UK IRE REFRIGERATION GEN 25 - Flipbook - Page 27
R32
REFRIGERATION INDEX
REFRIGERATION
PACi NX Series Elite adaptive ducted unit - PF3 · R32
For light refrigeration applications.
nanoe™ X as a standard.
High temperature
Kit
36
Indoor unit - 1
Outdoor unit
Outdoor
30 °C
(DB)
60
71
100
125
140
200
250
S-6071PF3E S-6071PF3E S-1014PF3E S-1014PF3E S-1014PF3E S-1014PF3E S-1014PF3E S-1014PF3E S-1014PF3E
Indoor unit - 2
Outdoor
35 °C
(DB)
50
kW
—
—
—
—
—
—
U-36PZH3E5
U-50PZH3E5
U-60PZH3E5
U-71PZH4E5/8
U-100PZH4E5/8
U-125PZH4E5/8
S-1014PF3E S-1014PF3E S-1014PF3E
U-140PZH4E5/8
U-200PZH4E8
U-250PZH4E8
3,50
4,90
5,80
6,60
8,80
11,20
13,00
18,50
23,20
3,98
3,20
3,52
3,37
3,79
3,21
3,59
3,50
3,08
Indoor
15 °C
(WB)
Cooling capacity
Input power
kW
0,88
1,53
1,65
1,96
2,32
3,49
3,62
5,29
7,54
Indoor
12 °C
(WB)
Cooling capacity
kW
3,19
4,46
5,28
6,01
8,01
10,19
11,83
16,84
21,11
3,69
2,97
3,26
3,13
3,52
2,98
3,33
3,25
2,86
Input power
kW
0,86
1,50
1,62
1,92
2,27
3,42
3,55
5,18
7,39
Indoor
8 °C
(WB)
Cooling capacity
kW
2,10
2,94
3,48
3,96
5,28
6,72
7,80
11,10
13,92
3,06
2,46
2,70
2,59
2,92
2,47
2,76
2,69
2,37
Input power
kW
0,69
1,19
1,29
1,53
1,81
2,72
2,82
4,13
5,88
Indoor
15 °C
(WB)
Cooling capacity
kW
3,75
5,24
5,92
6,73
9,42
11,98
13,91
20,17
25,29
4,63
3,72
3,81
3,65
4,41
3,73
4,18
4,14
3,65
Input power
kW
0,81
1,41
1,55
1,84
2,13
3,21
3,33
4,87
6,94
Indoor
12 °C
(WB)
Cooling capacity
kW
3,43
4,80
5,39
6,14
8,62
10,98
12,74
18,50
23,20
4,33
3,49
3,55
3,40
4,13
3,49
3,91
3,89
3,42
Input power
kW
0,79
1,38
1,52
1,80
2,09
3,14
3,26
4,76
6,79
Indoor
8 °C
(WB)
Cooling capacity
kW
2,10
2,94
3,48
3,96
5,28
6,72
7,80
11,10
13,92
3,41
2,75
2,93
2,81
3,25
2,75
3,08
3,00
2,64
0,62
1,07
1,19
1,41
1,62
2,44
2,53
3,70
5,28
EER
EER
EER
EER
EER
EER
Input power
kW
Dimension (H x W x D) mm
Indoor unit
Net weight
kg
nanoe X Generator
Outdoor unit
Dimension (H x W x D) mm
Net weight
kg
250x1000x730 250x1000x730 250x1400x730 250x1400x730 250x1400x730 250x1400x730 250x1400x730 250x1400x730 250x1400x730
30
30
39
39
39
39
39
39
39
Mark 2
Mark 2
Mark 2
Mark 2
Mark 2
Mark 2
Mark 2
Mark 2
Mark 2
695x875x320 695x875x320 695x875x320 996x980x370 996x980x370 996x980x370 996x980x370 996x1140x460 996x1140x460
42
42
Accessories
43
66
84
86
86
—
—
Accessories
CZ-RTC6W
CONEX wired remote controller (non-wireless), white
PAW-GRDBSE20
Outdoor base ground support for noise and vibration absorption
CZ-RTC6WBL
CONEX wired remote controller with Bluetooth®, white
PAW-GRDSTD40
Outdoor elevation platform 400 x 900 x 400 mm
CZ-RTC6WBLW
CONEX wired remote controller with Wi-Fi and Bluetooth®, white
CZ-CENSC1
Econavi energy saving sensor
CZ-RTC6
CONEX wired remote controller (non-wireless), black
CZ-56DAF2
Air outlet plenum for S-3650PF3E
CZ-RTC6BL
CONEX wired remote controller with Bluetooth®, black
CZ-90DAF2
Air outlet plenum for S-6071PF3E
CZ-RTC6BLW
CONEX wired remote controller with Wi-Fi and Bluetooth®, black
CZ-160DAF2
Air outlet plenum for S-1014PF3E
CZ-RTC5B
Wired remote controller with Econavi function and datanavi
PAW-APF800F
NEW BION air pollutant filter for S-3650PF3E
PAW-APF1000F
NEW BION air pollutant filter for S-6071PF3E
PAW-APF1400F
NEW BION air pollutant filter for S-1014PF3E
CZ-RWS3 +
CZ-RWRC3
Infrared remote controller and receiver
PAW-WTRAY
Tray for condenser water compatible with outdoor elevation
platform
Technical focus
· 2 installation possibilities (horizontal / vertical)
· Maximum external static pressure: 150 Pa
· Selectable inlet air position (rear / bottom entry)
· Improved drain pan suitable for both horizontal / vertical
installation
· Drain pump included
· nanoe™ X (Generator Mark 2: 9,6 trillion hydroxyl
radicals/sec) as standard for the long duct piping case*
· New BION air pollutant filter for certain types of
pollutants, such as nitrogen dioxide (NO2), nitrogen
oxides (NOX) and Ozone (O3) (optional)
· Wired remote control CZ-RTC6WBL and CZ-RTC6BL
allows easy system setting via Bluetooth®
* The performance of nanoe™ X air can be expected even by 10 m long duct by Panasonic internal
survey.
2 installation possibilities (horizontal /
vertical)
Vertical installation is available.
ESP 150Pa, sufficient for remotely
installing units away from the rooms.
Improved drain pan design
Drain pan is shared in both
cases horizontal and vertical
installation.
No need to modify the unit.
Horizontal
Shared
drain pan
Vertical
27