UK HYDRONICS GEN 26 - Flipbook - Page 45
RANGE
R410A
CHILLERS AND HEAT PUMPS
Technical performance
Voltage
V
Phase
Power supply 1)
Frequency
Hz
Size
400
400
400
400
400
400
400
400
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
50
400
50
450 S
50
490 S
50
530 S
50
600
50
670
50
750 S
50
800 S
ECOi-W AQUA EVO 400-800 C AC - chiller
P-AQAVE
0400CA
0450CA
0490CA
0530CA
0600CA
0670CA
0750CA
0800CA
Nominal cooling capacity 2)
kW
390,4
431,1
470,2
513,7
584,5
653,2
727,7
775,4
Input power 2)
kW
126,7
138,6
152,7
167,9
189,1
210,7
234,7
250,1
EER 2)
3,08
3,11
3,08
3,06
3,09
3,10
3,10
3,10
SEER 3) 4)
ηs,c 3) 4)
4,48
4,63
4,58
4,78
4,58
4,59
4,73
4,70
%
176
182
180
188
180
180,7
186
185
Nominal water flow (in the evaporator)
m³/h
68,0
75,1
82,0
89,5
101,8
113,9
113,9
135,1
Sound power 5)
dB(A)
92
87
87
87
94
94
89
89
Sound pressure at 10 m 6)
dB(A)
60
54
54
54
61
61
56
56
400
450 S
490 S
530 S
600
670
750 S
800 S
ECOi-W AQUA EVO 400-800 C EC - chiller
Nominal cooling capacity 2)
kW
400,0
447,0
489,0
535,0
599,0
669,0
751,4
801,4
Input power 2)
kW
127,0
140,0
154,0
170,0
189,0
211,0
239,7
255,7
EER 2)
3,15
3,19
3,17
3,16
3,17
3,17
3,13
3,13
SEER 3) 4)
ηs,c 3) 4)
4,65
4,58
4,68
4,55
4,78
4,87
4,65
4,68
%
183
180
184
179
188
192
183
184
Nominal water flow (in the evaporator)
m³/h
68,8
76,9
84,2
92,2
103,1
115,1
131,0
139,7
Sound power 5)
dB(A)
92
93
93
94
94
94
95
95
Sound pressure at 10 m 6)
dB(A)
60
61
60
61
61
61
62
62
400
450 S
490 S
530 S
600
670
750 S
800 S
mm
2 500 x 2 175
2 500 x 2 175
2 500 x 2 175
2 500 x 2 175
2 500 x 2 175
2 500 x 2 175
2 500 x 2 175
2 500 x 2 175
Length STD / EC / HPF mm
4 580
5 620
6 680
6 680
7 760
7 760
8 900
8 900
Length S / EC S / HT
mm
5 620
6 680
7 760
7 760
8 800
8 800
11 000
11 000
STD / EC / HPF
kg
3 028
3 367
3 783
4 069
4 317
4 524
5 536
5 607
S / EC S / HT
kg
3 318
3 656
4 069
4 369
4 597
4 789
6 111
6 183
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
4
4
4
4
4
5
6
6
Physical features
ECOi-W AQUA EVO 400-800 C - chiller
HxW
Dimension
Operating weight
Water connections (evaporator and condenser)
Type of connections
Inlet/outlet diameter
Inch
1) Voltage 400 V +/‑ 10%. 2) According to EN 14511‑2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 3) ErP compliant: following COMMISSION REGULATION (EU)
2016/2281. 4) According to EN 14825. 5) Sound power is declared in nominal full load condition (cooling operation), referring to ISO standard 9614, in accordance with Eurovent certification program. 6) Sound
pressure refer to ISO Standard 3744, parallelepiped shape in a free field on a reflective surface.
Accessories and options
Accessories and options
Anti-vibration spring dampers
Mechanical gauges
Automatic circuit breaker
Overload protection for compressors
Coils treatments
Power factor corrector capacitors
Desuperheater
Several communication protocols
Fan speed control (-14 °C in cooling mode – standard as EC/HPF/S versions)
Soft starter
Hydrokit with 1 or 2 pumps with or without buffer tank (500 L 400-450, 1 000 L 470670)
Unit protection grilles
Accessories supplied loose
Accessories supplied loose
P-376463
Sequencer for up to 4 chillers installation
P-473465
Pressure switch
P-347941
Remote ON / OFF control
P-348620
Water filter for sizes 400-530
P-364735
Remote keyboard panel
P-348618
Water filter for sizes 580-750
P-365581
Flow switch
P-362589
Water filter for size 800
ErP
✔
HIGH
SEER
4,78
AIR
COOLED
PLATE HEAT
EXCHANGER
SCROLL
COMPRESSOR
VERY HIGH
PERFORMANCE
Variable pump (for sizes 750-800 upon request)
ErP: Check ErP compliance according to the configurations in AC SLECT:
https://acselect.panasonic.eu/.
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
45