Technical features
Fan coil wall AC fan
P‑FW07(IR)
P‑FW09(IR)
P‑FW18(IR)
P‑FW22(IR)
S2 / S3 / S4 1)
S2 / S3 / S4 1)
S2 / S3 / S4 1)
S2 / S3 / S4 1)
2‑pipes, without valve, without/with IR infrared control
Total cooling capacity 2)
kW
1,00 / 1,34 / 1,69
1,58 / 1,79 / 2,50
2,78 / 3,05 / 3,60
2,93 / 3,29 / 4,00
Sensible capacity 2)
kW
0,72 / 0,97 / 1,20
1,21 / 1,37 / 1,87
2,12 / 2,39 / 2,74
2,28 / 2,62 / 3,11
Water flow 2)
l/h
172 / 231 / 291
270 / 308 / 431
479 / 525 / 620
505 / 565 / 687
Water pressure drop 2)
kPa
18,6 / 24,9 / 31,4
18,5 / 21,4 / 31,0
34,6 / 40,0 / 52,3
37,2 / 42,8 / 54,9
3,18 / 3,63 / 4,50
Heating capacity 3)
W
1,42 / 1,62 / 1,72
1,68 / 1,92 / 2,80
2,99 / 3,30 / 4,10
Water flow 3)
l/h
245 / 279 / 296
289 / 331 / 482
515 / 568 / 706
548 / 625 / 775
Water pressure drop 3)
kPa
17,6 / 23,4 / 26,5
21,4 / 23,5 / 28,6
39,9 / 46,3 / 64,7
41,7 / 55,0 / 85,8
Sound levels
Sound power
dB(A)
45 / 49 / 51
40 / 43 / 52
47 / 50 / 54
50 / 55 / 60
Sound pressure 4)
dB(A)
30 / 33 / 35
32 / 36 / 40
39 / 41 / 43
39 / 43 / 48
NR 4)
dB(A)
32 / 36 / 38
34 / 39 / 44
40 / 43 / 46
43 / 46 / 50
1
1
1
1
m³/h
282 / 321 / 360
367 / 413 / 551
532 / 592 / 680
617 / 709 / 850
G1
G1
G1
G1
Ventilation
Number of fans
Air flow
Filter
Electrical data
Voltage
Power supply
V
Phase
Consumption
230
230
230
230
Single phase
Single phase
Single phase
Single phase
Frequency
Hz
50
50
50
50
Cooling
W
39 / 42 / 62
30 / 33 / 40
44 / 48 / 53
50 / 55 / 69
Heating
W
39 / 42 / 62
27 / 30 / 50
42 / 45 / 60
46 / 51 / 66
Female gas threaded
Female gas threaded
Female gas threaded
Female gas threaded
½
½
½
½
845 x 180 x 275 / 11
940 x 200 x 298 / 13
Water connections
Connection type
Connections
Inch
Dimension and weight
Dimension / Weight
LxWxH
mm / kg
845 x 180 x 275 / 11
Fan coil wall AC fan
940 x 200 x 298 / 13
P‑FW09IR‑3W
P‑FW22IR‑3W
S2 / S3 / S4 1)
S2 / S3 / S4 1)
2‑pipes, with valve, with IR infrared control
Total cooling capacity 2)
kW
1,11 / 1,25 / 1,40
2,32 / 2,68 / 3,10
Sensible capacity 2)
kW
0,91 / 1,08 / 1,25
1,68 / 1,98 / 2,28
Water flow 2)
l/h
191 / 215 / 241
400 / 460 / 532
Water pressure drop 2)
kPa
14,9 / 16,8 / 18,8
42,4 / 50,8 / 61,5
2,51 / 2,75 / 3,30
Heating capacity 3)
W
1,29 / 1,61 / 2,00
Water flow 3)
l/h
222 / 277 / 344
432 / 474 / 568
Water pressure drop 3)
kPa
16,1 / 21,3 / 28,2
45,8 / 48,6 / 54,1
Sound levels
Sound power
dB(A)
44 / 50 / 54
53 / 57 / 60
Sound pressure 4)
dB(A)
32 / 36 / 40
39 / 43 / 48
NR 4)
dB(A)
27 / 31 / 37
34 / 37 / 41
1
1
m³/h
150 / 250 / 400
290 / 400 / 600
G1
G1
Ventilation
Number of fans
Air flow
Filter
Electrical data
Voltage
Power supply
V
Phase
Consumption
230
230
Single phase
Single phase
Frequency
Hz
50
50
Cooling
W
35 / 38 / 43
50 / 58 / 69
Heating
W
30 / 33 / 43
50 / 58 / 69
Female gas threaded
Female gas threaded
½
½
845 x 180 x 275 / 11
940 x 200 x 298 / 13
Water connections
Connection type
Connections
Inch
Dimension and weight
Dimension / Weight
LxWxH
mm / kg
1) Fan standard factory set speeds. 2) According to Eurovent standard. Air: 27 °C DB/19 °C WB, chilled water: 7 °C/12 °C. 3) According to Eurovent standard. Air: 20 °C, hot water: 45 °C/40 °C. 4) Informative
data, considering an hypothetical sound attenuation of the room and installation of 9 dB(A).
Control options.
Optional wired remote
controller for AC fan,
2‑pipe and 4‑pipe
application.
Optional wired
remote controller
for AC fan 2‑pipe
application.
Optional wired
remote controller for
EC fan, 2‑pipe and
4‑pipe application.
PAW-FC-RC1
PAW-FC-903AC /
PAW-FC-907AC
PAW-FC-903EC /
PAW-FC-907EC
ErP
✔
SUPER QUIET
ErP compliant following COMMISSION REGULATION (EU) 2016/2281.
71