UK IRE REFRIGERATION GEN 25 - Flipbook - Page 36
iCOOL
GENERAL INDEX
iCOOL OCU Series · R448A / R449A / R134a / R513A
Specifications and capacity tables.
New
2025
Model
OCU-KRC045M08
OCU-KRC070M08
OCU-KRC100M08
OCU-KSC120M08
OCU-KSC150M08
Compressor
Single
compressor
Single
compressor
Single
compressor
Single
compressor
Single
compressor
Compatible refrigerants
R448A, R449A,
R134a, R513A
R448A, R449A,
R134a, R513A
R448A, R449A,
R134a, R513A
R448A, R449A,
R134a, R513A
R448A, R449A,
R134a, R513A
PED category
I
II
II
II
II
MT (4,5)
MT (7,0)
MT (9,0)
MT (12,0)
MT (15,0)
SEPR cooling at ET -10 °C AT 32 °C
3,28
3,60
4,29
3,48
3,87
SEPR freezing at ET -35 °C AT 32 °C
—
—
—
—
—
Application and nominal cooling capacity
MT/LT (kW)
Annual electricity consumption at ET -10 °C AT 32 °C
kWh/a
9 070
12 324
13 347
20 141
23 139
Annual electricity consumption at ET -35 °C AT 32 °C
kWh/a
—
—
—
—
—
Nominal operating current at ET -10 °C MT / -30 °C LT AT 32 °C
and 230 - 400 V 50 Hz
A
5,0
6,9
7,2
14,8
15,2
Maximum operating current (in the most loaded phase at
230 - 400 V 50 Hz)
A
7,2
10,1
9,8
20,5
22,6
Maximum power consumption
kW
3,7
5,6
5,4
9,3
10,1
mm
1 106 x 559 x 461
1 140 x 758 x 439
1 280 x 963 x 439
1 420 x 963 x 439
1 322 x 1 493 x 475
Dimensions
WxHxD
Weight
kg
94
110
140
175
231
Sound level at 10 m
dB(A)
39,0
40,0
41,0
40,0
44,0
Fans x diameter
mm
1x450
1x630
1x630
1x710
2x630
Air flow
m³/h
3 850
6 150
6 150
6 920
11 150
Fan static pressure
Pa
Fan power supply
V / ph / Hz
Fan power consumption
Nominal fan amperage
Condenser
N/A
N/A
N/A
N/A
N/A
200 - 277 / 1 / 50
200 - 277 / 1 / 50
200 - 277 / 1 / 50
200 - 277 / 1 / 50
200 - 277 / 1 / 50
W
170
220
220
280
2x230
A
1,4
1,2
1,2
1,2
2x1
C-7RVN113L0A
C-7RZ320L4ABL
C-8RZ420L4AAL
C-SBS180H00B
C-SBVN373L0B
Model
Compressor
Volumetric flow
m³ / h
1,25 - 7,5
1,7 - 10,4
3,0 - 13,6
5,8 - 19,2
9,2 - 24,6
Rotation range
rps
15 - 90
15 - 90
20 - 90
32 - 100
30 - 80
Full load amperage
A
5,8
8,7
8,8
15,8
16,9
Peak current limit / Locked
rotor amperage
A
17,8 / —
19,2 / —
31,9 / —
40 / —
46 / —
FV68S (PVE)
Current
Oil type
FV68S (PVE)
FV68S (PVE)
FV68S (PVE)
FV68S (PVE)
W
35
40
35
70
90
dm³
0,7 + 0,4
0,7 + 0,4
1,35 + 0,4
2,0 + 0,4
2,0 + 0,6
Suction
Inch
5/8
3/4
7/8
7/8
1 1/8
Liquid
Inch
3/8
3/8
1/2
1/2
5/8
dm³
3,9
7,1
10,0
10
15
Voltage
V / Hz
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
Recommended minimum cable cross-section
mm²
5x2,5
5x2,5
5x2,5
5x4,0
5x6,0
C16
C16
C20
C25
C32
m
40
40
40
40
50
Evaporator above
m
12
12
12
12
12
Evaporator below
m
12
12
12
12
12
Suction
Suction
Suction
Suction
Suction
13
Crankcase heater power consumption
Oil charge
Connections
Liquid receiver
CU power
supply
Recommended minimum protection
Maximum recommended pipe distance
Maximum height distance
Which pipes needs to be insulated
Suction / liquid / both
Recommended insulation thickness
mm
13
13
13
13
Maximum quantity of evaporators connected
Qty.
5
5
7
7
7
Evaporation temperature
Min ~ Max
°C
-15 ~ 5
-15 ~ 5
-15 ~ 10
-15 ~ 10
-15 ~ 10
Ambient temperature
Min ~ Max
°C
-20 ~ 43
-20 ~ 43
-20 ~ 43
-20 ~ 43
-20 ~ 43
43 °C
HIGH EFFICIENCY
COMPRESSOR
34
SUPER QUIET
AMBIENT
TEMPERATURE
AUTOMATIC FAN
CUSTOMIZATION
OPTIONS
BMS