UK IRE REFRIGERATION GEN 25 - Flipbook - Page 19
CO2
REFRIGERATION
New 2024
REFRIGERATION INDEX
Standard outdoor unit
OCU-CR1000VF8
Anti corrosion coating outdoor unit
OCU-CR1000VF8A
OCU-CR2000VF8A*
OCU-CR1000VF8SL
OCU-CR1000VF8ASL
OCU-CR2000VF8ASL*
MT (15 kW)
MT (16 kW) / LT (8 kW)
MT (29 kW) / LT (15 kW)
380 / 400 / 415
380 / 400 / 415
380 / 400 / 415
Three phase
Three phase
Three phase
Hz
50
50
50
Cooling capacity at ET -10 °C AT 32 °C
kW
14,00
15,10
28,74
Cooling capacity at ET -35 °C AT 32 °C
kW
—
8,00
14,73
SEPR cooling at ET -10 °C AT 32 °C
2,62
2,86
3,10
SEPR freezing at ET -35 °C AT 32 °C
—
1,49
1,64
32 815
32 409
57 076
Type (MT: medium temperature, LT: low temperature)
Voltage
Power supply
V
Phase
Frequency
Annual electricity consumption at ET -10 °C AT 32 °C
kWh/a
Annual electricity consumption at ET -35 °C AT 32 °C
kWh/a
Evaporator connection
—
39 985
66 760
Multiple
Multiple
Multiple
Min ~ Max
°C
-20 ~ -5
-45 ~ -5
-45 ~ -5
Min ~ Max
°C
-20 ~ +43
-20 ~ +43
-20 ~ +45
R744
R744
R744
Refrigerant
Design pressure liquid line
Mpa
8
8
Design pressure suction line
Mpa
8
8
Yes
Yes
220 / 230 / 240
220 / 230 / 240
Yes
Yes
Yes
Yes
User system external alarm. Digital input. Non-voltage contact
Liquid tube electromagnetic valve
Vac
Showcase operation ON / OFF signal. Digital input. Non-voltage contact
Modbus communication line (RS485)
Ports
Compressor type
Dimension
HxWxD
mm
Net weight
2- stage rotary
2- stage rotary
1 941 x 890 x 890
1 941 x 890 x 890
Kg
Piping diameter 1)
293
320
Suction pipe
Inch (mm)
¾ (19,05)
¾ (19,05)
Liquid pipe
Inch (mm)
⅝ (15,88)
⅝ (15,88)
100
8
8
Yes
—
Yes
Yes
2- stage rotary
1 941 x 1 190 x 890
494
1 (25,40)
¾ (19,05)
Length of connection piping
m
PED
CAT
ΙΙ
ΙΙ
ΙΙ
Air flow
m³/min
220
220
220
External static pressure
Pa
58
58
58
—
Yes
Yes
Heat recovery port
Standard performance
100
Tentative data
Evaporation temperature
Ambient temperature
3)
100 3)
3)
Ambient temperature
°C
32
Evaporating temperature
°C
-10
-10
32
-35
-10
32
-35
Cooling capacity
kW
14,00
15,10
8,00
28,74
14,73
Power consumption
kW
8,20
8,20
7,57
15,67
13,45
Nominal load ampere
A
12,60
12,60
11,60
24,31
20,49
Sound pressure
dB(A)
36,0 6)
36,0 6)
36,0 6)
38,9 6)
38,9 6)
Necessary accessories
Drier filter liquid line, Ø6,35 mm
D-152T / DCY-P12
—
—
—
Drier filter liquid line, Ø15,88 mm
D-155T / DCY-P8
Yes (included)
Yes (included)
Yes (included)
Suction filter, Ø19,05 mm (outer Ø welding)
S-008T / S-008T1
Yes (included)
Yes (included)
Yes (included)
1) These diameters correspond to the output of the unit. The required diameter must be calculated with Refrigeration designer available on PRO Club. 2) PZ-68S (refrigeration oil) must be added according to
Refrigeration designer available on PRO Club. 3) PZ-68S (refrigeration oil) must be added if >50 m. 4) ET-10 °C, 65 S-1, 10 m from product. 5) ET-10 °C, 80 S-1, 10 m from product. 6) ET -10 °C, 60 S-1, 10 m from product.
* Available in Summer 2024. Tentative data.
45 °C
CO2
R744
HIGH EFFICIENCY
COMPRESSOR
SUPER QUIET
AMBIENT
TEMPERATURE
ANTI CORROSION
COATING
HEAT RECOVERY
PORT
AUTOMATIC FAN
5
YEARS
COMPRESSOR
WARRANTY
BMS
CONNECTIVITY
19