UK HYDRONICS GEN 26 - Flipbook - Page 29
RANGE
R32
CHILLERS AND HEAT PUMPS
Technical performance
Voltage
V
Phase
Power supply
Frequency
400
400
Three phase
Three phase
Hz
Size
ECOi-W AQUA-Z EVO 40-50 H EC fan - heat pump
50
50
40
50
P-AQAVZ0040HA
P-AQAVZ0050HA
Cooling capacity 1)
kW
41,0
48,2
Input power 1)
kW
12,8
15,1
3,20
3,19
5,59
5,65
EER 1)
SEER 2)
ηs,c 2)
%
221
223
Heating capacity 3)
kW
41,5
48,5
Input power 3)
kW
13,4
16,2
COP 3)
3,10
2,99
SCOP 4)
ηs,h 4)
4,22
4,52
166
178
A+++
A+++
Energy efficiency class (SCOP) 4)
A+++ to D
Sound power (STD / S)
dB(A)
79,5 / 78,5
80,5 / 79,5
Sound pressure at 10 m (STD / S) 5)
dB(A)
47,8 / 46,8
48,8 / 47,8
40
50
Height
mm
1 732
1 732
Length w/o / w water tank
mm
2 209 / 2 913 6)
2 209 / 2 913 6)
Width
mm
1 100
1 100
kg
348
368
1
1
Physical features
ECOi-W AQUA-Z EVO 40-50 H EC fan - heat pump
Dimension
Operating weight
Refrigerant and compressors
Number of refrigerant circuits
Refrigerant (R32)
kg
5
6
GWP 7)
CO₂ eq.
675
675
1 / Scroll Inverter
1 / Scroll Inverter
0-100
0-100
Compressors
Number / type
Capacity steps
%
Water connections
Type of connections
Inlet/outlet diameter
Male gas threaded
Male gas threaded
Inch
1¼
1¼
l
200
200
Buffer tank (option)
Volume
1) According to EN 14511‑2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According to EN 14825 and following COMMISSION REGULATION (EU) 2016/2281.
3) According to EN 14511‑2013: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 4) According to EN 14825 and following COMMISSION REGULATION
(EU) No 813/2013: low temperature application. 5) Sound pressures refer to ISO 3744 standard, parallelepiped shape. 6) Tank is external to the unit chassis. 7) Based on the Sixth Assessment Report (AR6)
adopted by the Intergovernmental Panel on Climate Change (IPCC).
*w/o: without, w: with.
Accessories and options
Accessories and options
BACnet MSTP or BACnet IP
Water tank
Energy meter for power input
Fin&Tube Al/Cu with epoxy
Coil guards
Anti-vibration mount rubber
Compressor jackets
Anti-vibration spring
Variable speed pumps
Kit water flow switch
Water filter
Water pressure switch
Water flow switch
Shut off valves
Accessories supplied loose
Accessories supplied loose
P-364735
P-3721027
ErP
✔
Kit remote control
HIGH
SEER
HIGH
SCOP
5,65
4,52
AIR
COOLED
PLATE HEAT
EXCHANGER
SCROLL INVERTER
COMPRESSOR
DHW
Kit DHW
COMMERCIAL
SMART EDGE
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
29