UK IRE REFRIGERATION GEN 25 - Flipbook - Page 46
iCOOL
GENERAL INDEX
iCOOL WCU Series (water cooled condensing units) · R448A / R449A / R134a / R513A
Specifications and capacity tables.
Model
WCU-KRC045M08 WCU-KRC070M08 WCU-KSC100M08 WCU-KSC160M08 WCU-KSC190M08
Compressor
Single
compressor
Single
compressor
Single
compressor
Tandem
compressor
Tandem
compressor
Compatible refrigerants
R448A, R449A,
R134a, R513A
R448A, R449A,
R134a, R513A
R448A, R449A,
R134a, R513A
R448A, R449A,
R134a, R513A
R448A, R449A,
R134a, R513A
PED category
I
I
II
II
II
MT (5,1)
MT (7,2)
MT (10,0)
MT (16,3)
MT (19,6)
A
4,9
7,5
12,1
19,5
24,5
Maximum operating current (in the most loaded phase at 400 V
50 Hz)
A
7,5
11,4
17,9
25,9
30,3
Maximum power consumption
kW
3,5
5,4
8,4
13,6
16,7
mm
1 000 x 705 x 530
1 000 x 772 x 507
1 200 x 775 x 561
1 300 x 874 x 662
1 300 x 874 x 662
Application and nominal cooling capacity
MT/LT (kW)
Nominal operating current at ET -10 °C MT / -30 °C LT AT 32 °C
and 400 V 50 Hz
Dimensions
WxHxD
Weight
kg
90
94
134
219
221
Sound level at 10 m
dB(A)
39,0
42,0
54,0
54,0
54,0
C-7RVN113L0A
C-7RZ320L4ABL
C-SBS180H00B
C-SBS180H00B/
C-SBN303H8G
C-SBS180H00B/
C-SBN453H8G
5,8 - 17,4 / 14,7
Model
Volumetric flow
m³/h
1,25 - 7,5
1,7 - 10,4
5,8 - 17,4
5,8 - 17,4 / 11,6
Rotation range
rps
15 - 90
15 - 90
32 - 90
32 - 90
32 - 90
Full load amperage
A
5,8
8,7
14,7
14,7 / 8,0
15,2 / 11,9
Peak current limit / Locked
rotor amperage
A
11,2 / —
15 / —
34 / —
34 / 48
34 / 66
FV68S (PVE)
Compressor
Current
Oil type
Crankcase heater power consumption
Oil charge
FV68S (PVE)
FV68S (PVE)
FV68S (PVE)
35
40
70
2x70
2x70
dm³
0,7 + 0,4
0,7 + 0,4
2,0 + 0,4
2,0 + 1,7 + 2x0,4
2,0 + 1,7 + 2x0,4
Suction
Inch
5/8
3/4
7/8
1 1/8
1 1/8
Liquid
Inch
3/8
3/8
1/2
5/8
5/8
dm³
3,9
7,1
10,0
14
14
Voltage
V / Hz
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
3x400 / 50 PE+N
(TN-S)
Recommended minimum cable cross-section
mm²
5x2,5
5x2,5
5x4,0
5x6,0
5x10,0
C16
C16
C25
C32
C40
m
40
40
40
50
50
Evaporator above
m
12
12
12
12
12
Evaporator below
m
12
12
12
12
12
Suction
Suction
Suction
Suction
Suction
13
Connections
Liquid receiver
CU power
supply
FV68S (PVE)
W
Recommended minimum protection
Maximum recommended pipe distance
Maximum height distance
Which pipes needs to be insulated
Recommended insulation thickness
mm
13
13
13
13
Maximum quantity of evaporators connected
Qty.
5
5
7
10
10
Evaporation temperature
Min ~ Max
°C
-15 ~ 5
-15 ~ 5
-15 ~ 10
-15 ~ 10
-15 ~ 10
Ambient temperature
Min ~ Max
°C
-20 ~ 43
-20 ~ 43
-20 ~ 43
-20 ~ 43
-20 ~ 43
Inlet
Inch
1/2
1/2
1
1
1
Outlet
Inch
3/4
3/4
1/2
1
1
Plate heat exchanger connections
HIGH EFFICIENCY
COMPRESSOR
44
Suction / liquid / both
BMS
CONNECTIVITY