UK HYDRONICS GEN 26 - Flipbook - Page 27
RANGE
R410A
CHILLERS AND HEAT PUMPS
Technical performance
Voltage
V
Phase
Power supply
Frequency
400
400
400
400
400
Three phase
Three phase
Three phase
Three phase
Three phase
Hz
Size
ECOi-W AQUA 20-40 C - chiller
50
50
50
50
50
20
25
30
35
40
P-AQAE0020CA
P-AQAE0025CA
P-AQAE0030CA
P-AQAE0035CA
P-AQAE0040CA
Cooling capacity 1)
kW
19,2
24,3
27,1
36,7
39,0
Input power 1)
kW
5,9
7,7
9,3
12,2
13,0
EER 1)
3,25
3,17
2,9
3,01
3,0
SEER 2) 3)
ηs,c 2) 3)
4,78
4,38
4,43
4,43
4,48
188
172
174
174
176
Nominal water flow (in the evaporator)
m³/h
3,3
4,2
4,7
6,3
6,7
Sound power (STD fan)
dB(A)
75
76
76
77
77
Sound pressure at 10 m (STD fan) 4)
dB(A)
42,8
43,8
43,8
44,8
44,8
P-AQAE0040HA
ECOi-W AQUA 20-40 H - heat pump
P-AQAE0020HA
P-AQAE0025HA
P-AQAE0030HA
P-AQAE0035HA
Cooling capacity 1)
kW
18,7
23,7
26,4
35,8
38,1
Input power 1)
kW
5,9
7,7
9,4
12,3
13,1
EER 1)
3,15
3,07
2,81
2,92
2,92
SEER 2)
ηs,c 2)
4,68
4,31
4,28
4,25
4,33
170
184
169
168
167
Nominal water flow (in the evaporator)
m³/h
3,3
4,3
4,6
6,2
6,4
Heating capacity 5)
kW
19,5
26,9
29,7
37,3
41,6
Input power 5)
kW
COP 5)
6,1
9,3
9,9
13,2
13,5
3,19
2,90
2,99
2,82
3,08
COP 6)
4,17
4,10
4,10
4,11
3,86
SCOP 2) 7)
3,50
3,38
3,45
3,50
3,50
Energy efficiency class 2) 7)
ηs,h 2) 7)
A+++ to D
A+
A+
A+
A+
A+
137
132
135
137
137
Nominal water flow (in the evaporator)
Sound power (STD fan)
m³/h
3,4
4,7
5,2
6,5
7,2
dB(A)
75
76
76
77
Sound pressure at 10 m (STD fan) 4)
77
dB(A)
42,8
43,8
43,8
44,8
44,8
ECOi-W AQUA 25-40 E - condensing unit
—
P-AQAE0025EA
P-AQAE0030EA
P-AQAE0035EA
P-AQAE0040EA
Cooling capacity 8)
kW
—
32,4
33,7
43,1
44,8
Input power 8)
kW
—
10,0
10,7
14,9
15,0
—
3,24
3,15
2,90
2,99
dB(A)
—
75
75
76
76
20
25
30
35
40
Height (STD / HPF)
mm
1 983 / 2 025
1 983 / 2 025
1 983 / 2 025
1 983 / 2 025
1 983 / 2 025
Width w/o / w water tank
mm
1 000 / 1 507
1 000 / 1 507
1 000 / 1 507
1 000 / 1 507
1 000 / 1 507
Length
mm
1 000
1 000
1 000
1 000
1 000
kg
285 / 450
295 / 460
325 / 490
335 / 500
335 / 500
Male gas threaded
BSPP ISO 228
Male gas threaded
BSPP ISO 228
Male gas threaded
BSPP ISO 228
Male gas threaded
BSPP ISO 228
Male gas threaded
BSPP ISO 228
1½
1½
1½
1½
1½
—
25
30
35
40
mm
—
1 983 x 1 000 x 1 000
1 983 x 1 000 x 1 000
1 983 x 1 000 x 1 000
1 983 x 1 000 x 1 000
kg
—
260
270
280
280
Inch
—/—
⅝/1⅛
⅝/1⅛
⅝/1⅛
⅝/1⅛
EER 8)
Sound power
Physical features
ECOi-W AQUA 20-40 C/H - chiller / heat pump
Dimension
Operating weight without / with water tank - 1 pump
Water connections
Type of connections (evaporator)
Inlet/outlet diameter
Inch
ECOi-W AQUA 25-40 E - condensing unit
Dimension
HxWxL
Operating weight
Refrigerant connections
Liquid / suction line
1) According to EN 14511‑2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According to EN 14825. 3) ErP compliant: following COMMISSION REGULATION (EU)
2016/2281. 4) Sound pressures refer to ISO 3744 standard, parallelepiped shape. 5) According to EN 14511‑2013: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB.
6) According to EN 14511‑2013: warm water inlet/outlet temperature: 30/35 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 7) ErP compliant: following COMMISSION REGULATION (EU) No 813/2013. 8) Data
refers to 7 °C leaving chilled water temperature and 35 °C condenser air temperature, according EN 14511‑2013 standard.
*w/o: without, w: with.
Accessories and options
Accessories and options
Accessories and options
Anti-vibration rubber mount / spring dampers
Modbus TCP/IP
Variable or fixed* speed pumps
BACnet IP or BACnet MSTP
Outdoor coil protection grid
Water pressure switch
Fan speed control
Nordic pack (H type only)
Water tank 100 L
Finned coil blygold treatment (upon request) or epoxy
Shut off valves
Without neutral (upon request)
High pressure fan (HPF)
Soft starter
*Not available with ECOi‑W AQUA C and ECOi‑W AQUA H 20‑30 due to Ecodesign compliance.
Accessories supplied loose
Accessories supplied loose
P-375281
SRC – mini BMS controller
SVC-HYD-COMM-CLD1
1-year pre-paid Cloud access
P-372061
Remote keyboard panel
SVC-HYD-COMM-CLD3
3-year pre-paid Cloud access
P-372615
Kit 4G modem
P-378016
Kit anti-vibration mount rubber
ErP
✔
HIGH
SEER
HIGH
SCOP
4,59
3,40
AIR
COOLED
PLATE HEAT
EXCHANGER
SCROLL
COMPRESSOR
SUPER QUIET
VERY HIGH
PERFORMANCE
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
27