UK HYDRONICS GEN 26 - Flipbook - Page 88
GENERAL
R410A
ECOi-RT 65-190 C · R410A
Rooftop cooling only units.
Cooling capacity: 62,8 to 197 kW.
The range at a glance
· 1 version: C (cooling only)
· SEER up to 3,94
· 5 sizes
· Nominal air flow from 11 500 to 30 000 m³/h
· Additional heaters available
· Many aeraulic configurations
· 2 energy recovery system configurations (RECO and
TRECO)
Advantages
· Low energy consumption EC fans
· Wide operating limits
· Thermal/acoustic insulation: double skin (25 mm glass
wool)
· 100% factory tested
Operating limits
To be confirmed with AC SELECT:
https://acselect.panasonic.eu/
Ambient temperature (DB).
‑10 °C 1)
-20
-15
-10
50 °C
-5
0
5
10
15
20
25
30
35
40
45
50
55
35
40
45
50
55
Temperature before indoor coil 2).
12 °C
-20
-15
-10
-5
0
5
10
26 °C
15
20
1) Using fan speed control option. 2) Cooling: °C (WB).
88
25
30
Equipment
· 2 refrigerant circuits for an optimised defrost logic,
completely closed in a separate compartment to reduce
noise level. Each circuit comprises of Scroll
compressor(s) (2 per circuit from size 160), indoor and
outdoor coils, filter dryer, sight glass, thermostatic or
electronic expansion valve (from 160 to 190), high and low
pressure switches, defrosting pressure switch, intake
temperature sensor, and a liquid accumulation bottle (for
sizes from 160 to 190)
· 2 or 4 Scroll compressors - 1 per circuit from 65 to 95
and 2 per circuit for 160 to 190 assembled together in
tandem. Each compressor is equipped with a crankcase
heater and mounted on rubber pads to eliminate noise
and vibration transmissions. The motors are equipped
with overload protection and have direct start-up. A
phase sequence monitor is supplied as standard
· The controls are grouped and wired in the unit, factory
tested and shipped READY TO USE. They are located in a
sealed compartment that is isolated from the air flow.
The electrical equipment is compliant with EC standards
and EN60204-1
· The outdoor and indoor heat exchangers are made of
seamless copper tubes mechanically expanded into
aluminium fins. Outdoor coils are largely dimensioned to
optimise performance and defrost cycles. They are also
equipped with a protective grille to prevent shocks Bluefin treatment applicable to reversible type
· The unit casing is of heavy duty galvanized steel, painted
with a special anti-corrosion process (RAL 9001). The
complete unit is covered with double skin panels to
ensure perfect thermal insulation. For full unit access,
all service panels are removable. Under the indoor heat
exchanger, an extractable condensate drain pan allows
hygienic cleaning
· The indoor fan(s) are plug type with EC motors; low
pressure or high pressure according to the configuration
selected by the customer.