UK IRE REFRIGERATION GEN 25 - Flipbook - Page 47
iCOOL
REFRIGERATION INDEX
REFRIGERATION
New
2025
Model
WCU-KSC280M08 WCU-KSC400M08 WCU-KRC020L08 WCU-KRC035L08 WCU-KRC050L08 WCU-KSC090L08
Tandem
compressor
Compressor
Tandem
compressor
Single
compressor
R448A,
R448A,
R449A, R134a, R449A, R134a, R448A, R449A
R513A
R513A
II
II
I
Compatible refrigerants
PED category
Single
compressor
Single
compressor
Single
compressor
R448A, R449A
R448A, R449A
R448A, R449A
I
I
II
MT (27,7)
MT (38,0)
LT (2,0)
LT (3,0)
LT (5,4)
LT (8,7)
A
28,7
36,9
3,9
6,1
11,7
18,9
Maximum operating current (in the most loaded phase at 400 V
50 Hz)
A
38,4
51
5,7
8,4
14,9
27,9
Maximum power consumption
kW
20,4
26,6
2,7
3,9
7,0
13,1
mm
1650 x 975 x 649
1860 x 975 x 890
1000 x 705 x 530
1000 x 705 x 530
1000 x 772 x 536
1300 x 705 x 530
Application and nominal cooling capacity
MT/LT (kW)
Nominal operating current at ET -10 °C MT / -30 °C LT AT 32 °C
and 400 V 50 Hz
Dimensions
WxHxD
Weight
kg
316
395
92
92
139
169
Sound level at 10 m
dB(A)
52,0
55,0
39,0
42,0
50,0
55,0
C-SBVN373L0B/
C-SCN603H8T
4CC149NA04/
C-SCN753H8T
Model
Volumetric flow
m³/h
1,25 - 7,5
1,7 - 10,4
5,2 - 18,7
10,0 - 37,6
rps
31 - 80
21 - 75
15 - 90
15 - 90
25 - 90
25 - 72
Full load amperage
A
18,4 / 16,0
26,0 / 19,4
4,4
6,4
10
22,9
Peak current limit / Locked
rotor amperage
A
46 / 80
52 / 96
11,2 / —
15 / —
28 / —
46 / —
FV32S (PVE)
Current
Oil type
FV68S (PVE)
FV68S (PVE)
FV68S (PVE)
FV68S (PVE)
FV68S (PVE)
W
2x90
2x90
35
35
35
2x90
dm³
2,0 + 2,8 + 2x0,6
2x2,8 + 2,0
0,7 + 0,4
0,7 + 0,4
2,1 + 0,4
2,5 + 0,4
Suction
Inch
1 3/8
1 5/8
5/8
7/8
7/8
1 1/8
Liquid
Inch
7/8
7/8
3/8
3/8
3/8
5/8
dm³
14
30
3,9
3,9
7,1
14
Voltage
V / Hz
3x400 / 50
PE+N (TN-S)
3x400 / 50
PE+N (TN-S)
3x400 / 50
PE+N (TN-S)
3x400 / 50
PE+N (TN-S)
3x400 / 50
PE+N (TN-S)
3x400 / 50
PE+N (TN-S)
Recommended minimum cable cross-section
mm²
5x10,0
5x16,0
5x2,5
5x2,5
5x4,0
5x6,0
C50
C63
C16
C16
C25
C32
m
70
70
40
40
40
40
Evaporator above
m
12
12
12
12
12
12
Evaporator below
m
12
12
12
12
12
12
Suction
Suction
Suction
Suction
Suction
Suction
19
Crankcase heater power consumption
Oil charge
Connections
Liquid receiver
CU power
supply
ACC144NA03
Rotation range
Compressor
7,7 - 24,6 / 23,6 10,7 - 39,3/30,3
C-7RVN113L0A C-7RZ320L4ABL C-9RZ580L4AAL
Recommended minimum protection
Maximum recommended pipe distance
Maximum height distance
Which pipes needs to be insulated
Suction / liquid / both
Recommended insulation thickness
mm
13
13
13
19
19
Maximum quantity of evaporators connected
Qty.
10
20
5
5
5
5
Evaporation temperature
°C
-15 ~ 10
-15 ~ 10
-35 ~ 5
-35 ~ -15
-35 ~ -15
-35 ~ -10
Ambient temperature
Plate heat exchanger connections
Min ~ Max
Min ~ Max
°C
-20 ~ 43
-20 ~ 43
-20 ~ 43
-20 ~ 43
-20 ~ 43
-20 ~ 43
Inlet
Inch
1 1/2
1 1/2
3/4
1/2
1/2
1
Outlet
Inch
1
1
3/4
3/4
3/4
1
Accessories for iCOOL WCU Series.
Compressor oil FV68S 2 L.
Compressor oil FV32S 2 L.
CZ-HFC-FV68SL2
CZ-HFC-FV32SL2
HIGH EFFICIENCY
COMPRESSOR
BMS
CONNECTIVITY
45