UK HYDRONICS GEN 26 - Flipbook - Page 28
GENERAL
R32
ECOi-W AQUA-Z EVO 40-50 H · R32
R32
Air cooled heat pumps Inverter.
REFRIGERANT
Cooling capacity: 41 to 48 kW.
Heating capacity: 42 to 49 kW.
The range at a glance
· 1 version: H (heat pump)
· 2 sizes
· 2 acoustic options: STD (standard) and S (super low noise)
Advantages
· Low GWP R32 refrigerant (GWP= 675)
· Inverter driven compressor
· Very high performance (SEER up to 5,65, SCOP up to 4,52)
· Low energy consumption
· Expanded operating limit (LWT 58 °C with OAT 40 °C)
· Compact chassis
· Very quiet operation
· Cascade configuration through MAIN/SUB management:
up to 8 units
· SG Ready
· Very low refrigerant charge
· Removable panels for great accessibility to internal
components
Operating limits
Equipment
To be confirmed with AC SELECT:
https://acselect.panasonic.eu/
· 1 refrigerant circuit with Inverter scroll compressors for a
higher efficiency at partial load
· EC fan
· Stainless steel plate heat exchanger insulated with closed
cell synthetic foam
· Finned coil condenser constructed with seamless copper
tubes mechanically expanded into aluminium fins Bluefin treatment
· Hydraulic circuit without pump
· Complete integrated control system with an external
control panel that displays the operating parameters and
alarms
· Modbus RTU, Modbus TCP/IP
· Reduced mode for energy savings and low sound levels
· Electronic expansion valve
· Return or leaving water temperature control
· External switch (cooling/heating, ON / OFF, reduced
mode)
· Water filter and differential pressure switch
· Phase sequence monitor
· Without neutral
· DHW function available on the controller with DHW probe
and 3 way valve available as options
Ambient temperature.
‑15 °C
48 °C
‑15 °C
-20
-15
40 °C
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
Leaving water temperature.
‑10 °C 1)
20 °C
20 °C
-20
-15
-10
-5
0
5
10
15
20
25
58 °C
30
35
40
45
50
55
60
Operating limits at nominal speed.
1) Below 5 °C, glycol is required.
AC SELECT.
Smart and user-friendly selection tool.
Configure your air conditioning solution at required
conditions: https://acselect.panasonic.eu/
28