GENERAL
R410A
ECOi-W AQUA EVO 400-800 C · R410A
Air cooled chillers.
Cooling capacity: 390,4 to 775,4 kW.
The range at a glance
· 1 version: C (chiller)
· 8 sizes
· 3 configurations: STD (standard), HT (high temperature)
and HPF (high pressure fan)
· 2 fan types: AC (standard fan) and EC (high-efficiency fan)
· 2 acoustic options: STD (standard) and S (super low
noise)
Advantages
· High seasonal performances: SEER up to 4,6
· Low sound emission and high-efficiency level in a single
unit: Super Low Noise version
· Electronic expansion device: excellent control of
superheating for the best performance at full and partial
load and for a safe operation
· E-coated microchannel coils: Significant reduction on
refrigerant charge and operating weight and excellent
anticorrosion protection with the standard delivery
· Compressor box: remarkable sound reduction even for
the basic noise version
· Control platform: modular architecture, compressor
envelope integration, corrective actions in border line
areas, easy-friendly user interface
Operating limits
To be confirmed with AC SELECT:
https://acselect.panasonic.eu/
ECOi-W AQUA EVO 400-800 C - chiller
Chilled liquid
Liquid outlet
temperature
Water
°C
From 5 to 18
Water with glycol*
°C
From -10 to 5
ΔT
K
From 3 to 7
bar
6
STD
°C
From 10 to 48
S / EC / EC S
°C
From -18 to 48
HT
°C
From -18 to 52
Pa
0
Pa