4,37
4,30
4,31
4,21
%
171,9
168,9
169,4
165,4
Heating capacity 3)
kW
49,2
61,1
73,5
83,6
Input power 3)
kW
15,6
18,6
21,7
24,9
COP 3)
3,2
3,3
3,4
3,4
SCOP 4)
ηs,h 4)
3,67
3,75
3,87
3,84
143,7
146,8
151,8
150,5
A+
A+
A++
A++
3,11
3,14
3,26
3,22
121,4
122,7
127,3
126,0
A+
A+
A++
A++
Energy efficiency class (SCOP) 4)
A+++ to D
SCOPMT 4)
ηs,hMT 4)
Energy efficiency class (SCOPMT) 4)
A+++ to D
Sound power (STD / S)
dB(A)
82,7 / 79,9
84,1 / 80,5
85,1 / 81,5
85,8 / 81,9
Sound pressure at 10 m (STD / S) 5)
dB(A)
51,0 / 48,2
52,3 / 48,7
53,3 / 49,7
54,0 / 50,1
50
60
70
80
mm
1 730
2 011
2 030
2 030
Length w/o / w water tank
mm
2 215 / 2 915 6)
2 180 / 2 680
2 180 / 2 680
2 180 / 2 680
Width
mm
1 032
1 160
1 160
1 160
kg
538
603
628
669
1
1
1
1
kg
4,50
4,80
5,30
6,80
Physical features
ECOi-W AQUA-G BLUE 50-80 H EC fan - heat pump
Height
Dimension
Operating weight
Refrigerant and compressors
Number of refrigerant circuits
Refrigerant (R290)
GWP 7)
CO₂ eq.
Compressors
Number / type
Capacity steps
0,02
0,02
0,02
0,02
2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
50 / 100
40 / 60 / 100
40 / 60 / 100
50 / 100
%
Water connections
Type of connections
Inlet/outlet diameter
Male gas threaded
Male gas threaded
Male gas threaded
Male gas threaded
Inch
1¼
2
2
2½
l
200
300
300
300
Buffer tank (option)
Volume
1) According to EN 14511‑2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According to EN 14825 and following COMMISSION REGULATION (EU) 2016/2281.
3) According to EN 14511‑2013: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 4) According to EN 14825 and following COMMISSION REGULATION
(EU) No 813/2013. 5) Sound pressures refer to ISO 3744 standard, parallelepiped shape. 6) Tank is external to the unit chassis. 7) Based on the Sixth Assessment Report (AR6) adopted by the Intergovernmental
Panel on Climate Change (IPCC).
*w/o: without, w: with.
Accessories and options
Accessories and options
Anti-vibration rubber mount / spring dampers
Electric heater for the water tank
Refrigerant gauges HP/LP
Variable or fixed speed pumps
Shut off valves
Water tank 200 L for sizes 50
Soft starter
Water tank 300 L for sizes 60-70-80
Accessories supplied loose
Accessories supplied loose
P-375281
SRC – mini BMS controller
SVC-HYD-COMM-CLD3
3-year pre-paid Cloud access
P-586595_G
Cascade controller
P-3721027
3 way valve and probe for DHW management for size 50
P-372061_G
Remote keyboard panel
P-3721028
3 way valve and probe for DHW management for sizes 60-80
P-372615_G
Kit 4G modem
P-3721050
Kit temperature probe for deported tank
SVC-HYD-COMM-CLD1
1-year pre-paid Cloud access
R290
HIGH
SEER
HIGH
SCOP
REFRIGERANT
4,33
3,54
AIR
COOLED
PLATE HEAT
EXCHANGER
SCROLL
COMPRESSOR
COMMERCIAL
SMART EDGE
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
23