GENERAL
R410A
Technical performance
Voltage
400
400
400
400
400
400
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Hz
50
704
50
804
50
904
50
1 004
50
1 104
50
1 204
704
804
904
1 004
1 104
1 204
Cooling capacity 1)
kW
175,6
199,7
229,5
250,1
276,5
305,6
Input power 1)
kW
114,2
Power supply
V
Phase
Frequency
Size
ECOi-W VL 704-1 204 H HT - heat pump
66,3
72,4
83,6
87,4
101,1
EER 1)
2,64
2,75
2,74
2,85
2,73
2,67
SEER 2)
ηs,c 2)
3
3
3,1
3,28
3,3
3,23
117
117
121
128
129
126
Nominal water flow (in the evaporator)
m³/h
30,1
34,3
39,4
42,9
47,5
52,5
Heating capacity 3)
kW
200,7
224,0
256,6
273,7
305,5
341,5
Input power 3)
kW
68,6
71,7
81,8
90,2
103
115
2,93
3,13
3,14
3,04
2,98
2,97
COP 3)
COP 4)
3,66
3,92
3,91
3,79
3,73
3,73
SCOP 2) 5)
ηs,h 2) 5)
3,44
3,40
3,32
3,33
3,37
3,26
Nominal water flow (in the evaporator)
m³/h
135
133
130
130
132
127
34,9
39,0
44,7
47,6
53,2
59,4
100
Sound power 6)
dB(A)
99
99
100
100
100
Sound pressure at 10 m 7)
dB(A)
67
67
68
68
68
68
P-VLE0704EA
P-VLE0804EA
P-VLE0904EA
P-VLE1004EA
P-VLE1104EA
P-VLE1204EA
ECOi-W VL 704-1 204 E STD / HPF - condensing unit
Cooling capacity 8)
kW
199,0
224,0
258,0
283,0
315,0
347,0
Input power 8)
kW
68,7
74,7
86,6
90,6
106
120
Sound power 6)
dB(A)
93
93
94
94
95
95
Sound pressure at 10 m 7)
dB(A)
61
61
62
62
63
63
704
804
904
1 004
1 104
1 204
Cooling capacity 8)
kW
194,0
218,0
251,0
272,5
301,0
330,0
Input power 8)
kW
69,6
76,6
87,8
92,8
109
126
Sound power 6)
dB(A)
87
87
88
88
89
89
Sound pressure at 10 m 7)
dB(A)
55
55
56
56
57
57
704
804
904
1 004
1 104
1 204
Cooling capacity 8)
kW
188,5
211,0
244,0
264,5
292,0
319,0
Input power 8)
kW
72,0
79,5
90,5
95,5
112
131
Sound power 6)
dB(A)
83
83
84
84
85
85
Sound pressure at 10 m 7)
dB(A)
51
51
52
52
53
53
704
804
904
1 004
1 104
1 204
Cooling capacity 8)
kW
201,0
226,5
261,0
286,5
318,0
353,0
Input power 8)
kW
68,9
74,9
87,1
91,0
105
119
Sound power 6)
dB(A)
99
99
100
100
100
100
Sound pressure at 10 m 7)
dB(A)
67
67
68
68
68
68
ECOi-W VL 704-1 204 E L - condensing unit
ECOi-W VL 704-1 204 E S - condensing unit
ECOi-W VL 704-1 204 E HT - condensing unit
1) According to EN 14511‑2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According to EN 14825. 3) According to EN 14511‑2013: warm water inlet/outlet
temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 4) According to EN 14511‑2013: warm water inlet/outlet temperature: 30/35 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 5) ErP
compliant: following COMMISSION REGULATION (EU) No 813/2013. 6) Sound levels are at fully loaded conditions. Sound power values refers to ISO 3744 standard. 7) Sound pressures refer to ISO 3744 standard,
parallelepiped shape. 8) Data refers to 7 °C leaving chilled water temperature and 35 °C condenser air temperature.
42