UK HYDRONICS GEN 26 - Flipbook - Page 25
RANGE
R290
CHILLERS AND HEAT PUMPS
Technical performance
Voltage
V
Phase
Power supply
Frequency
400
400
400
Three phase
Three phase
Three phase
Hz
Size
ECOi-W AQUA-G EVO 60-110 H - heat pump
50
50
50
60
80
110
P-AQAVG0060CA
P-AQAVG0080CA
P-AQAVG0110CA
Cooling capacity 1)
kW
56,7
67,4
91,0
Input power 1)
kW
18,9
22,6
33,9
Total EER 1)
3,00
2,98
2,68
Total EER (A 35 °C, W 23/18 °C)
2,48
3,68
3,29
SEER 2)
ηs,c 2)
4,07
4,84
4,77
%
160,0
190,5
187,2
Heating capacity 3)
kW
61,2
80,8
101,9
Input power 3)
kW
17,6
22,3
29,7
3,48
3,62
3,43
Total COP 3)
Heating capacity (A 7 °C, W 30/35 °C)
kW
62,7
83,2
104,8
Input power (A 7 °C, W 30/35 °C)
kW
14,9
18,7
25,4
COP (A 7 °C, W 30/35 °C)
4,21
SCOP 4)
ηs,h 4)
4,32
%
Tentative data
4,45
4,13
4,13
4,49
169,6
162,0
176,5
3,72
3,56
3,87
139,4
151,7
SCOP 5)
ηs,h 5)
%
145,9
SCOP 6)
ηs,h 6)
3,41
3,25
3,55
%
133,3
127,1
138,8
SCOP 7)
ηs,h 7)
3,00
2,88
3,15
%
118,1
112,2
123,1
Energy efficiency class (SCOP) 4)
A+++ to D
A++
A++
A++
Sound power (STD)
dB(A)
79,0
80,0
81,0
Sound pressure at 10 m (STD) 8)
dB(A)
47,2
48,0
49,0
60
80
110
mm
1 998 x 1 116
1 998 x 1 116
1 998 x 1 116
mm
2 385
3 385
3 385
kg
572
906
950
Physical features
ECOi-W AQUA-G EVO 60-110 H - heat pump
Height x Width
Dimension
Length w/o / w water tank
Operating weight (STD)
Refrigerant and compressors
Number of refrigerant circuit
Compressor
Number / type
Capacity steps
%
1
1
1
1 / Scroll
2/ Scroll
2 / Scroll
25-100
25-100
25-100
Victaulic®
Victaulic®
Victaulic®
2
2½
2½
Not available
230
230
Water connections
Type of connections
Inlet/outlet diameter
Inch
Buffer tank (option)
Volume
l
1) According to EN 14511‑2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According to EN 14825 and following COMMISSION REGULATION (EU) 2016/2281.
3) According to EN 14511‑2013: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 4) According to EN 14825 and following COMMISSION REGULATION
(EU) No 813/2013. 4) According EN 14825 and following COMMISSION REGULATION (EU) No 813/2013: low temperature application. 5) According EN 14825 and following COMMISSION REGULATION
(EU) No 813/2013: intermediate temperature application. 6) According EN 14825 and following COMMISSION REGULATION (EU) No 813/2013: medium temperature application. 7) According EN 14825 and
following COMMISSION REGULATION (EU) No 813/2013: high temperature application. 5) Sound pressures refer to ISO 3744 standard, parallelepiped shape. 8) Sound pressures refer to ISO 3744 standard,
parallelepiped shape.
*w/o: without, w: with.
Accessories and options
Accessories and options
Accessories and options
Dual pressure safety valve with changeover device
Pump acoustic box (super low noise version)
Water tank (for sizes 80-110)
Epoxy or blygold treatment
Power factor corrector capacitor (for sizes 80-110)
Hydro connection pipes
Chiller protection grids
Variable pump
Energy meter
Anti-vibration rubber mount / spring dampers
Water pressure switch
Flow meter
Compressor jacket (super low noise version)
Shut off valve
BACnet MSTP or BACnet IP
Tentative data
Accessories supplied loose
Accessories supplied loose
Water filter
Separator refrigerant/water
Kit remote control
Manifold 3’’ for modular configuration standard (60 cm distance)
Kit 4G modem
Manifold 3’’ for modular configuration ultra-compact (5 cm distance)
Tentative data
1-year pre-paid Cloud access
Manifold 4’’ for modular configuration standard (60 cm distance)
3-year pre-paid Cloud access
Manifold 4’’ for modular configuration ultra-compact (5 cm distance)
Flow switch
DHW kit including a water temperature probe, a 230 V motorised 3 way valve
R290 ErP
REFRIGERANT
✔
HIGH
SEER
HIGH
SCOP
5,19
4,59
AIR
COOLED
PLATE HEAT
EXCHANGER
SCROLL INVERTER
COMPRESSOR
DHW
COMMERCIAL
SMART EDGE
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
25