UK HYDRONICS GEN 26 - Flipbook - Page 99
RANGE
AQUAREA
FAN COIL UNITS
Aquarea Air Smart fan coil – Wall-mounted
Slim chassis profile, only 128 mm / RAL 9003 / DC Inverter –
maximising comfort and energy savings / Modulated air flow.
Possible configurations: Left or right water connections / 2
or 3 way valves as accessories / On-board or wall mounted
control or PCB for analog input (0-10 V)
Optional
Model (the complete model codes are shown in the table below)
Fan speed 1)
P-FMM10
P-FMM15
P-FMM20
P-FMM40
Min / Med / Max
Min / Med / Max
Min / Med / Max
Min / Med / Max
1,32 / 2,66 / 3,94
Total cooling capacity 2)
kW
0,49 / 0,88 / 1,24
0,62 / 1,08 / 1,61
0,70 / 1,21 / 1,94
Sensible capacity 2)
kW
0,37 / 0,70 / 0,98
0,52 / 0,86 / 1,27
0,57 / 1,02 / 1,52
1,08 / 2,05 / 2,92
Water flow 2)
l/h
84,00 / 150,80 / 212,40
106,20 / 185,00 / 275,80
119,90 / 207,30 / 332,40
226,40 / 455,30 / 674,30
Water pressure drop 2)
kPa
4,8 / 10,5 / 11,7
4,7 / 5,6 / 5,1
5,5 / 5,4 / 5,3
1,8 / 6,0 / 12,1
Heating capacity 3)
kW
0,54 / 0,98 / 1,45
0,76 / 1,30 / 1,93
0,78 / 1,49 / 2,28
1,63 / 3,04 / 4,44
Water flow 3)
l/h
97,00 / 176,30 / 264,50
139,30 / 239,80 / 354,40
141,10 / 273,30 / 414,40
296,40 / 547,00 / 800,90
Water pressure drop 3)
kPa
5,1 / 12,0 / 16,3
4,8 / 6,3 / 7,2
6,0 / 6,4 / 8,1
2,3 / 6,9 / 14,1
Sound levels
Sound power
dB(A)
35 / 46 / 53
36 / 47 / 54
37 / 48 / 58
38 / 48 / 62
Sound pressure 4)
dB(A)
25 / 33 / 40
25 / 34 / 41
26 / 34 / 42
27 / 37 / 51
m³/h
84 / 155 / 228
124 / 229 / 331
138 / 283 / 440
230 / 480 / 788
V
230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
W
5 / 8 / 19
5 / 9 / 20
5 / 11 / 29
8 / 23 / 30
Eurokonus
Eurokonus
Eurokonus
Eurokonus
¾
¾
¾
¾
335 x 815 x 128 / 14
335 x 1 015 x 128 / 16
335 x 1 215 x 128 / 19
335 x 1 215 x 215 / 24
Ventilation
Air flow
Electrical data
Power supply
V / Phase / Hz
Consumption
Water connections
Hydraulic connections type
Hydraulic connections
Inch
Dimension and weight
Dimension / Weight
HxWxD
mm / kg
1) Fan standard factory set speeds. 2) According to Eurovent standard. Air: 27 °C DB/19 °C WB, chilled water: 7 °C/12 °C. 3) According to Eurovent standard. Air: 20 °C, hot water: 45 °C/40 °C. 4) Informative
data, considering an hypothetical sound attenuation of the room and installation of 9 dB(A).
Option 1. Standard configurations with built-in
accessories
Option 2. Configure your own Aquarea Air Smart fan
coil – Wall-mounted unit
Fan coil with on-board display and wireless IR control
Fan coil with on-board display and wireless IR control
Right-hand piping, built-in 3 way valve
Left-hand piping
Right-hand piping
P-FMM10DC-QNE
P-FMM10SC-Q0E
P-FMM10DC-Q0E
P-FMM15DC-QNE
P-FMM15SC-Q0E
P-FMM15DC-Q0E
P-FMM20DC-QNE
P-FMM20SC-Q0E
P-FMM20DC-Q0E
P-FMM40DC-QNE
—
P-FMM40DC-Q0E
Fan coil with wall-mounted control
Fan coil with wall-mounted control
Right-hand piping, built-in 3 way valve
Left-hand piping
Right-hand piping
P-FMM10DC-RNE
P-FMM10SC-R0E
P-FMM10DC-R0E
P-FMM15DC-RNE
P-FMM15SC-R0E
P-FMM15DC-R0E
P-FMM20DC-RNE
P-FMM20SC-R0E
P-FMM20DC-R0E
P-FMM40DC-RNE
—
Control (required, to be
ordered separately)
With Modbus
PCZ-EEB749
With integrated Wi-Fi
PCZ-EFB749
Control (required, to be
ordered separately)
P-FMM40DC-R0E
With Modbus
PCZ-EEB749
With integrated Wi-Fi
PCZ-EFB749
Fan coil with PCB for analog control (0-10 V)
Valve kits (optional)
Left-hand piping
Right-hand piping
P-FMM10SC-V0E
P-FMM10DC-V0E
P-FMM15SC-V0E
P-FMM15DC-V0E
P-FMM20SC-V0E
P-FMM20DC-V0E
—
P-FMM40DC-V0E
Valve kits (optional)
PCZ-V30688
3 way valve with motor for models 10, 15, 20
PCZ-V20687
2 way valve with motor for models 10, 15, 20
PCZ-V30718
3 way valve with motor for model 40
PCZ-V20139
2 way valve with motor for model 40
Control options.
On-board display
with Modbus.
Wall-mounted control
with Modbus or
integrated Wi-Fi.
PCB for analog control
(0-10 V).
PCZ-EEB749 /
PCZ-EFB749